%6
2SHUDWRUVKDQGERRN
3%6)(('RF/13.03.00
31
Autronica Fire and Security AS
7HVW%0$%0)
,QIRUPWKH)LUH%ULJDGH)LJKWHUVEHIRUHWKHWHVWLVFDUULHGRXW
Select “BMA/BMF” by pressing “2” in the “TEST”-menu.
The following text will appear in the display:
7(672)75$160,66/,1(72),5(%5,*$'(
:+(1&203/(7('35(66µ0(18¶
This function will activate the devices connected to the corresponding outputs.
7HVWIDXOW
Select “FAULT” by pressing “3” in the “TEST”-menu.
The following text will appear in the display:
7(67($57+)$8/7$&7,9(
This test simulate an earth-fault, and is a test of the earth-fault monitoring
function.
An earth-fault message will be given. The earth-fault message will disappear by
resetting the control panel.
When the earth failure test sequence is finished, the next sequence automatically
will start.
The following text will appear in the display:
7(67$''5(66)$8/7$&7,9(
The test process will take 1 minute. It is indicated by appearing dots in the display
for the first half minute. Then the sequence is reversed the next half minute.
When the address fault active test sequence is finished, the next sequence will
automatically start.
The following text will appear in the display:
7(67%$77(5<$&7,9(
This test sequence (which is a real battery load test) lasts for 10 seconds, and will
normally not give any fault message.
When the test battery active sequence is finished, the main menu will appear.
7HVWIDXOW
7HVW%0$%0)