Select “SET ALARM DELAY” function by pressing “3” in the “OUT/IN-
CONTROL”-menu.
The following text will appear in the display:
$/$50'(/$<
(17(5'85$7,21+2856
Enter duration of alarm delay and press
↵
.
Max. duration is 98 hours. By selecting a duration of 99 hours the alarm delay will
last for ever.
7RUHDFKWKLVIXQFWLRQUDSLGO\SUHVV³´ZKHQWKHIURQWGRRULVRSHQHG
The following text will appear in the display:
$/=21(<<<$''5(66;;;
$/$50'(/$<77,0(287WW0,1
YYY is the current zone.
XXX is the current address.
tt is the duration of timeout.
When the alarm delay is activated, a alarm delay (T1) function will hold the
controlling of sounders and BMA-circuit. (Fire Brigade/Fighters).
If the alarm is confirmed within the alarm delay (T1) by operating the
“SILENCE/RESOUND SOUNDERS” button, an additional alarm delay (T2) will
be activated.
The following text will appear in the display:
$/=21(<<<$''5(66;;;
$/$50'(/$<77,0(287WW0,1
When the “SILENCE/RESOUND SOUNDERS” button is operated within
timeout (T2), the following text will appear in the display:
$/=21(<<<$''5(66;;;
$/$50,69(5,),('
YYY is the current zone.
XXX is the current address
However, if the “SILENCE/RESOUND SOUNDERS” button is not operated
within timeout of T1 and T2, the alarm is automatically released.