Planning
Technical Handbook, AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339, Revision 1, 2020-06-29,
Autronica Fire and Security
Page 41
8. Planning
8.1 Reference to National/Local Regulations
Local regulations apply.
Make sure to meet the requirements of national/local regulations.
Anyone installing, commissioning, using or maintaining Autronica Fire
and Security products must follow the instructions in this handbook
and other applicable handbooks or standards in order to ensure safe
operation of the products and services.
Autronica Fire and Security is not responsible for ensuring that the
products are installed according to national/local regulations.
8.2 Enviromental Requirements
8.2.1 Location / Required Space
Local regulations apply. Autronica Fire and Security guidelines are
listed below.
Refer to Area Coverage and Monitoring Distance in chapter 8.3
Protector bases must be mounted on a level surface in the ceiling
Protectors must be mounted minimum 0,5 meters from any wall
Protectors must be mounted at least 1 meter away from air-
conditioning inlets, ventilator other equipment that causes
airflow
Protectors must not be mounted in steady airflow
Stairwells must always be equipped with protectors on the top
floor. Additionally, there must be protectors on at least every
third floor
Avoid mounting on steps, concrete ribs, etc.