4. Technical Specifications
4.1 Protector and Base
Technical Specifications
Dimensions
Height = 45,3mm (49,6mm including base)
Diameter = 113,6mm
Weight
127g (172g including base)
Housing material
PC ABS
Colour
White: RAL9010
Black: RAL9005
Customized colours will be available on request
Ingress protection
IP44D (IP55 when used with conduit box)
Current consumption base - Average
60µA
Current consumption protector - Average
60µA
Current consumption – Normal (base +
protector)
120µA
Current consumption – alarm indicator
(Red LED indicator ON)
2,1mA
Current consumption – fault indicator
(Yellow LED indicator ON)
2,8mA
Protector Base
V-100 Standard base
V-110 standard base with SIL2 approval, with remote LED output
V-120 EX base with SIL2 approval, without remote LED output
System compatibility
V-430: AutroSafe system version 4.11 and higher
V-530: AutroSafe system version 4.11 and higher
Operating temperature
-30 to +70
C (+80
C when configured as heat detection only)
Storage temperature
Maximum 85
C
Operating humidity
10% - 95% RH (non-condensing)
Cable requirements
Minimum 0,14mm
2
/AWG26
Maximum 2,5mm
2
/AWG14
Country of origin
Norway
EN54 approved
Heat
EN54-5:2017
Optical Smoke
EN54-7:2018
Multi sensor
EN54-29:2015
Short circuit Isolator (Base)
EN54-17:2005