APT3100
Smart Pressure Transmitter
Operation Manual M3100-EO1G
12
Duon System Co.,Ltd.
z
Nonsparking Equipment for class I, Zone 2 : Ex nA IIC T4
z
Enclosure : Type 4X, IP66
z
Ambient Temperature : -20 to 60
°
C
z
Supply Voltage : 42V dc max.
z
Output Signal : 4 to 20mA + HART
®
z
Electrical Connection : 1/2” – 14 npt Female
z
List of standards that product compiles with,
z
specifically E60079-1 end E60079-15.
z
The warning: “WARNING-EXPOLSION HAZARD-SUBSTITUTION OF
z
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2” or equivalent.
Note 2. Installation
z
All wirings have to be installed by the final revision of Canadian Electrical Code.
z
Input equipment of cable should be certified by explosionproof and be adjusted to using
conditions.
z
Wire connection that is no use has blocked by available plugs.
z
All screws of cable tube have to be set the 5 teeth.
z
Method of cable connection has to be followed by Class I, Division 1 in spite of its length.
z
All cable tubes have to be sealed with 50 cm from housing.
z
Installation in Division 2 zone does not need to be sealed.
z
In assembly of sensor module and housing, over 7 screws have to be set the teeth and be
fixed in order not to spin.
Note 3. Operation
z
Be cautious of the CAUTION attached to transmitter.
CAUTION IN EXPLOSIVE ATMOSHERE DO NOT OPEN WHILE ENERGIZED
z
Wait one minute after power-disconnection, before opening the enclosure.
z
Take care not to generate mechanical spark when access to the instrument and
peripheral devices in hazardous location.
Note 4. Maintenance and Repair
z
The instrument modification or parts replacement by other than authorized
representative of DUON System is prohibited and will void CSA Explosionprooof /
Flameproof.
2-10-4. FM Certification
HAZARDOUS LOCATION ELECTRICAL EQUIPMENT
APT3100-abclgjkm. Pressure Transmitters.
APT3100-abcdefgijklm. Pressure Transmitters.
APT3100-abcdfghiklm. Pressure Transmitters.
XP/I/1/ABCD/T6 Ta = 60
℃
;