16
Operation
► Check whether the unit operates correctly�
> The LED lights when the switching output is switched�
> The detected distance value is shown in the display�
8.2 Electronic lock
The unit can be locked electronically to prevent unintentional settings� On delivery
the unit is not locked�
Locking
► Make sure that the unit is in the normal operating mode�
► Keep
[+]
+
[-]
pressed, until
[Loc]
is displayed�
> The unit is locked�
Unlocking
► Keep
[+]
+
[-]
pressed, until
[uLo]
is displayed�
> The unit is unlocked�
8.3 Fault indication
Display
Possible cause
Switching output
[Hno]
[Hnc]
[++]
Too much light,
e�g� reflective surfaces
ON
OFF
[--]
Not enough light, no object
OFF
ON
[nEA]
Object to be measured outside the
measuring range < 30 mm
ON
OFF
[FAr]
Object to be measured outside the
measuring range > 2500 mm
OFF
ON
[ERP]
Plausibility (e�g� object too fast)
unchanged
unchanged
[SC]
Short circuit at the switching output