2 Modbus Mapping Table
18
© Copyright Reserved Autonics Co., Ltd.
2
Modbus Mapping Table
2.1
Read Coil Status.(Func 01) /
Force Single Coil(Func 05)
[Func: 01/05, R/W: R/W]
No(Address)
Parameter
Description
Setting range
Unit Factory
default Note
000001(0000)
Enable AUX Output
Auxiliary output ON/OFF 0:
OFF
, 1:
ON
-
1
000002(0001)
Enable Comp Output Compressor output
ON/OFF
0:
OFF
, 1:
ON
-
1
000003(0002)
Parameter Initialize
Parameter reset
0:
NO
, 1:
YES
-
0
000004 to
000050
Reserved
2.2
Read Input Status.(Func 02)
[Func: 02, R/W: R]
No(Address)
Parameter
Description
Setting range
Unit Factory
default Note
100001(0000)
℃
indicator
Unit indicator
0: OFF, 1: ON
-
-
100002(0001)
℉
indicator
Unit indicator
0: OFF, 1: ON
-
-
100003(0002) COMP indicator
Compressor output
indicator
0: OFF, 1: ON
-
-
100004(0003) DEF indicator
Defrost output indicator 0: OFF, 1: ON
-
-
100005(0004) FAN indicator
Evaporation-fan output
indicator
0: OFF, 1: ON
-
-
100006(0005) AUX indicator
Auxiliary output indicator 0: OFF, 1: ON
-
-
100007(0006)
▲
indicator
Deviation indicator
0: OFF, 1: ON
-
-
100008(0007)
■
indicator
Deviation indicator
0: OFF, 1: ON
-
-
100009(0008)
▼
indicator
Deviation indicator
0: OFF, 1: ON
-
-
100010(0009) DI input
Digital input
0: OFF, 1: ON
-
-
100011 to
100050
Reserved
Summary of Contents for TF3 Series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd 1 USER MANUAL For COMMUNICATION ...
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd ...
Page 28: ...2 Modbus Mapping Table 28 Copyright Reserved Autonics Co Ltd ...
Page 29: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 29 MCT TF3C1 V1 1 1701US ...