2 Modbus Mapping Table
24
© Copyright Reserved Autonics Co., Ltd.
2.4.5
Parameter 3 Setting Group
No(Address)
Parameter Description
Setting range
Factory
default Unit
Note
400201(00C8)
DEF
Defrost method & operation
0:
hTM
, 1:
gTM
, 2:
hTT
, 3:
gTT
0
-
400202(00C9)
DIN
Defrost cycle
0
to
24
,
0
to
100
4
Hour
400203(00CA)
rDI
Real-time defrost cycle
0:
OFF
, 1:
ON
0
-
400204(00CB)
DH1
Real-time defrost cycle 1: hour
0
to
23
, 24:
OFF
24
Hour
400205(00CC)
DM1
Real-time defrost cycle 1: min
0
to
59
, 60:
OFF
60
Min
400206(00CD)
DH2
Real-time defrost cycle 2: hour
0
to
23
, 24:
OFF
24
Hour
400207(00CE)
DM2
Real-time defrost cycle 2: min
0
to
59
, 60:
OFF
60
Min
400208(00CF)
DH3
Real-time defrost cycle 3: hour
0
to
23
, 24:
OFF
24
Hour
400209(00D0)
DM3
Real-time defrost cycle 3: min
0
to
59
, 60:
OFF
60
Min
400210(00D1)
DH4
Real-time defrost cycle 4: hour
0
to
23
, 24:
OFF
24
Hour
400211(00D2)
DM4
Real-time defrost cycle 4: min
0
to
59
, 60:
OFF
60
Min
400212(00D3)
DH5
Real-time defrost cycle 5: hour
0
to
23
, 24:
OFF
24
Hour
400213(00D4)
DM5
Real-time defrost cycle 5: min
0
to
59
, 60:
OFF
60
Min
400214(00D5)
DH6
Real-time defrost cycle 6: hour
0
to
23
, 24:
OFF
24
Hour
400215(00D6)
DM6
Real-time defrost cycle 6: min
0
to
59
, 60:
OFF
60
Min
400216(00D7)
DH7
Real-time defrost cycle 7: hour
0
to
23
, 24:
OFF
24
Hour
400217(00D8)
DM7
Real-time defrost cycle 7: min
0
to
59
, 60:
OFF
60
Min
400218(00D9)
DH8
Real-time defrost cycle 8: hour
0
to
23
, 24:
OFF
24
Hour
400219(00DA)
DM8
Real-time defrost cycle 8: min
0
to
59
, 60:
OFF
60
Min
400220(00DB)
DET
Defrost time
1
to
100
30
Min/Sec
400221(00DC)
PdD
Pump down delay time
)00
to
(59
(
0
min.
00
sec. to
9
min.
59
sec.)
0.00
Min.Sec
400222(00DD)
DrT
Defrost end delay time
)00
to
(59
(
0
min.
00
sec. to
9
min.
59
sec.)
1.00
Min.Sec
400223(00DE)
EDT
Defrost end temperature
-40
to
99
4
℃
-40
to
212
℉
400224(00DF)
dHY
Defrost hysteresis
1
to
5
(
)5
to
%0
)
1
℃
2
to
10
(
@0
to
1)0
)
℉
400225(00E0)
pDE
Defrost when power ON
0:
OFF
, 1:
ON
0
-
400226(00E1)
dDE
Defrost delay when power
ON/manual defrost
0
to
60
0
Min
400227(00E2)
dGR
Defrost group
0:
OFF
, 1:
MAS
, 2:
SLV
0
-
400228(00E3)
pDC
Parameter copy
0:
OFF
, 1:
ON
0
-
400229(00E4)
dPR
Prior defrost selection
0:
OFF
, 1:
ON
0
-
400230(00E5)
uDE
Defrost time unit
0:
HGH
, 1:
LOW
0
-
400231(00E6)
AdD
Alarm delay after defrost/door
open
0
to
24
1
Hour
400232(00E7)
tDE
Temperature display during
defrosting
0:
OFF
, 1:
ON
0
-
Summary of Contents for TF3 Series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd 1 USER MANUAL For COMMUNICATION ...
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd ...
Page 28: ...2 Modbus Mapping Table 28 Copyright Reserved Autonics Co Ltd ...
Page 29: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 29 MCT TF3C1 V1 1 1701US ...