-|Transparent Guide|-
Unit Descriptions
2
2
1
3
1. Temperature display part (Red)
•
Run mode: Displays PV (Present value)
•
Setting
mode: Displays parameter
name
3. Input key
2. Indicator
Display
Name
Description
▲
■
▼
Deviation
Displays deviation of PV (Present value) based on SV (Setting
value).
COMP
Compressor
output
Turns ON when compressor output is ON.
Flashes when output is OFF or protection operation.
DEF
Defrost output
Turns ON when defrost output is ON.
Flashes when defrost
delay operation.
FAN
Evaporation-fan
output
Turns ON when evaporator-fan output is ON.
Flashes when evaporator-fan
output
delay operation.
℃, ℉
Temperature unit
Displays selected unit (parameter).
Display
Name
[MD]
Mode key
[▲], [▼]
Setting value control key
Mode Setting
RUN
[MD]
→
SV setting
Change value: [▼], [▲]
Save: [MD] or no key
input over 60 sec
→
RUN
[MD] 3 sec
→ Parameter 1 group
[MD] over 3 sec
→
[MD] 5 sec
→ Parameter 2 group
[▲] over 3 sec
→
Manual defrost
execution
[▼] over 3 sec
→
Auto when
conditions are
satisfied
→
Loop break alarm
(LBA)
Release
: [▼] + [▲] over 3
sec
→
Parameter Setting
•
Some parameters are activated/deactivated depending on the model or setting of
other parameters. Refer to the descriptions of each item.
•
[MD] key: Move to next item after saving / Return to RUN mode after saving (≥ 3 sec)
[▲], [▼] key: Select parameter / Change setting value
■ Parameter 1 group
Parameter
Display
Default
Setting range
Condition
1-1
Hysteresis
HYS
!0
0.5 to 5.0 ℃, 2 to 50 ℉
-
1-2 Defrost
cycle
DIN
4
0 (manual defrost) to 24 hours
-
1-3
Defrost Time
DET
30
0 to 59
min
-
1-4
LBA time
LBA
0
0 to 999 sec
-
1-5 Input correction
INB
)0
-10.0 to 10.0 ℃, -18 to 18 ℉
-
1-6 SV low limit
LSV
-4)0
Refer to 'Input Type and Using
Range.
-
1-7 SV high limit
HSV
9(9
Parameter
Display
Default
Setting range
Condition
2-1
Compressor start
up delay and
restart delay time
SDL
)20
0 min 10 sec
to 9
min
59
sec
-
2-2 Compressor
Min.
operation time
ONT
)20
0 min 10 sec to 5 min 00 sec
-
2-3
Defrost end delay
and evaporator-
fan delay time
DRP
!00
0 min 00 sec to 5 min
59
sec
-
2-4 Evaporation-fan
operation mode
FAN
EF1
Refer to '
Evaporation-fan
Operation
Mode'
-
2-5
Error, compressor
operation cycle
CLE
0
0 to 20 min
-
2-6 Error, compressor
duty ratio
DUT
50
0 to 100%
2-5
Error,
compressor
operation
cycle: >
0
2-7 Temperature unit
UNT
?C
℃, ℉
-
2-8 Lock
LOC
OFF
OFF: No lock
LC.1: Parameter 2 group
lock
LC.2: Parameter 1, 2 group
lock
LC.3: Parameter 1, 2 Group, SV
setting mode lock
-
■ Parameter 2 group
Evaporation-fan Operation Mode
• Output does not turn ON but the dedicated indicator flashes at the compressor,
defrost, evaporator-fan delay period (■).
Power
ON
Start-up
delay
Compressor
operation
Compressor
operation
Compressor
operation
Defroster
operation
Defrost
time
Defrost
time
Defrost
time
Defrost
cycle
Defrost
cycle
Defrost
cycle
Defroster
operation
Defroster operation period
Defrost
end
delay
Defrost
end
delay
Defroster operation period
Comp
-ressor
Defrost
EF1
EF2
EF3
EF4
EF5
Evaporator-fan delay
Evaporator-fan delay
Evaporator-fan delay
Parameter
Description
EF1
When compressor operates, evaporator-fan also operates. When compressor
operation is finished, evaporator-fan also operation turns OFF.
EF2
When compressor operates, evaporator-fan operates after the set evaporator-
fan start-up delay time. When compressor operation is finished, evaporator-fan
operation turns OFF. (regardless of defroster operation)
EF3
When power turns ON, evaporator-fan operates. When defroster operates,
evaporator-fan stops. (regardless of compressor operation)
EF4
Evaporator-fan operates only when operating compressor or defrost. Evaporator-
fan stops when compressor and defroster stops. (for above zero temperature
control)
EF5
Evaporator-fan operates from power ON to power OFF. (regardless of compressor,
defroster operation)