-|Transparent Guide|-
Product Components
• Product
• Instruction manual
• Bracket ×2
• NTC sensor (5 kΩ) × 1
•
Make sure that power supply voltage reaches to the rated voltage within 2 sec after
supplying power.
•
Do not wire to terminals which are not used.
•
This unit may be used in the following environments.
- Indoors (in the environment condition rated in ‘Specifications’)
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II
Display Description
Troubleshooting
OPN
ERR and error display are cross flashed when input sensor
is disconnected or sensor is not connected.
Check input sensor
status.
HHH
ERR and error display when if the input value is above the
input range.
When input is within the
rated input range, this
display disappears.
LLL
ERR and error display are cross flashed if the input value is
below the input range.
LBA
ERR and error display are cross flashed when input sensor
is normal but freezer temperature does not change more
than 1.0 ℃ (2 ℉) during loop break alarm (LBA) time.
Check setting method.
Errors
• When an error occurs, the compressor is operated to protect the control object according to the 'Error,
compressor operation cycle/duty ratio' parameter setting values.
Input Type and Using Range
Input type
Using range (℃)
Using range (℉)
Thermistor
5 kΩ
-40.0 to 99.9
-40 to 212
RTD
01)
DPt100 Ω
-99.9 to 99.9
-148 to 212
01) RTD input type is option.
• Allowable line resistance per wire: ≤ 5 Ω
Specifications
Series
TC3YF Series
Power supply
AC
100 - 240 VACᜠ 50/60 Hz
DC
12-24 VDCᜡ
Allowable voltage range
90 to 110% of rated voltage
Power consumption
AC
≤ 4 VA
DC
≤ 8 W
Sampling period
500 ms
Input specification
Refer to 'Input Type and Using Range'.
Display accuracy
At room temperature
(23 ±5 ℃): (PV ±0.5% or 1 ℃ higher one) rdg ±1 digit
Out of room temperature range: (PV ±0.5% or 1 ℃ higher one) rdg ±1 ℃
Control
output
Compressor
(COMP)
250 VACᜠ 5 A 1a, 30 VDCᜡ 5 A 1a
Defrost
(DEF)
250 VACᜠ 10 A 1a
Evaporation-fan
(FAN)
250 VACᜠ 5 A 1a, 30 VDCᜡ 5 A 1a
Display type
7 segment (red), LED type
Control type
ON/OFF Control
Hysteresis
0.5 to 5.0 ℃, 2 to 50 ℉
Relay
life cycle
Mechanical
≥ 20,000,000 operations
Electrical
• COMP, DEF: ≥ 50,000 operations (load resistance: 250 VACᜠ 5 A)
• FAN ≥ 100,000 operations (load resistance: 250 VACᜠ 10 A)
Dielectric strength
Between all external terminals and case: 2,000 VACᜠ 60 Hz for 1 min
Vibration
0.75 mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X,
Y, Z direction for 2 hours
Malfunction vibration
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y,
Z direction for 10 min
Insulation resistance
≥ 100 MΩ (500 VDCᜡ megger)
Noise immunity
AC
±2 kV square shaped noise (pulse width 1 ㎲) by noise simulator
R-phase, S-phase
DC
±500 V square shaped noise (pulse width 1 μs) by noise simulator
R-phase, S-phase
Memory retention
≈ 10 years (non-volatile semiconductor memory type)
Ambient temperature
-10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity
35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Protection structure
IP65 (Front panel, IEC standards)
Approval
AC
ᜧ ᜣ (Except RTD option models) ᜫ
DC
ᜫ
Unit weight (packaged)
≈ 143 g (≈ 229 g)
Ordering Information
This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website .
T
C
3
Y
F
-
❶
❷
R
❶ Control output for refrigeration
1:
Compressor
2:
Comp Defrost
3:
Comp D
Evaporation-fan
❷ Power supply
1: 12-24 VDCᜡ
4: 100-240 VACᜠ 50/60 Hz
Installation Method
Mount the product to panel with bracket, fasten the bolts by using screwdriver..
Crimp Terminal Specifications
•
Unit: mm, Use the crimp terminal of follow shape.
6
≤ 1.9
≤ 4.0
Wire ferrule
Connections
B'
RTD
SENSOR
NTC
SOURCE
100-240 VACᜠ
4 VA 50/60 Hz
12-24 VDCᜡ 8 W
FAN OUT:
250 VACᜠ 5 A
30 VDCᜡ 5 A
RESISTIVE LOAD
DEF OUT:
250 VACᜠ 10 A
RESISTIVE LOAD
COMP OUT:
250 VACᜠ 5 A
30 VDCᜡ
5 A, 1a
RESISTIVE LOAD
B
A
-
1
-
2
-
3
-
4
-
5
-
6
-
7
-
8
-
9
-
10
-
11
Dimensions
•
Unit: mm, For the detailed drawings, follow the Autonics website.
30
77
6
36
72
■
Panel cut-out
■
Bracket
≥ 91
≥ 40
68
+0.7
0
31.5
+0.5
0
14.5
9
4
12
60
■
NTC sensor
(5kΩ)
AWG22
TPE lead wire
Soldering
≤
5
6 ±0.2
≤ 15
2000 ±50
5±1