background image

18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002

www.autonics.com  |  +82-2-2048-1577  |  [email protected]

-|Transparent Guide|-

Specifications

  

■ Input

Rated input voltage range

10 - 30 VDCᜡ

90 - 240 VACrmsᜠ 

(50 / 60 Hz)

Allowable input voltage range 

9 - 32 VDCᜡ

85 - 264 VACrmsᜠ (50 / 60 Hz)

Max. input current

15 mA

22 mA

Operating voltage

≥ 9 VDCᜡ

≥ 85 VACrmsᜠ

Releasing voltage

≤ 1 VDCᜡ

≤ 10 VACrmsᜠ

Operating 

time

Zero cross 

turn-on

≤  0.5 cycle of load power

+ 1 ms

≤  2 cycle of load power

+ 1 ms

Random turn-on  ≤ 1 ms

-

Releasing time

≤  0.5 cycle of load power

+ 1 ms

≤  2 cycle of load power

+ 1 ms

  

■ Output

Rated load voltage range

24 - 240 VACrmsᜠ (50 / 60 Hz)

Allowable load voltage range 

24 - 264 VACrmsᜠ (50 / 60 Hz)

Rated

load current

Resistive load

 

(AC-51)

01)

10 Arms

15 Arms

20 Arms

25 Arms

40 Arms

Min. load current

0.15 Arms 0.15 Arms 0.2 Arms

0.2 Arms

0.5 Arms

Max. 1 cycle surge current

(60 Hz)

160 A

160 A

250 A

250 A

400 A

Max. non-repetitive surge 

current (I

2

t, t = 8.3 ms)

130 A

2

s

130 A

2

s

300 A

2

s

300 A

2

s

910 A

2

s

Peak voltage (non-repetitive)

600 V

Leakage current (Ta = 25 ℃)

≤ 10 mArms (240 VACᜠ/60 Hz)

Output ON voltage drop [Vpk]

(max. load current)

≤ 1.6 V

Static off state dv/dt

500 V/μs

Rated load voltage range

48 - 480 VACrmsᜠ (50 / 60 Hz)

Allowable load voltage range 

48 - 528 VACrmsᜠ (50 / 60 Hz)

Rated

load current

Resistive load

 

(AC-51)

 01)

10 Arms

15 Arms

20 Arms

25 Arms

40 Arms

Min. load current

0.5 Arms

Max. 1 cycle surge current

(60 Hz)

300 A

300 A

500 A

500 A

500 A

Max. non-repetitive surge 

current (I

2

t, t = 8.3 ms)

350 A

2

s

350 A

2

s

1000 A

2

s

1000 A

2

s

1000 A

2

s

Peak voltage (non-repetitive)

1200 V (zero cross turn-on), 1000 A (random turn-on)

Leakage current (Ta = 25 ℃)

≤ 10 mArms (480 VACᜠ/60 Hz)

Output ON voltage drop [Vpk]

(max. load current)

≤ 1.6 V

Static off state dv/dt

500 V/μs

 01)  AC-51 is utilization category at IEC60947-4-3.

  

■ Overheat prevention function

Overheat prevention function is when SSR internal temperature is overheated, the load 

output is cut off to prevent internal device damage and also the alarm indicator and alarm 

output turn ON.

The operating temperature of the overheat prevention function may vary depending on the 

external environment, product configuration, and load current.

Rated input voltage range 10 - 30 VDCᜡ

90 - 240 VACrmsᜠ

(50 / 60 Hz)

Load voltage

≤ 30 VDCᜡ

≤ 30 VDCᜡ

Load current

≤ 50 mA

≤ 50 mA

Turn-off time

≤ 50 ms

≤ 100 ms

• 

Alarm output is only for the rated load current 40 A model, in case of the rated load current 10 / 15 / 20 / 25 A 

model, the alarm indicator turns ON without the alarm output.

• 

To clear alarm, cut off the input signal during over the alarm output return time at the rated ambient temperature.

  

■ General specifications

Dielectric strength (Vrms)

Input-output: 2500 VACᜠ 50 / 60 Hz for 1 min

Input / output-case: 4000 VACᜠ 50 / 60 Hz for 1 min

Insulation resistance

Input-output, input/output-case

: ≥ 100 MΩ (500 VDCᜡ megger)

Indicator

Input indicator (green), alarm indicator (red)

Vibration

0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) 

in each X, Y, Z direction for 1 hour

Vibration (malfunction)

0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) 

in each X, Y, Z direction for 10 min

Shock

300 m/s

(≈ 30 G) in each X, Y, Z direction for 3 times

Shock (malfunction)

100 m/s

(≈ 10 G) in each X, Y, Z direction for 3 times

Ambient temperature

 01)

-30 to 70 ℃, storage: -30 to 100 ℃ (no freezing or condensation)

Ambient humidity

45 to 85 %RH, storage: 45 to 85 %RH (no freezing or condensation)

Input terminal 

connection

≥ 1×0.5 mm

(1×AWG 20), 

 

≤ 1×4 mm

(1×AWG 12) or ≤ 2×1.5 mm

(2×AWG 16)

Output terminal 

connection

 02)

Rated load current 10 / 15 / 20 / 25 A

:  ≥ 1×0.75 mm

2

 (1×AWG 18), 

 

≤ 1×6 mm

2

 (1×AWG 10) or ≤ 2×2.5 mm

2

 (2×AWG 14)

Rated load current 40 A

:  ≥ 1×1.5 mm

2

 (1×AWG 16), 

 

≤ 1×16 mm

2

 (1×AWG 6) or ≤ 2×6 mm

2

 (2×AWG 10)

Input terminal 

fixed torque

0.75 to 0.95 N m

Output terminal 

fixed torque

Rated load current 10 / 15 / 20 / 25 A: 1.0 to 1.35 N m

Rated load current 40 A: 1.6 to 2.2 N m

Approval

ᜢ ᜧ ᜫ

Weight (packaged)

Rated load current 10 / 15 / 20 / 25 A: ≈ 192 g (≈ 270 g)

Rated load current 40 A: ≈ 372 g (≈ 468 g)

 01)  See the 'SSR Derating Curve' because the capacity of the rated load current is differ depending on the ambient 

temperature.

 02)  Connect the wire met the capacity of the load current to the output terminal.

SSR Derating Curve

• 

Be aware that the ambient temperature and the derating curve is different by the 
rated input voltage when using the product..

•    

Since the effectiveness of the heat radiation is decreased when SSRs are installed 

closely, be sure to supply less than 50 % of the rated load current.

• 

SSR derating curves obtained approval from the UL certification authority.

  

■ SRHL1-1210 / 1410 / 1410R / 4210 / 4410

Lo

ad curr

ent [A]

10

40

25

20

15

6

0

Ambient temperature [℃]

10 20

30

40

50 60

70

80

90

0

  

■ SRHL1-1215 / 1415 / 1415R / 4215 / 4415

Lo

ad curr

ent [A]

10

40

25

20

15

6

0

Ambient temperature [℃]

10 20

30

40

50 60

70

80

90

0

  

■ SRHL1-1220 / 1420 / 1420R / 4220 / 4420

Lo

ad curr

ent [A]

Ambient temperature [℃]

10 20

30

40

50 60

70

80

90

0

10

40

25

20

15

8

0

6

SRHL1-1220/1420/1420R/4220

SRHL1-4420

  

■ SRHL1-1225 / 1425 / 1425R / 4225 / 4425

SRHL1-1225/1425/1425R/4225

SRHL1-4425

Lo

ad curr

ent [A]

10

40

25

20

15

8

0

Ambient temperature [℃]

10 20

30

40

50 60

70

80

90

0

6

  

■  SRHL1-1240 / 1440 / 1440R / 4240 / 4440

Lo

ad curr

ent [A]

Ambient temperature [℃]

10 20

30

40

50 60

70

80

90

0

10

40

25

20

15

9
0

Reviews: