background image

-|Transparent Guide|-

Product Components

• Product

• Instruction manual

Dimensions

• 

Unit: mm, For the detailed drawings, follow the Autonics website.

 

A

Input indicator (green)

B

Alarm indicator (red)

• 

When installing to the panel, tightening the screw with a torque of 1.8 to 2.5 N m.

  

■ Rated load current 10 / 15 / 20 / 25 A

97.6

29

Ø 4.5

3.5

76

90

100

4.5

3.5

22.5

A

B

  

Rated load current 40 A

97.6

29

76

90

100

3.5

4.5

3.5

44.8

Ø 4.5

A

B

  

Panel cut-out

2-M4

90

7

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website.  

SRHL1

-

❶ Rated input voltage

1: 4 - 30 VDCᜡ
4: 90 - 240 VACᜠ

❸ Rated load current

Number: Rated load current (unit: A)

❷ Rated load voltage

2: 24 - 240 VACᜠ
4: 48 - 480 VACᜠ

❹ Function

No-mark: Zero cross turn-on
R: Random turn-on

Cautions during Installation

While supplying power to the load or right after turning off the power of the load,

do not touch the body and heat sink. Failure to follow this instruction may result in

burn due to high temperature of the surface.

Caution High Temperature 

  

■ Spacing

• When installing multiple SSRs, be sure to keep space between SSRs for heat 

radiation.

• When installing SSRs horizontally (input part and output part on the same height),

 

be sure to supply less than 50 % of the rated load current.

Panel

Panel

100

100

20

  

■ DIN rail mounting

• For attachment, hang the upper part of the Rail lock on the rear of the product to 

the DIN rail, and push the product toward the DIN rail. 

• For detachment, Press the product down, and pull it forward. 

  

■ Grounding

• Ground the DIN rail. 

Connections

• 

Alarm output terminal 

 is for the rated load current 40 A model only.

Input power

(DC, AC)

Load power

(AC)

SSR

A1+

2/T1

A2-

1/L1

Rapid fuse

AL+

AL-

Load

Load

Output

Input

Alarm output

Cautions for Wiring 

• 

Unit: mm, When connecting the wire to the terminal, use the round crimp terminal.

Size

Input

Output

Rated load current

10 / 15 / 20 / 25 / 40 A

10 / 15 / 20 / 25 A

40 A

a

≥ 3.5 mm

≥ 4.0 mm

≥ 5.0 mm

b

≤ 7.0 mm

≤ 9.0 mm

≤ 12.0 mm

a

b

Reviews: