background image

 

I N S T R U C T I O N   M A N U A L

 Indicator (MP5M- N)

 

Specifications

 

Connections

1: Setting range will vary depending on the decimal point.

2: The weight includes packaging. The weight in parenthesis is for unit only.

Environment resistance is rated at no freezing or condensation. 

Model

MP5M-2N

MP5M-4N

MP5M-21

MP5M-41

MP5M-22

MP5M-42

Indicator

High-limit setting

High/Low-limit setting

Display method

7-segment LED (zero blanking method)

Character size

W4×H8mm

Display range

-19999 to 99999

Power 

supply

AC voltage

100-240VAC  50/60Hz

AC/DC voltage 24VAC  50/60Hz, 24-48VDC

Power 

consumption

AC voltage

Max. 9VA (100-240VAC  50/60Hz)

AC/DC voltage Max. 6.5VA (24VAC  50/60Hz), Max. 5W (24-48VDC )

Permissible voltage range 90 to 110% of rated voltage
External power supply

Max. 12VDC

 

±10% 80mA

Input frequency

·

Solid state input 1: Max. 50kHz (pulse width: min. 10

)

·

Solid state input 2: Max. 5kHz (pulse width: min. 100

)

 

For F7, F8 operation mode, max. 1kHz (pulse width: min. 500

)

·

Contact input: Max. 45Hz (pulse width: min. 11ms)

Input method

[Voltage Input]  High: 4.5-24VDC

, Low: 0-1VDC, input impedance: 3.9kΩ

[No-voltage Input]  

Short-circuit impedance: Max. 80Ω, Residual voltage: Max. 1VDC, 

Open-circuit impedance: Min. 100kΩ

Measurement range

·Operation 

mode F1, F2, F7, F8

·Operation 

mode F3, F4, F5, F6

·Operation 

mode F9, F10, F11, F14

·Operation 

mode F12, F13

: 0.0005Hz to 50kHz

: 0.01 to max. of each time range

: 0 to 99999

: -19999 to 99999

Measurement accuracy 

(23

±5

)

·Operation 

mode F1, F2, F7, F8

·Operation 

mode F3, F4, F5, F6

: F.S.±0.05%rdg±1-digit

: F.S.±0.01%rdg±1-digit

Display cycle

OFF (for F2, F14 operation mode), 0.05, 0.5, 1, 2, 4, 8 sec (same as update output cycle)

Operation mode

Frequency/Revolutions/Speed (F1), Passing speed (F2), Cycle (F3), 

 

Passing time (F4), Time interval (F5), Time differential (F6), Absolute ratio (F7), 

Density (F8), Length measurement 1 (F9), Interval (F10), Accumulation (F11), 

Addition/Subtraction-individual input (F12), Addition/Subtraction-phase difference 

input (F13), Length measurement 2 (F14)

Prescale function

Direct input method (0.0001×10

-9

 to 9.9999×10

9

)

Hysteresis

-

0 to 9999

1

Main

output

Relay single

-

250VAC  3A resistive load 1c -

Relay dual

-

250VAC  3A resistive load 1a 

×2

NPN open 

collector

Max. 30VDC  100mA

Max. 30VDC  100mA ×2

Memory retention

Non-volatile memory (number of inputs: 100,000 operations)

Insulation resistance

Over 100MΩ (at 500VDC megger)

Dielectric strength

2,000VAC 60Hz for 1 min

Noise immunity

±2kV the square wave noise (pulse width: 1

) by noise simulator 

Vibration

Mechanical

0.75mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 1 hour

Malfunction

0.5mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 10 min

Shock

Mechanical

300m/s² (approx. 30G) in each X, Y, Z direction for 3 times

Malfunction

100m/s² (approx. 30G) in each X, Y, Z direction for 3 times

Relay

life cycle

Mechanical

-

Min. 5,000,000 operations

Electrical

-

Min. 100,000 operations (250VAC 3A resistive load)

Environ-

ment

Ambient temp. -10 to 50

, storage: -20 to 60

Ambient humi.

35 to 85%RH, storage: 35 to 85%RH

Approval

 

 

Weight

2

Approx. 243g (approx. 168g) Approx. 256g (approx. 181g) Approx. 265g (approx. 190g)

 High/Low-limit setting (MP5M- 2)

 

Ordering Information

 

Product Description

Main output (Comparative value output)

N

Indicator

1

Relay single (high-limit)

 

NPN open collector output

2

Relay dual (

high

/low-limit)

 

NPN open collector output

2

24VAC 50/60Hz, 24-48VDC

4

100-240VAC 50/60Hz

M

DIN W72×H72mm

5

99999 (5-digit)

MP

Pulse meter

MP 5 M

4

-

N

Output

Power supply

Size

Digit

Item

 

Dimensions

(unit: mm)

 Panel Cut-out Dimensions

 Bracket

 

Parameter Groups

 

Operation Mode By Parameter Groups

1: Only appears in high/low-limit setting models.      

2: Only appears in high-limit setting models, high/low-limit setting models.  

3: The settings for 

IN-B

 and 

IN-A 

are applied.

4: ( ) F output mode[

OUT-F

] cannot be set.   

5: ( ) setting range: 

OFF

)05

)5

1

2

4

8

Output mode

S mode

H mode

L mode

B mode

I mode

F mode

Parameter

STARD

OVT-;

OVT-L

OVT-B

OVT-I

OVT-F

Comparative output limit

Start compensation timer

 Monitoring delay function by output mode

● Parameter 3 group

● Parameter 2 group

00000

tSEC

10  01

10  01

Decimal point location of display value

Setting range: 

00000

000)0

00)00

0)000

)0000

RUN mode

  DOT

PARa1

PARa2

 tUNT

PScaY

PScbY

99(99

99(99

tMIN

^0000

^0000

 PScaH

 PScbH

PARa3

)05

99999

  DISpT

  COUnB

Setting range

Time unit and range

Prescale mantissa (X) of input A

Setting range: 

)0001

 to 

(9999

   

Prescale mantissa (X) of input B

Setting range: 

)0001

 to 

(9999

Prescale exponent (y) of input A

Setting range: 

10 - 9 

(10

-9

) to 

10  09 

(10

9

)

Prescale exponent (y) of input B

Setting range: 

10 - 9 

(10

-9

) t

o 10  09 

(10

9

)

Setting value of Input B

Setting range: 

1

 to 

99999

 High-limit setting (MP5M- 1)

 

Operation mode F1 to F10 

: Display value HOLD

 Operation mode F11 to F14 

: Display value RESET

Terminal 

input

11-12

RUN 

mode

Parameter 0 group

(Max./Min. monitoring value)

HOLD/RESET

Input

Parameter 1/2/3 group

2 sec

3 sec

RUN mode

  hPEK

  lPEK

`9999

99999

Max. monitoring 

value

Min. monitoring 

value

● Parameter 0 group

2 sec

14.3
11.8

75

67.5

 Min. 91

46

8.3

4

7.3

40.7

68

0.7

  0

68

0.7   0

Min. 91

● Parameter 1 group

ㄹF1

NPnhF

NPnhF

STARD

0001

fDEFY

999(9

999(9

OFF

9(9

STArT

Operation mode

Setting range: 

F1

 to 

F14

Sensor type of 

input A 

Sensor type of 

input B

L comparative output 

limit

Only appears in high/low-limit setting models. 

Start compensation timer function & compensation time

Setting range: 

)0

 to 

9(9

(sec)

 Only appears in high/low-limit setting models. 

Output hysteresis

Setting range: 

0000

 to 

9999

(

the setting range varies depending on the decimal point setting

)

 Only appears in high-limit setting models,  

high/low-limit setting models. 

Auto-zero time for input A

Auto-zero time for input B 

Memory retention

Setting range: 

ㄹㄹON

OFF

 

RUN mode

  MODE

PARa1

  IN-A

  IN-B

  OUT-T

  HYS

 GUARD

AUToA

AUToB

  MEMO

PARa2

PARa3

Parameter Input sensor type

NPnhF

NPN solid state input 1

NPnmF

NPN solid state input 2

NPnlF

NPN contact input

PNphF

PNP solid state input 1

PNpmF

PNP solid state input 2

PNplF

PNP Contact input

Parameter Output mode Parameter Output mode

STARD

S (Standard)

OUT-B

B (Block)

OUT-H

H (High)

OUT-I

I (One-shot)

OUT-L

L (Low)

OUT-F

F (Deflection)

Setting range

2 sec

Output mode

Setting range

3 sec

OFF

Lock

RUN mode

  LOC

PARa1

PARa2

PARa3

Parameter Function

OFF

Unlock

LOc0

Locks all

LOc1

Parameter 1, 2, 3 lock

LOc2

Parameter 2, 3 lock

LOc3

Parameter 3 lock

2 sec

3 sec

Model

Source

MP5M-21

24-48VDC

24VAC 50/60Hz  

MP5M-22
MP5M-2N
MP5M-41

100-240VAC 

50/60Hz

MP5M-42
MP5M-4N

1:  Operation mode F1 to F10 

: Display value HOLD 

Operation mode F11 to F14 

: Display value RESET

2: 

 

Resetting monitoring value

 

:  Hold the   key for over 2 sec. 

(reset current value)

 Only appears in high/low-limit setting model. 

tSEC 

(sec)

tMIN 

(min)

99(99

 

999.99s

99(99

999.99m

999(9

9999.9s

999(9

 

9999.9m

99999

99999s

99999

99999m

      

Operation 

mode

Parameter

F1

F2

F3

F4

F5

F6

F7

F8

F9

F10 F11 F12 F13 F14

0 group

hPEK
lPEK

1 group

MODE

Appears in all operation modes(F1 to F14).

IN-A
IN-B

OUT-T

HYS

GVARD
AVToA
AVToB

MEMO

2 group

DOT

tUNT

PScaH
PScaY
PScbH
PScbY
DISpT

ㄹCOUnB

3 group

LOC

Appears in all operation modes(F1 to F14).

3

4

1

2

1

5

Display cycle of measurement value 

Setting range: 

)05

)5

1

2

4

(sec)

 Setting range in operation mode F2, F14 

OFF

)05

)5

1

2

4

(sec)

3 sec

 

Setting range:  

)1

 to 

999(9

(sec)

 

The above specifications are subject to change and some models may be discontinued 

without notice. 

Setting range: 

The high-limit setting model(MP5M- 1) does not include the dotted line parts. 

INA

Black

Black

Brown

Blue

+12V

HOLD/

RESET

1

INB

0V

8

1

10

3

12

5

9

2

11

4

13

6

14

7

SOURCE

2

+

-

15

17

16

INA

+12V

HOLD/

RESET

1

CONTACT OUT: 

250VAC 3A 

RESISTIVE LOAD

INB

0V

High

8

1

10

3

12

5

9

2

11

4

13

6

14

7

+

-

SOURCE

2

Black

Black

Brown

Blue

15

17

16

HOLD/

RESET

1

INA

H

L

+12V

CONTACT OUT: 

250VAC 3A 

RESISTIVE LOAD

INB

0V

High Low

8

1

10

3

12

5

9

2

11

4

13

6

14

7

SOURCE

2

+

-

Black

Black

Brown

Blue

15

17

16

1: 

 

Display 

 

Displays current value in RUN mode. 

 

Alternately displays setting parameters and cor-

responding value in SETTING mode. 

2:  

 key

 

In RUN mode, press the key once to check max./

min. value. 

In RUN mode, hold the key for over 2 sec to enter 

parameter groups.  

3:  

 key

 

Select parameter groups, and select or setting 

values in the corresponding parameters.

4:  Output status indicator
5: Thumbwheel switch for HIGH/LOW setting value

Press the  , 

 

keys to select or set the desired value.

Press the 

 key once after changing the setting value, to save the setting value and move to the 

next parameter. 

Hold the 

 key for 1.5 sec at any parameters to return to the select parameter group mode. 

 Hold  the 

 key for 

3 sec to save the setting value and return to RUN mode after changing the 

setting value. 

 If there is no key input for 60 sec while setting the parameters, the new settings are ignored, and the 

unit will return to RUN mode with previous settings. 

 The dotted line parameters may not appear depending on output specifications or other parameter  

settings. Please refer to '  Operation mode by parameter group'. 

1: Each parameter and corresponding setting value will flash alternately every 0.5 sec. 

Flashes 

alternately

1

Flashes 

alternately

1

Flashes 

alternately

1

Flashes 

alternately

1

(  : parameter display,  

X: no parameter display)

  

1

4

3

5

2

72

DRW160446AC

PULSE METER

MP5M SERIES

1.  Fail-safe device must be installed when using the unit with machinery that may cause 

serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, 

ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster 

prevention devices, etc.)

 

Failure to follow this instruction may result in personal injury, fire, or economic loss.

2.  The unit must be installed on a device panel before use.

 

Failure to follow this instruction may result in electric shock.

3.  Do not connect, repair, or inspect the unit while connected to a power source.

 

Failure to follow this instruction may result in electric shock.

4.  Do not disassemble or modify the unit. Please contact us if necessary.

 

Failure to follow this instruction may result in electric shock or fire.

5.  Check the terminal numbers before connecting the power source and measurement input.

 

Failure to follow this instruction may result in fire.

1.  Do not use the unit outdoors.

 

Failure to follow this instruction may result in electric shock or shortening the life cycle of the unit.

 

2.  When connecting the power input or measuring input, make sure to tighten the terminal 

screw bolt above 0.74N•m to 0.90N•m.

 

Contact failure may result in fire.

3.  Use the unit within the rated specifications.

 

Failure to follow this instruction may result in electric shock or shortening the life cycle of the unit.

4.  Do not use loads beyond the rated switching capacity of the relay contact.

 

Failure to follow this instruction may result in insulation failure, contact failure, contact bonding, relay 

damage, or fire.

5.  Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the 

unit.

 

Failure to follow these instructions may result in electric shock or fire.

6.  Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat, 

vibration, and impact may be present.

 

Failure to follow this instruction may result in fire or explosion.

7.  Keep dust and wire residue from flowing into the unit.

 

Failure may result in fire or product malfunction.

8.  Check the polarity of the measurement input contact before wiring the unit.

 

Failure to follow this instruction may result in fire or explosion.

Thank you for choosing our Autonics product.

Please read the following safety considerations before use.

 Safety Considerations

Warning

 

Please observe all safety considerations for safe and proper product operation to avoid hazards.

Safety considerations are categorized as follows.

Warning

 Failure to follow these instructions may result in serious injury or death.

Caution  

Failure to follow these instructions may result in personal injury or product damage.

The symbols used on the product and instruction manual represent the following

 symbol represents caution due to special circumstances in which hazards may occur. 

Caution

Reviews: