6
System Screen
64
© Copyright Reserved Autonics Co., Ltd.
6.7
Set parameter
6.7.1
Filter
This menu is for displaying the set input filter value at SmartStudio.
For input filter setting, refer to ‘SmartStudio user manual’.
Filter value is not set.
Filter value is set at SmartStudio.
No.
Function and operation
①
Displays the set X0 to X7 filter values.
②
Displays the set X8 to XF filter values.
③
Displays inner device to save the set filter value.
When inner device is set, it is able to control filter value as the designated device.
Change M device for using inner device to filter value. Filter value is available from 0 to 63(6bit).
Below table is for actual filter value by filter value. Please refer this for setting filter value.
Filter
time(ms)
Actual filter
value
Filter
time(ms)
Actual filter
value
0
0
7
17
1
1
8
19
2
4
9
22
3
6
10
24
4
9
15
37
5
11
20
52
6
14
Summary of Contents for LP-S044
Page 1: ... Copyright Reserved Autonics Co Ltd i USER MANUAL ...
Page 2: ...ii Copyright Reserved KONICS Co Ltd ...
Page 12: ...Table of Contents xii Copyright Reserved Autonics Co Ltd ...
Page 44: ...4 System Organization 44 Copyright Reserved Autonics Co Ltd ...
Page 84: ...10 Firmware update 84 Copyright Reserved Autonics Co Ltd ...
Page 88: ...11 Repair and Check 88 Copyright Reserved Autonics Co Ltd ...
Page 90: ...12 Appendix 90 Copyright Reserved Autonics Co Ltd 12 2 ASCII code table ...
Page 92: ...12 Appendix 92 Copyright Reserved Autonics Co Ltd ...
Page 93: ...12 Appendix Copyright Reserved Autonics Co Ltd 93 MTG LPS044U1 V1 2 1303US ...