USER MANUAL

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for LP-S044

Page 1: ... Copyright Reserved Autonics Co Ltd i USER MANUAL ...

Page 2: ...ii Copyright Reserved KONICS Co Ltd ...

Page 3: ...electing Autonics products Please familiarize yourself with the information contained in the Safety Precautions section before using this product This user manual contains information about the product and its proper use and should be kept in a place where it will be easy to access ...

Page 4: ...eproduced in either part or whole without permission A user manual is not provided as part of the product package Please visit our home page www autonics com to download a copy The manual s content may vary depending on changes to the product s software and other unforeseen developments within Autonics and is subject to change without prior notice Upgrade notice is provided through our homepage We...

Page 5: ...s Symbol Description Supplementary information for a particular feature Failure to follow instructions can result in serious injury or death Failure to follow instructions can lead to a minor injury or product damage An example of the concerned feature s use 1 Annotation mark ...

Page 6: ...perty damage in the event of a malfunction It may cause a fire human injury or property loss In the event of LP defect or malfunction in the Logic Panel an alternative circuit must be constructed on the exterior It may cause a fire human injury or property loss Construct an emergency power off circuit safety circuit or interlock circuit on the exterior of the Logic Panel It may cause a fire human ...

Page 7: ... electric shock or malfunction Make sure the ground wire of Logic Panel is wired separately from the ground wires of other devices Ground resistance must be less than 100Ω and a lead wire of which sectional area is over 1 25mm 2 should be used It may cause electric shock or malfunction When connecting Logic Panel ports with communication port and constructing input output check the pin number and ...

Page 8: ... Please separate as an industrial waste when discarding this unit To change the battery contact the store or an authorized technician The manufacturer is not liable for damages that occur due to causes for which the manufacture is not responsible regardless of manufacturer s prediction about customer s opportunity loss and damage from the unit malfunction damages due to extraordinary situations se...

Page 9: ...ce 21 1 6 Part description 21 1 7 Dimensions 22 2 Installation 23 2 1 LP installation 23 2 2 Power wiring 24 2 2 1 Ground wiring 25 2 2 2 Input wiring 26 2 2 3 Output wiring 27 2 3 Battery replacement 28 2 4 Caution for using 28 3 Device Construction 29 3 1 Device element 29 3 2 Device range 31 3 2 1 Bit device range 31 3 2 2 Word device range 32 3 3 Application of UW UB corresponding 32 4 System ...

Page 10: ...ystem screen 48 6 3 Monitoring 49 6 3 1 Device monitor 49 6 3 2 I O monitoring 49 6 4 Set Environment 50 6 4 1 Language 50 6 4 2 PLC setting 51 6 4 3 Clock 55 6 4 4 Clear USER DATA 55 6 4 5 Menu call key 56 6 4 6 Buzzer 56 6 4 7 Opening time 57 6 4 8 Backlight 57 6 4 9 Battery 58 6 4 10 Contrast 58 6 5 Data View 59 6 5 1 Base screen 59 6 5 2 Window screen 59 6 5 3 Comment 59 6 5 4 Memory size 59 6...

Page 11: ... Window 77 8 1 Keypad type 77 8 2 Keypad organization 78 9 Troubleshooting 79 10 Firmware update 81 10 1 Firmware update by GP Editor 81 10 2 Firmware update by SmartStudio 83 11 Repair and Check 85 11 1 Battery change 85 11 2 Check 86 11 2 1 General check 86 11 2 2 Periodic check 86 12 Appendix 89 12 1 Self diagnosis code table 89 12 2 ASCII code table 90 12 3 UW correspondence table 91 ...

Page 12: ...Table of Contents xii Copyright Reserved Autonics Co Ltd ...

Page 13: ...ollers from LP is connected by serial communication and it is able to exchange mutual information The variable for controller is displayed by various methods as tag which is graphic object For example if the physical variable for monitoring is temperature LP displays temperature as numeral by numeral input tag or as trend graph with changes by time LP screen consists of these graphic objects combi...

Page 14: ...font various manuals at www autonics com to download conveniently Monitoring function of other type controller By PLC connection port LP monitors and controls the variable of additionally connected controller PLC etc Communication between heterogeneous controllers You can connect other type controller to serial port separately LP monitors two different controllers simultaneously and relays communi...

Page 15: ...able to input value in controller with touch switch on front screen 1 3 Ordering information Model LP S044 S1D0 C5T A LP S044 S1D0 C5R A LP S044 S1D1 C5T A LP S044 S1D1 C5R A 화면크기 4 4inch 표시장치종류 STN LCD 표현 색상수 MONO Blue White 전원전압 24VDC 인터페이스 RS232C RS422C 각 1 개 RS232C 2 개 모듈형태 일체형 I O 구성 IN 16 점 OUT 16 점 I O 커넥터타입 터미널 블록 커넥터 리본케이블 커넥터 터미널 블록 커넥터 리본케이블 커넥터 확장기능타입 Type A 지원 ...

Page 16: ...h 0 5kV Withstanding voltage 500VAC 50 60Hz for a minute Vibration Mechanical 0 75mm amplitude at frequency of 10 to 55Hz for a minute in each of X Y Z directions for an hour Malfunction 0 5mm amplitude at frequency of 10 to 55Hz for a minute in each of X Y Z directions for 10 minutes Shock Mechanical 300m s2 30G X Y Z directions for 3 times Malfunction 100m s2 10G X Y Z directions for 3 times Env...

Page 17: ...f user screen 500 pages Touch switch Width 15 X Height 4 Total 60 Control performance Instruction Basic instruction 28 Application instruction 220 Program capacity 8K step Processing time Average 6 to 7 step I O control type Batch processing Operation control mode Repeated doubling method interrupt processing Device range Refer to 3 2 Device range Interface Communication interface LP S044 S1D0 C5T...

Page 18: ...n when supplying power BACKLIGHT Set off time for backlight as screensaver BATTERY Displays battery remaining with percentage and bar graph CONTRAST Adjusts LCD screen contrast DATA VIEW BASE SCREEN Displays user defined base screen title and number WINDOW SCREEN Displays user defined window screen title and number COMMENT Displays downloaded comment list in LP MEMORY SIZE Displays total memory ca...

Page 19: ...efer to GP LP user manual for communication Every device such as PLC is able to connect any RS232C or RS422 port CH1 CH2 is designates in GP Editor Connection of 1 PLC Connect PLC to a port and one of PC printer barcode reader to the other port Connection of CH1 and CH2 Connect PLC to LP ports It is able to connect even if CH and CH2 are not same type PLC LP can relay data exchange between CH1 and...

Page 20: ...rved Autonics Co Ltd Connection of plural PLCs It is able to connect same device type to CH1 and CH2 as up to 32 by each In this case LP can link data between CH1 1 to CH1 n and CH2 1 and CH2 n and it is able not to use CH1 or CH2 ...

Page 21: ... 4 Non used 5 SG 5 SG 6 DSR 6 TXD 7 Non used 7 RXD 8 Non used 8 Non used 9 Non used 9 Non used Serial port setting Designate the desired settings for below items at SET ENVIRONMENT PLC SETTING Interface RS232 RS422 Baudrate 300 600 1200 2400 4800 9600 19200 38400 57600 115200bps Data length 7 8 Bit Stop bit 1 2 Bit Parity ODD EVEN Flow control XON XOFF DSR DTR NONE 1 6 Part description ...

Page 22: ...1 Overview 22 Copyright Reserved Autonics Co Ltd 1 7 Dimensions Unit mm Fixing bracket Panel cut out Panel thickness max 4mm ...

Page 23: ...Copyright Reserved Autonics Co Ltd 23 2 Installation 2 1 LP installation 1st Set LP S044 in panel 2nd Set the fixing bracket to slot upper 2 lower 2 3rd Tighten the fixing bracket with 0 3N m torque by M4 screw driver ...

Page 24: ... m torque Ground resistance should be less than 100Ω and ground it separately Caution for power wiring Before connecting power line you must check power polarity Do not connect power when power is supplied Observe following allowable voltage change range of power voltage Power voltage 24VDC Allowable voltage change range 21 6V to 26 4VDC When connecting power supply power by power supply which has...

Page 25: ...ved Autonics Co Ltd 25 2 2 1 Ground wiring Caution for ground wiring Connect max 100Ω of ground resistance Diameter of cable for ground wiring connection should be over than 2 As above figure separate from other device s ground wire ...

Page 26: ...timal diameter cables 1 Input terminal wiring Inner input module of LP S044 series is NPN open collector source type type LP S044 S1D0 1 C5R input connection LP S044 S1D0 1 C5T input connection Divide I O cable by color Do not wire I O cables to same duct Keep min 100mm distance from power line and other high voltage line to wire ...

Page 27: ...ved Autonics Co Ltd 27 2 Connection method by input device type Connect with relay output type Connect with NPN open collector output type 2 2 3 Output wiring LP S044 S1D0 1 C5R output connection LP S044 S1D0 1 C5T output connection ...

Page 28: ...ll be used indoor Altitude Max 2 000m Pollution Degree 2 Installation Category Ⅱ It may cause malfunction if above instructions are not followed Do not install this product as below places A place where ambient temperature is outside the range of 0 C to 50 C A place where ambient humidity is outside the range of 35 to 85 RH A place where sudden temperature change occurs frequently so dew may form ...

Page 29: ... is a device used when using the recipe function of graphic panel Virtual device V It is the used area for matched automatically device area by system when using user defined function User cannot use this device area For more details refer to SmartStudio programming manual s 3 8 Usages of user defined functions Special device F This area is for displaying and controlling several information and st...

Page 30: ...n which cannot control external I O for example it receives external input and cannot execute external load Step device S This allotted area is for controlling step such as the progress which needs the order Link device L It is a device for linking external device and data If this is not used as data link it is available as data device or inner device Data device D It is an allotted device for sav...

Page 31: ...V Virtual device V0 to V255F UB061000 to UB06355F 00256F bit F Special device F0 to F255F UB064000 to UB06655F 00256F bit Z Index device Z0 to Z255F UB067000 to UB06955F 00256F bit X Input device X0 to X255F UB044000 to UB07255F 00256F bit Y Output device Y0 to Y255F UB080000 to UB08255F 00256F bit T Timer contact T0 to T255 UB100000 to UB10015F 00256 Bit C Counter contact C0 to C255 UB150000 to U...

Page 32: ...ord M Auxiliary device M0 to M9999 UW20000 to UW29999 10000 Word L Link device L0 to L255 UW38000 to UW38999 01000 Word D Data device D0 to D9999 UW40000 to UW49999 10000 Word V Virtual device V0 to V255 UW06100 to UW06355 00256 Word 3 3 Application of UW UB corresponding LP series is integrated with PLC and HMI device as one You can monitor and control the device of the additionally connected dev...

Page 33: ...n 4 1 Stand alone As following organization stand alone system with LP S044 monitors the program for controlling several type I O and operation items device parameter without additional device You can also organize controlling organization for specific operation items with touching ...

Page 34: ...d device during executing LP S044 operation For monitoring inner device of LP S044 and inner device of the connected controller at the same time refer to 12 3 UW correspondence table If there are too much draw data screen processing speed may be reduced However control program speed is not affected To monitor external connected devices be sure that draw data properly not to cause problems for comm...

Page 35: ...ers PLC etc during executing LP S044 operation as following figure For monitoring inner device of LP S044 and inner device of a connected controller at the same time refer to 12 3 UW correspondence table You can connect devices up to 32 it may be different by the product Respond time is different by the connected devcie during communication data renewal time may be longer For more details refer to...

Page 36: ...meter etc status of between two devices which are connected at each port as different type controller PLC etc during executing LP S044 operation as following figure For monitoring inner device of LP S044 and inner device of a connected controller at the same time refer to 12 3 UW correspondence table For more details refer to GP LP user manual for communication ...

Page 37: ...em to monitor or control host unit data by universal communication during executing LP S044 operation For monitoring inner device of LP and inner device of an addtionally connected controller at the same time refer to 12 3 UW correspondence table For more details refer to 5 4 Universal protocol of GP LP user manual for communication ...

Page 38: ...ct with barcode printer As following figure you can organize the system to read barcode data by connecting barcode reader or to print alarm history by connecting serial print during executing LP S044 operation For more details refer to GP LP user manual for communication ...

Page 39: ...s waiting status for executing debug instruction by stopping user defined program at 0 step At the same time it initializes inner memory data except latch area parts of special device and makes every external output signal turn OFF 4 5 1 Change operation mode 1 Change inner device status when entering operation mode MODE RUN STOP PAUSE DEBUG Inner device Latch area Maintain Maintain Maintain Maint...

Page 40: ...4 System Organization 40 Copyright Reserved Autonics Co Ltd 4 6 Program processing procedure When power ON or LP mode switch is RUN as following processing it processes operation ...

Page 41: ... is not as EDITOR touch PROTOCOL part and cofigure as EDITOR Touch this it rotates in order as EDITOR PRINTER BARCODE MONITOR Touch PORT area to configure the connection port of LP S044 Touch this it rotates in order as RS422 and RS232C To check baud rate data bit stop bit parity etc touch the desired channel CH1 or CH2 It is able to download and upload GP Editor content to LP S044 only when the b...

Page 42: ...Select Communication Option and Option dialog box appears Designate communication configuration as same as that of from LP S044 LP S044 supports only serial communication therefore Ethernet and USB communication are not activated For more details of each option refer to GP Editor user manual 3rd After configuration connect LP and PC by communication cable to download and upload drawn program from ...

Page 43: ...4 7 Connect with GP Editor to configurate LP 4 8 2 SmartStudio configuration Communication between PC and LP S044 is available with serial communication Select Online Communication Option in SmartStudio menu to configurate communication between LP S044 and PC For configuration method by each item refer to SmartStudio user manual ...

Page 44: ...4 System Organization 44 Copyright Reserved Autonics Co Ltd ...

Page 45: ...lled Check fixing brackets are fixed with approved tightening torque 2 Emergency stop circuit Check individual emergency stop circuit at the external LP S044 is placed Check there is problem to emergency stop when error occurs 3 Ground Check ground cable is installed with separated other device ground cable Check there is 3rd grounding 4 Power cable Check cable connection by polarity Check the tig...

Page 46: ...d devices such as HDD etc After recording special information or printing program contents exit the operation 1 If there are error for LCD screen operation of LP S044 and power LED refer to 9 Troubleshooting 2 To delete program SET ENVIRONMENT CLEAR USER DATA of system setting menu or refer to SmartStudio user manual 3 Connection with SmartStudio GP Editor and LP S044 is able to connect download u...

Page 47: ...nu and their sub menu appears The system screen organization is as below LP S044 system setting menu MONITORING DEVICE MONITOR I O MONITORING SET ENVIRONMENT LANGUAGE PLC SETTING CLOCK CLEAR USER DATA MENU CALL KEY BUZZER OPENING BACKLIGHT BATTERY CONTRAST DATA VIEW BASE SCREEN WINDOW SCREEN COMMENT MEMORY SIZE MODEL VERSION SET FUNCTION DATA TRANSFER TIME SWITCH PRINT OUT SET PARAMETER FILTER INT...

Page 48: ...tonics Co Ltd 6 2 Operation of system screen No Function and operation Moves from system screen to user screen Displays current screen s menu Moves to upper parameter Moves to up and down items Touch the desired menu and it moves to that menu ...

Page 49: ...connected device Confirm monitorable device by each device from GP LP user manual for communication No Function and operation Calls input window to select special device set as CH1 Calls input window for word device value at cursor Sets bit device value at cursor Resets selected bit device Displays close up device list Touch this Dec or Hex is displayed in order Dec means decimal Hex means hexadec...

Page 50: ...ernational character font English font vector font You can designate system langauge for LP inner system language Supported language It supports Korean English Japanesse Chinese Russian and the other languages are supported later with upgrade Font type It supports various fonts by each language No Function and operation Displays designated user language and font 1 Displays designated ASCII charact...

Page 51: ...ocol Displays PLC protocol of CH1 CH1connect port Displays connect port of CH1 CH2 configuration line Displays connected device and connect port for CH2 Touch this to select one from downloaded protocol in EDITOR PRINTER BARCODE MONITOR protocol and designate connect port Select one of RS232C or RS422 or depending on CH1 setting CH2 may be changed as the other If CH1 is SLAVE MONITOR does not appe...

Page 52: ...s CH1 protocol Rotates in order as downloaded protocol EDITOR PRINTER BARCODE UNIVERSAL DEFAULT protocol Displays CH2 protocol as EDITOR for default Rotates in order as EDITOR PRINTER BARCODE MONITOR If CH1 is SLAVE MONITOR does not appear Displays CH1 connect port Designates automatically as non using port in LP S044 S1D0 RS422 A PORT RS 232C B PORT LP S044 S1D1 RS232C A PORT RS232C B PORT Displa...

Page 53: ...Use it is not able to communication configuration Displays CH1 protocol Rotates in order NoUse EDITOR PRINTER BARCODE UNIVERSAL DEFAULT protocl Displays CH2 protocol as downloaded protocol for default Rotates in order as downloaded protocol EDITOR PRINTER BARCODE Displays CH1 connect port Designates automatically as non using port in LP S044 S1D0 RS422 PORT RS232C PORT LP S044 S1D1 RS232C A PORT R...

Page 54: ... reading data from barcode For more details refer to GP LP user manual for communication MONITOR Available only in CH2 Monitoring mode for PLC which is connected to LP from PC directly LP is as transmitter by transmitting data from PC to PLC and data from PLC to PC In case of MITSUBISHI FX Series editor mode is available for monitoring NoUse Displayed only not using appropriate CH Designate baud r...

Page 55: ... BATTERY of system setting menu 6 4 4 Clear USER DATA This menu is for initializing user data and setting values of LP Be sure that once deleted data cannot recover Be sure that once deleted data cannot recover Especially for saving alarm history contents by GP Editor upload alarm history and alarm frequency with checking Alarm History Alarmhistory txt and Alarm Frequency Alarmfrequency txt in tag...

Page 56: ...s vertical bottom side from front screen is placed at left status default position of system setting menu key is placed at left upper point Touch left upper point as soon as re supply power and it enters to system setting menu If there is numeral ASCII input or touch key tag at system setting menu key position it executes only tag operation and it does not enter system setting menu 6 4 6 Buzzer De...

Page 57: ... time of backlight LCD backlight is OFF Backlight is ON again when user touches it In this case touching is only for backlight ON and the other operation is not valid No Function and operation Designate back light off time if there is no touch input 0 to 9 Touch the desired time CLR Cancel the set input input cursor disappears ENT Set the input value Set range is 0 min to 99min If 0 is set backlig...

Page 58: ...ys battery remaining with bar graph Displays battery remaining with 0 to 100 as numerical percentage When battery remaiing is 0 Bat Low message flashes 6 4 10 Contrast No Function and operation Displays current set status Displays set screen contrast ratio as bar graph Touch this it decreases contrast ratio Touch this it increases contrast ratio ...

Page 59: ...d base screen operates normally but the input object of the selected screen does not operate 6 5 2 Window screen This menu displays screen number and screen title list for window screen Screen check method is same as base screen s Window screen is designed up to 500 from GP Editor but actial downloadable window screens are up to 3 to LP 6 5 3 Comment This menu displays downlowaded user defined com...

Page 60: ...6 System Screen 60 Copyright Reserved Autonics Co Ltd 6 5 5 Model Version This menu displays LP S044 model name and firmware version ...

Page 61: ...6 System Screen Copyright Reserved Autonics Co Ltd 61 6 6 Set Function This menu screen is displayed during communicating download upload between GP Editor of PC and LP Waiting Download Upload ...

Page 62: ...le to set at Common Time Action menu of GP Editor Not desiganted ACTION ACT item displays action time as No Function and operation Action number of time switch If there is no designated device as time switch bit device Device is displayed Touch this numeral input key pad appears to input start time and end time No Function and operation Touch desired day of the week Shaded item MON WED FRI are sel...

Page 63: ... printing alarm history which is listed during LP operation by external printer No Function and operation Prints alarm history with touching Printer port setting From SET ENVIRONMENT PLC SETTING of system setting menu set PRINTER Cancels alarm history output Alarm history printout format ...

Page 64: ...X7 filter values Displays the set X8 to XF filter values Displays inner device to save the set filter value When inner device is set it is able to control filter value as the designated device Change M device for using inner device to filter value Filter value is available from 0 to 63 6bit Below table is for actual filter value by filter value Please refer this for setting filter value Filter tim...

Page 65: ...tudio No Function and operation Displays the set interrupt type of X00 X0F No Int Falling Rising Saves the set value at the device by 2 bit 2 WORD in order This example is that each interrupt set value is mapping to inner device In case of setting inner device as M0100 From the logic to change this inner device value on ladder program it can control filter value To use inner device to control inte...

Page 66: ...ad information refer to SmartStudio user manual Keypad MATRIX is not set Keypad MATRIX is set at SmartStudio No Function and operation Displays whether using keypad MATRIX Displays the set input register value Displays the set output register value Displays the device to save key input Displays whether using Device Extensions Matrix connection diagram ...

Page 67: ... 2nd 8th Bth bit of word device M0 turn ON and M0 value of word device is changed as 0x0904 6 7 4 7 segment display This menu is for displaying the set 7 segment output data at SmartStudio For 7 segment information refer to SmartStudio user manual 7 segment is not set 7 segment is set at SmartStudio No Function and operation Displays whether using 7 segment Displays the set output register COM val...

Page 68: ...t saves 0 If output register SEG setting is Y0 to Y7 it saves 1 WDS 2 First segment output data WDS 3 Second segment output data WDS 4 Third segment output data WDS 5 Fourth segment output data Not using device extensions WDS First segment output data WDS 1 Second segment output data WDS 2 Third segment output data WDS 3 Fourth segment output data Setting example and output timing diagram Setting ...

Page 69: ... user manual Synchronous serial SIO is not set Synchronous serial SIO is set at SmartStudio No Function and operation Displays whether using synchronous serial SIO set Displays the set output register value Displays the set data bit Displays the set number of data Displays the set data lead device Displays whether using Device Extensions Output data information range varies according to set data b...

Page 70: ...s 0 If output register setting is YC YD and YE it saves 1 WDS 1 Saves the set number of data bits WDS 2 Saves the set number of data WDS 3 1st display data WDS n n 3 th display data n 3 the number of data Not using device extensions WDS 1st display data WDS n n 3 th display data n the number of data Setting example and output timing diagram Setting item Setting example Using SIO Check Using Output...

Page 71: ...een right lower point 239 79 15 19 to 239 79 Position by screen type Base screen size is not changeable and has fixed coordinate value If window screen is over maximum size right lower point moves automatically to the end point of screen Therefore it may different between user defined position and window screen position 4 Screen number and the number of screen Item Base screen Window screen Screen...

Page 72: ...lay line graph trend graph bar graph statistic graph panel meter touch key 1 These are displayed only on base screen 2 Limit the number of display objects by screen type Except below some objects there is no limit the number of displaying for all tags on screen However too many objects on a screen may cause reducing monitor speed remarkably Object which can exist only one on a screen Alarm history...

Page 73: ...screen number corresponding the device value of screen data error message appears 2 Screen switching methods It is switched to the appropriate screen when changing screen switching device value It is changed as below methods 1 Using touch key for switching screen There are switching functions of touch key operations as follows Switching to the fixed screen Switching to the previous screen Switchin...

Page 74: ...een satisfying current value of the device on a base screen In order to use screen overlap function designate the device for overlap window in GP Editor The overlap window is displayed in order of window 1 2 on current screens as below In case the value of overlap window device is exceeded the range 1 to 500 or does not exist the window is not displayed ...

Page 75: ...en numbers 1 2 3 4 5 6 7 8 In case of D0 1 D1 3 D2 11 Overlap window 2 is not overlapped because the value of overlap window 2 device is not an existing base screen number In case of D0 1 D1 3 D2 5 Various tags of overlap screen in the upper part can cover lower part of tags and they are not shown If touch keys or input tags are overlapped the upper one is only operated when it touched ...

Page 76: ...e as following screen Touch CLOSE and error message dialog box disappears If connection error is not resolved after 5 seconds error message appears again on the screen Connection error message appers only on user screen When the third CH1 fourth CH2 bit of system signal 1 device in system information device are ON status error message for specified connect device appears on the screen For more det...

Page 77: ...8 System Window Copyright Reserved Autonics Co Ltd 77 8 System Window 8 1 Keypad type No Type Keypad screen 1 Binary 2 Octal 3 Decimal 4 Hexadeci mal 5 Real number 6 ASCII ...

Page 78: ... 1 Moves to the previous page 1 Moves to the next page 1 Those keys are displayed only for ASCII input key pad ENT CLR key operation of user screen is according to Key Action settings of Screen Auxiliary Configuration dialog box Key operation CLR ENT No movement Holds keypad Holds keypad Not operated Not operated In order of user ID Holds keypad Holds keypad Moves to previous input tag Moves to ne...

Page 79: ...in power LED turning OFF Check as following list by number If error is not solved please notify this to our service center No Check item Error 1 Is power supplied 2 Is supplied power within the allowable voltage range 3 Is the polarity of power line wiring correct 4 Is there a problem to tighten power terminal 2 Troubleshooting in error status Check item Error checking Troubleshooting Program gram...

Page 80: ...error for external output Check as following list by number If error is not solved please notify this to our service center No Check item Error 1 Is output wiring connection correct 2 Is connection status of output connector fine 3 Is connected power voltage to output within allowable voltage range 4 Is there problem to output device operation 5 Troubleshooting in communication connection error Ch...

Page 81: ... is available for firmware download 10 1 Firmware update by GP Editor 1st Firmware file is different as GP LP model Download a LP S044 firmware file from www autonics com You can download only for same firmware GP LP type with GP LP type designated at GP Editor Select Common GP PLC Type of menu GP PLC Type dialog box appears By pull down menu designate to be downloaded GP LP type 2nd Select Commun...

Page 82: ...r displays GP Firmware Download dialog box and download progresses If you want to discontinue download click Cancle and Do you want to interrupt firmware download message appears Click Yes and it discontinues download For discontinuing downlaod re start GP LP 6th When completing download successively GP LP displays UPGRADE OK PLEASE POWER OFF message 7th When failing donwload GP LP displays UPGRAD...

Page 83: ...rtStudio 1st Start SmartStudio 2nd Create new project for to be firmware upgraded LP type Two of RS 232C LP S044 S1D1 Each of RS232C RS422 LP S044 S1D0 3rd Select Online Firmware Download in SmartStudio Following steps are as same as that of firmware update by GP Editor s from 2nd step ...

Page 84: ...10 Firmware update 84 Copyright Reserved Autonics Co Ltd ...

Page 85: ...n time is not correct After power failure time is reset After power failure data of latch area is reset 2 Battery residual quantity display You can check battery remaining from SETENVIRONMENT BATTERY of system setting menu in LP S044 Please replace battery if battery remaining is below 5 3 Special register for battery Current backup battery error F0002C Turns ON when battery voltage is below than ...

Page 86: ...ector Check whether connector locking or not check connection of connector Connection part for connector should be connected tightly Secure locking part Wire connect cable with duct etc 11 2 2 Periodic check The following table is for checking by every month Item Description Standard Troubleshooting Power voltage Measure power voltage Within power voltage specification Change supply power Battery ...

Page 87: ... check For checking power voltage use the specified measuring device If there are error elements please write down the error and notify us with details For changing the product power must be turned OFF For removing dust foreign substance use dry cloth without moist or detergents ...

Page 88: ...11 Repair and Check 88 Copyright Reserved Autonics Co Ltd ...

Page 89: ...tion error 0X0030 Program instruction error When the program contains instructions that are not able to read and inappropriate forms 0X0031 Program sequence error When there is not the instructions required to process the program such as user defined functions label name END RET and IRET etc 0X0040 Parameter setting error When there are some problems in settings for common and expansion parameters...

Page 90: ...12 Appendix 90 Copyright Reserved Autonics Co Ltd 12 2 ASCII code table ...

Page 91: ...mer contact T0 to T255 UB100000 to UB10015F T Timer present value T0 to T255 UW11000 to UW11255 T Timer set value T0 to T255 UW13000 to UW13255 C Counter contact C0 to C255 UB150000 to UB15015F C Counter present value C0 to C255 UW16000 to UW16255 C Counter set value C0 to C255 UW18000 to UW18255 Z Index device Z0 to Z255F Z0 to Z255 UB067000 to UB06955F UW6700 to UW6955 F Special device F0 to F25...

Page 92: ...12 Appendix 92 Copyright Reserved Autonics Co Ltd ...

Page 93: ...12 Appendix Copyright Reserved Autonics Co Ltd 93 MTG LPS044U1 V1 2 1303US ...