(2) Alarm output operation mode [CH AL Type]
Mode Operation
Descriptions
Off
-
■
None
PV.Hi
High-limit alarm temp (AL1.H): 90
High-limit alarm temp (AL1.H):110
■
High-limit alarm
PV ≥ high limit alarm
temperature(AL1.H) , alarm output
is ON.
Recording mark: AL1=↑ AL2=
PV.Lo
Low-limit alarm temp (AL1.L): 90
Low-limit alarm temp (AL1.L):110
■
Low-limit alarm
PV ≤ low-limit alarm temperature
(AL1.L) , alarm is ON.
Recording mark: AL1=↓ AL2=
SBA -
■
Sensor Break Alarm
When input is not connected or
disconnected during recording, alarm
output is ON.
You can check the input break using
external alarm output contact by
buzzer or others.
Recording mark: AL1= B AL2= B
P.End -
■
Paper end alarm
If running out of recording paper
during recording, alarm output is
ON. (measured value is saved at
system memory) When recording
paper is replaced, alarm is cleared
automatically (standard alarm) and P
is printed on recording paper when
printing back up data.
Recording mark: AL1= P AL2= P
● Factory default: CH
AL1 Type(PV.Hi), CH AL2 Type(PV.Lo)
Summary of Contents for KRN50 SERIES
Page 2: ... ii Copyright Reserved Autonics Co Ltd ...
Page 20: ...2 Specifications 20 Copyright Reserved Autonics Co Ltd ...
Page 22: ...3 Dimensions 22 Copyright Reserved Autonics Co Ltd ...
Page 24: ...4 Connections 24 Copyright Reserved Autonics Co Ltd ...
Page 28: ...6 Functions 28 Copyright Reserved Autonics Co Ltd ...
Page 34: ...7 General operation and parameter setting menu 34 Copyright Reserved Autonics Co Ltd ...
Page 66: ...8 Recording 66 Copyright Reserved Autonics Co Ltd ...
Page 71: ...8 Recording 71 Copyright Reserved Autonics Co Ltd ...
Page 75: ...8 Recording 75 Copyright Reserved Autonics Co Ltd ...
Page 77: ...8 Recording 77 Copyright Reserved Autonics Co Ltd ...