Specifications
MULTI FUNCTION TIMER
AT11DN/AT11EN SERIES
※
Sockets (PG-11, PS-11(N)) are sold separately.
AT 11 DN -
No mark
100-240VAC 50/60Hz,
24-240VDC
1
12VDC
2
24VAC 50/60Hz, 24VDC
DN
Time limit 2c
EN
Instantaneous 1c
+ Time limit 1c
11
11-pin plug type
AT
Analog Timer
Power
supply
Time operation
Number of plug pins
Item
Model
AT11DN-
AT11EN-
Function
Multi Function Timer
Control time setting range
※
1
0.05 sec. to 100 hour
Power supply
•100-240VAC
ᜠ
50/60Hz, 24-240VDC
ᜡ
universal •24VAC
ᜠ
50/60Hz, 24VDC
ᜡ
universal
• 12VDC
ᜡ
Allowable voltage range
90 to 110% of the rated voltage
Power consumption
•Max. 3.5VA (100-240VAC
ᜠ
) ,
Max. 1.5W (24-240VDC
ᜡ
)
•Max. 4VA (24VAC
ᜠ
),
Max. 1.5W (24VDC
ᜡ
)
•Max. 1W (12VDC
ᜡ
)
•Max. 4.3VA (100-240VAC
ᜠ
) ,
Max. 2W (24-240VDC
ᜡ
)
•Max. 4.5VA (24VAC
ᜠ
),
Max. 2W (24VDC
ᜡ
)
•Max. 1.5W (12VDC
ᜡ
)
Return time
Max. 100ms
Time operation
Signal ON Start
Min. input signal width
START, RESET, INHIBIT: Min. 50ms
Input
START, RESET, INHIBIT: [No-voltage input] - Short-circuit impedance: Max. 1
kΩ
,
Residual voltage: Max. 0.5VDC, Open-circuit impedance: Max. 100
kΩ
Control
output
Contact type
Time limit DPDT (2c)
Instantaneous SPDT (1c)+Time limit SPDT (1c)
Contact capacity 250VAC
ᜠ
5A resistive load
Relay
life cycle
Mechanical
Min. 10,000,000 operations
Electrical
Min. 100,000 operations (250VAC 5A resistive load)
Repeat error
Max. ±0.2% ±10ms
Setting error
Max. ±5% ±50ms
Voltage error
Max. ±0.5%
Temperature error
Max. ±2%
Insulation resistance
100
MΩ
(at 500VDC megger)
Dielectric strength
2,000VAC 50/60Hz for 1 minute
Environ-
ment
Ambient temp.
-10 to 55
℃
, Storage: -25 to 65
℃
Ambient humid. 35 to 85%RH, Storage: 35 to 85%RH
Approval
Accessory
Bracket
Weight
※
2
Approx. 132.2g (approx. 85g)
Approx. 134.7g (approx. 87.5g)
I N S T R U C T I O N M A N U A L
Safety Considerations
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
※
Please observe all safety considerations for safe and proper product operation to avoid hazards.
※
Safety considerations are categorized as follows.
Warning
Failure to follow these instructions may result in serious injury or death.
Caution
Failure to follow these instructions may result in personal injury or product damage.
※
The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Warning
Caution
Ordering Information
Time Specifications
AT11DN SERIES
AT11EN SERIES
Unit Description
Connections
※
1: AC/DC voltage: 100-240VAC 50/60Hz, 24-240VDC
: 24VAC 50/60Hz, 24VDC
DC voltage: 12VDC
RESET
START
INHIBIT
6
5
4
3
2
1 11
10
9
8
7
CONTACT OUT:
250VAC 5A
RESISTIVE LOAD
※
1
(Time limit
1c)
(Time limit 1c)
RESET
START
INHIBIT
6
5
4
3
2
1 11
10
9
8
7
CONTACT OUT:
250VAC 5A
RESISTIVE LOAD
※
1
(Time limit 1c)
(Instantaneous
1c)
※
The above specifications are subject to change and some models may be discontinued
without notice.
※
Be sure to follow cautions written in the instruction manual and the technical descriptions
(catalog, homepage).
Time range Time unit Time setting range
0.5
sec
0.05 to 0.5 sec.
1.0
0.1 to 1 sec.
5
0.5 to 5 sec.
10
1 to 10 sec.
0.5
min
0.05 to 0.5 min.
1.0
0.1 to 1 min.
5
0.5 to 5 min.
10
1 to 10 min.
0.5
hour
0.05 to 0.5 hour
1.0
0.1 to 1 hour
5
0.5 to 5 hour
10
1 to 10 hour
0.5
10h
0.5 to 5 hour
1.0
1 to 10 hour
5
5 to 50 hour
10
10 to 100 hour
Mode
Time chart
A
t
t1
t2
Power 2-10
START 2-6
INHIBIT 2-5
RESET 2-7
Time limit contact N.C.
Time limit contact N.O.
Time limit output indicator
Operation/Power indicator
Signal ON
Delay
F
t
t
t-a
t
t1
t2
Power 2-10
START 2-6
INHIBIT 2-5
RESET 2-7
Time limit contact N.C.
Time limit contact N.O.
Time limit output indicator
Operation/Power indicator
Flicker
(OFF Start)
F1
t
t
t-a
t
t1
t2
Power 2-10
START 2-6
INHIBIT 2-5
RESET 2-7
Time limit contact N.C.
Time limit contact N.O.
Time limit output indicator
Operation/Power indicator
Flicker 1
(ON Start)
C
t
t-a
t1
t2
t-a
Power 2-10
START 2-6
INHIBIT 2-5
RESET 2-7
Time limit contact N.C.
Time limit contact N.O.
Time limit output indicator
Operation/Power indicator
Signal OFF
Delay
D
t
t
t-a t1
t2
t-a
t
t-a t-a
START 2-6
INHIBIT 2-5
RESET 2-7
Time limit contact N.C.
Time limit contact N.O.
Time limit output indicator
Operation/Power indicator
Power 2-10
Signal
ON/OFF
Delay
I
t
t
t
t-a
t-a t1
t2
Operation/Power indicator
Time limit output indicator
Time limit contact N.O.
Time limit contact N.C.
INHIBIT 2-5
START 2-6
Power 2-10
RESET 2-7
Interval
※
If power is cut or the RESET terminal is short-circuited, the timer will be reset.
※
If the INHIBIT terminal is short-circuited during a time limit operation, the time will stop.
※
In case of F, F1 output operation mode, setting time should be over 100ms.
If not, it may cause abnormal output operation due to under 100ms of setting time.
[t: Setting time, t=t1+t2, t>t-a]
Output Operation Mode
64.5
50
15
44.8
Dimensions
Panel cut-out
Bracket
31
55
56
20
15
21
5
45
16
48.6
44.9
36
(unit: mm)
Cautions during Use
Major Products
Photoelectric Sensors
Temperature Controllers
Fiber Optic Sensors
Temperature/Humidity Transducers
Door Sensors
SSRs/Power Controllers
Door Side Sensors
Counters
Area Sensors
Timers
Proximity Sensors
Panel Meters
Pressure Sensors
Tachometers/Pulse (Rate) Meters
Rotary Encoders
Display Units
Connector/Sockets
Sensor Controllers
Switching Mode Power Supplies
Control Switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper Motors/Drivers/Motion Controllers
Graphic/Logic Panels
Field Network Devices
Laser Marking System (Fiber, Co
₂
, Nd: YAG)
Laser Welding/Cutting System
M
ain
circ
uit
(Figure 1)
< Sensor >
Power
Rectification
circuit
Isolation
transformer
<External sensor
power supply>
START
RESET
INHIBIT
※
1: Refer to time specifications for control time setting range by model.
※
2: The weight includes packaging. The weight in parenthesis is for unit only.
※
Environment resistance is rated at no freezing or condensation.
48
55
Operation/Power indicator
(Flashes for timer operation,
Turns ON for timer stop)
Output operation mode indicator
(sec, min, hour, 10h mode)
Output operation
mode indicator
(A, F, F1,
C, D,
I
mode)
Output operation
mode setting SW
Time limit output
indicator
Time range indication
Time range setting switch
Min. 65
Min. 65
45
45
+0.6
0
+0.6
0
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury
or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles,
railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in fire, personal injury, or economic loss.
2. Install on a device panel to use.
Failure to follow this instruction may result in electric shock or fire.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or fire.
4. Check 'Connections' before wiring.
Failure to follow this instruction may result in fire.
5. Do not disassemble or modify the unit.
Failure to follow this instruction may result in electric shock or fire.
1. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage.
2. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in electric shock or fire.
3. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight,
radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in fire or explosion.
4. Keep metal chip, dust, and wire residue from flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
http://www.autonics.com
HEADQUARTERS:
18, Bansong-ro 513beon-gil, Haeundae-gu,
Busan, South Korea, 48002
TEL: 82-51-519-3232
E-mail:
DRW171149AA
DRW171149AA
1. Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents.
2. 12VDC, 24VDC, 24VAC power supply should be insulated and limited voltage/current or Class 2, SELV power
supply device.
3. When supplying or turning off the power, use a switch or etc. to avoid chattering.
4. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
5. In order to block peripheral current, use isolation transformer which of secondary part is not grounded as (Figure 1)
to supply power to the external input device.
6. In order to avoid leakage current flowing, connect resistance and condenser as (Figure 3).
If connect as (Figure 2), it may cause malfunction due to leakage current.
7. Do not connect two or more timers with only one input contact or transistor simultaneously.
8. Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at
input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
9. Change setting time, time range, operation mode or etc. after turning off the power of the timer.
10. This unit may be used in the following environments.
①
Indoors (in the environment condition rated in 'Specifications')
②
Altitude max. 2,000m
③
Pollution degree 2
④
Installation category II
Power
Power
Timer
Timer
(Figure 2)
(Figure 3)
R
C
T
R
C
T
Leakage
current