background image

-|Transparent Guide|-

Product Components

• 

Product (

Protective cover for the rotary switches

)

• 

Name plates × 20

• 

M4×10 screw with washer × 1

• 

Instruction manual × 1

• 

Waterproof cover × 4

Sold Separately

• 

Name plates

• 

Waterproof cover 

Software

Download the installation file and the manuals from the Autonics website.

  

atIOLink

atIOLink with purposes for setting, diagnosis, initialization and maintenance of IO-Link 
device via IODD file is provided as the dedicated Port and Device Configuration Tool 
(PDCT).

Connections

  

Ethernet port  

M12 (Socket-Female), D-coded

Pin

Function

Description

1

2

3

4

1

TX +

Transmit Data +

2

RX +

Receive Data +

3

TX -

Transmit Data -

4

RX -

Receive Data -

  

Power supply port

OUT 

(7/8'', Socket-

Female)

IN 

(7/8'', Plug-Male)

Pin

Function

Description

1

2

3

4

5

5

4

3

2

1

1, 2

0 V

Sensor and actuator 

supply

3

F.G.

Frame ground

4

+24 VDCᜡ

Sensor supply

5

+24 VDCᜡ

Actuator supply

  

PDCT port  

M12 (Socket-Female), A-coded

Pin

Function

1

4

5

3

2

1

Not Connected (N.C.)

2

Data -

3

0 V

4

Not Connected (N.C.)

5

Data +

  

I/O port

M12 (Socket-Female), A-coded

Pin

Function

1

4

5

3

2

1

+24 VDCᜡ

2

I/Q: Digital Input

3

0 V

4

C/Q: IO-Link, Digital Input/Output

5

Not Connected (N.C.)

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website.

ADIO

-

PN

-

MA

08

A

-

ILM

❶ I/O specification

N: NPN
P: PNP

Summary of Contents for ADIO-PN

Page 1: ...dify the unit Failure to follow this instruction may result in fire 06 Do not touch the product during operation or for a certain period of time after stopping Failure to follow this instruction may result in burn Caution Failure to follow instructions may result in injury or product damage 01 Use the unit within the rated specifications Failure to follow this instruction may result in fire or sho...

Page 2: ...ADIO PN Integrate the ADIO PN to PROFINET project ADIO PN TIA Portal V16Guide 01 Set the ports of ADIO PN Checking the operation Check the indicators ADIO PN Product Manual 01 The project planning software of the upper level communication system may be different depending on the user s environment For more information refer to the manufacturer s manual Operation mode Safe State01 Validation Data S...

Page 3: ... 4 1 TX Transmit Data 2 RX Receive Data 3 TX Transmit Data 4 RX Receive Data Power supply port OUT 7 8 Socket Female IN 7 8 Plug Male Pin Function Description 1 2 3 4 5 5 4 3 2 1 1 2 0 V Sensor and actuator supply 3 F G Frame ground 4 24 VDCᜡ Sensor supply 5 24 VDCᜡ Actuator supply PDCT port M12 Socket Female A coded Pin Function 1 4 5 3 2 1 Not Connected N C 2 Data 3 0 V 4 Not Connected N C 5 Dat...

Page 4: ...ide 29 6 4 7 1 3 215 24 26 5 26 5 26 5 35 26 Ø4 5 7 8 X 2EA 203 35 20 38 6 3 1 3 8 35 33 4 30 5 M4 X 0 7 Ø4 5 M12 X 1 X 11EA 66 Dimensions Unit mm For the detailed dimensions of the product follow the Autonics website ...

Page 5: ... Prepare a flat or metal panel in the enclosure 02 Drill a hole to mount and ground the product on the surface 03 Turn off all power 04 Fix the product using M4 screws in the mounting holes Tightening torque 1 5 N m M4 M4 Installation UnitDescriptions 1 2 3 2 4 4 5 5 6 7 9 10 8 01 Grounding hole 02 Mounting hole 03 Insertion part for the name plate 04 Ethernet port 05 Power supply port 06 PDCT por...

Page 6: ...y switches Description Value PROFINET Device Name 000 This device name is stored in the ADIO PN s EEPROM Applying the device name configured on the PROFINET Master or DCP tools PROFINET device name 001 to 999 Establish the communication connection after setting the ADIO PN s device name The value of rotary switches is displayed at the last of the device name ADIO PN MA08A ILM 02 Turn on the ADIO P...

Page 7: ...tor 1 Function Connector 2 Pin no Connector 2 Function 1 N C 1 5 VDCᜡ 2 Data 2 Data 3 0 V 4 0 V 4 N C 5 Data 3 Data 01 Connect to the PROFINET 01 Connect the M12 connector to the Ethernet port See the connections below 1 2 3 4 1 TX Transmit Data 2 RX Receive Data 3 TX Transmit Data 4 RX Receive Data 02 Connect the connector to the PROFINET network Network device PLC or PROFINET device supporting P...

Page 8: ... 24 VDCᜡ Sensor supply 5 24 VDCᜡ Actuator supply 1 2 3 4 5 5 4 3 2 1 PWR OUT PWR IN PortConnections 03 Connect with the atIOLink Do not use the PDCT port and the Ethernet port at the same time 01 Connect the M12 connector to the PDCT port See the connections below 1 4 5 3 2 1 Not Connected N C 2 Data 3 0 V 4 Not Connected N C 5 Data 02 Connect the connector to the network device Network device PC ...

Page 9: ...ngs of the rotary switches is changing Red Flashing 1 Hz Applied voltage low 18 VDCᜡ 02 The power supply of actuator Indicator LED color Status Description UA Green ON Applied voltage normal Red Flashing 1 Hz Applied voltage low 18 VDCᜡ Error in the rotary switches ON Applied voltage none 10 VDCᜡ 03 Product initialization Indicator LED color Status Description US UA Red ON ADIO initialization fail...

Page 10: ... 4 W 216 W Supplying current per port 2 A Port Sensor current US 9 A Dimensions W 66 H 215 D 38 mm Material Zinc Die casting Ethernet port M12 Socket Female 4 pin D coded Push Pull Number of ports 2 IN OUT Supported function daisy chain Power supply port Input 7 8 Plug Male 5 pin Output 7 8 Socket Female 5 pin Number of ports 2 IN OUT Supported function daisy chain PDCT port M12 Socket Female 5 pi...