Port Connections
■ Port specifications
•
Be sure to check the port specifications below before connecting the device. Prepare a cable that complies with the protection rating IP67.
Ethernet port
I/O port
PDCT port
Power supply port
Type
M12 (Socket-Female), 4-pin,
D-coded
M12 (Socket-Female), 5-pin,
A-coded
M12 (Socket-Female), 5-pin,
A-coded
Input: 7/8” (Plug-Male), 5-pin
Output: 7/8” (Socket-Female), 5-pin
Push-Pull
YES
YES
YES
N.A
Number of ports
2
8
1
2
Tightening torque
0.6 N m
0.6 N m
0.6 N m
1.5 N m
Supported function
Daisy chain
-
USB serial communication
Daisy chain
•
The example of communication cable for the PDCT port
Connector 1
Connector 2
Wiring
M12 (Plug-Male)
5-pin
1
2
3
4
5
USB Type A
1 2
4
3
Connector 1
Pin no.
Connector 1
Function
Connector 2
Pin no.
Connector 2
Function
1
N.C.
1
+ 5 VDCᜡ
2
Data -
→
2
Data -
3
0 V
→
4
0 V
4
N.C.
-
-
5
Data +
→
3
Data +
01. Connect to the PROFINET
01. Connect the M12 connector to the Ethernet port. See the connections below.
1
2
3
4
1
TX +
Transmit Data +
2
RX +
Receive Data +
3
TX - Transmit Data -
4
RX - Receive Data -
02. Connect the connector to the PROFINET network.
• Network device: PLC or PROFINET device supporting PROFINET protocol
03. Put the waterproof cover on the unused port.
02. Connect the IO-Link devices
The maximum output current is 2 A at each I/O port. Configure the device so that the total current of the I/O ports does not exceed 9 A.
Check the wiring information in the manual of the IO-Link device to be connected.
01. Connect the M12 connector to the I/O port. See the connections below.
1
4
5
3
2
1
+24 VDCᜡ
2
I/Q: Digital Input
3
0 V
4
C/Q: IO-Link, Digital Input/Output
5
Not Connected (N.C.)
02. Put the waterproof cover on the unused port.