Performance and data
Overview
The IC7-C and IC9-C meters are 230/400 volt 50 Hz, 5 amp
current transformer operated meter designed for measuring
3 phases in a 4 wire star configured system and is
capable of transmitting kWh and kVAH by means of the
volt free outputs which are standard on the basic model.
The model IC9-C is supplied with a fully programmable
RS485-communication output and is capable of
transmitting all of the data the meter monitors.
Technical Parameters
Meter Standard
BS EN 61036
Accuracy
Active 1.0, Reactive 2.0
Reference Voltage
3 x 230 /400 v
Basic Current
5 Amp
Maximum Current
6 Amp
Frequency
50/60 Hz
Pulse Constant (LED strobe) 1000 imp/kWh,
1000 imp/ kVAH
Range of Voltage
200- 250 volt
Operating Temperature
-30°C – +70°C
Stace:nowrap" class="ft02">Pulse Constant (LED strobe) 1000 imp/kWh,
1000 imp/ kVAH
Range of Voltage
200- 250 volt
Operating Temperature
-30°C – +70°C
Storage Temperature
-30°C – +80°C
Power Consumption
0.01VA @5A; 0.8W,
8VA @230V
Pulse Output
IEC 62053-31
Red L.E.D.
Pulse Indication.
Display
20 x 4 character LCM with
background light.
Output Details
2 – Opto isolated Mosfet
devices: 400 ACV, 100ma
KWh, KVAH
Pulse Duration
80-100 ms closure
Pulse Value
C.T. Value less than 1000/5A
= 1 kWh/imp
C.T. Value 1000/5A or more
than = 10 kWh/imp
0.4
0.3
0.2
0.1
-0.1
-0.2
-0.3
-0.4
0.1
1.0
2.0
3.0
4.0
5.0
6.0
IC
9
Load Curve
0.5 Lag 1.0
Unity 0.5
Lead
8
Current transformer selection
For accurate monitoring, correct selection
of the current transformers is critical.
Always select the current transformers suitable
for the load you are actually monitoring.
DO NOT
automatically select current
transformers to the breaker size
in case the load is significantly lower.
Main Function
Measurement and Information available from
Keypad.
1. Active, Reactive, Apparent import energy
2. Active, Reactive export energy
Real Variables
1. Voltage: 3 phase voltages, 3 line voltages
2. Current: 3 phase current and neutral
current
3. Active instant (kW): 3 phase and total
power
4. Reactive instant (KVAR): 3 phase and total
power
5. Apparent (KVA): 3 phase and total power
6. Power factor: 3 phase and total power
factor
7. Frequency
Demand (Demand period 30 minutes)
1. Current Demand: Active, Reactive,
Apparent demand
2. Maximum demand: Active, Reactive,
Apparent Maximum demand
Performance characteristics
Diagram 9:
Typical load curve with
balanced load at 50 Hz.