Performance and data

Overview

The IC7-C and IC9-C meters are 230/400 volt 50 Hz, 5 amp 
current transformer operated meter designed for measuring  
3 phases in a 4 wire star configured system and is  
capable of transmitting kWh and kVAH by means of the 
volt free outputs which are standard on the basic model. 
The model IC9-C is supplied with a fully programmable 
RS485-communication output and is capable of 
transmitting all of the data the meter monitors.

Technical Parameters

Meter Standard 

BS EN 61036

Accuracy 

Active 1.0, Reactive 2.0

Reference Voltage 

3 x 230 /400 v

Basic Current   

5 Amp

Maximum Current 

6 Amp

Frequency 

50/60 Hz

Pulse Constant (LED strobe)  1000 imp/kWh,  

1000 imp/ kVAH

Range of Voltage 

200- 250 volt

Operating Temperature 

-30°C – +70°C

Stace:nowrap" class="ft02">Pulse Constant (LED strobe)  1000 imp/kWh,  

1000 imp/ kVAH

Range of Voltage 

200- 250 volt

Operating Temperature 

-30°C – +70°C

Storage Temperature    

-30°C – +80°C 

Power Consumption 

0.01VA @5A; 0.8W,  
8VA @230V

Pulse Output 

IEC 62053-31

Red L.E.D. 

Pulse Indication.

Display 

20 x 4 character LCM with 
background light.

Output Details 

2 – Opto isolated Mosfet 
devices: 400 ACV, 100ma 
KWh, KVAH

Pulse Duration 

80-100 ms closure

Pulse Value 

C.T. Value less than 1000/5A 
= 1 kWh/imp 
C.T. Value 1000/5A or more 
than = 10 kWh/imp

    

0.4
0.3
0.2
0.1

-0.1
-0.2
-0.3
-0.4

0.1

1.0

2.0

3.0

4.0

5.0

6.0

IC

9

 Load Curve

0.5 Lag 1.0
Unity 0.5
Lead

8

Current transformer selection

For accurate monitoring, correct selection  
of the current transformers is critical.  
Always select the current transformers suitable 
for the load you are actually monitoring.  

DO NOT

 automatically select current 

transformers to the breaker size  
in case the load is significantly lower.

Main Function

Measurement and Information available from 
Keypad.
1. Active, Reactive, Apparent import energy
2. Active, Reactive export energy

Real Variables

1. Voltage:   3 phase voltages, 3 line voltages
2. Current:  3 phase current and neutral 
current
3. Active instant (kW): 3 phase and total 
power
4. Reactive instant (KVAR): 3 phase and total 
power
5. Apparent (KVA):  3 phase and total power
6. Power factor: 3 phase and total power 
factor
7. Frequency

Demand (Demand period  30 minutes) 

1. Current Demand: Active, Reactive, 
Apparent demand
2. Maximum demand: Active, Reactive, 
Apparent  Maximum demand

Performance characteristics

Diagram 9: 

Typical load curve with 

balanced load at 50 Hz.

Summary of Contents for IC7-C

Page 1: ...installation and operation manual IC7 C and IC9 C horizon r a n g e The fusion of land based metering and ether based monitoring 9...

Page 2: ...ing Slide the back of the meter first through the opening on the rear side of the door and then push the bezel from the front side over the protruding clear plastic and push fully home until it locks...

Page 3: ...t programming details for your chosen CT ratios e When the process is complete press the Function key to take you back to the default screen Note When setting CT ratios and if you have only three digi...

Page 4: ...IMPORT ENERGY KWH 000000 00 KVAH 000000 00 KVARH 000000 00 EXPORT ENERGY KWH 000000 00 KVARH 000000 00 VOLTAGE L 1 000 0 L 1 L2 000 0 L2 000 0 L2 L3 000 0 L3 000 0 L3 L1 000 0 FREQUENCY 50 00Hz AMPS L...

Page 5: ...will take you to the desired screen To return to the normal screen press FUNCTION key again If you enter an incorrect number or a function which is not available on this model you will see the screen...

Page 6: ...50 To check connections enter function 50 See Page 5 function operation display Press Funct key to see connections Press Funct key to return to normal display PULSE TEST Function 60 To test the relay...

Page 7: ...ches needs to be in the on position To allocate meter register number 14 dill switches numbers 5 6 and 7 must be in the on position To allocate meter register number 39 dill switches numbers 3 6 7 and...

Page 8: ...se Duration 80 100 ms closure Pulse Value C T Value less than 1000 5A 1 kWh imp C T Value 1000 5A or more than 10 kWh imp 0 4 0 3 0 2 0 1 0 1 0 2 0 3 0 4 0 1 1 0 2 0 3 0 4 0 5 0 6 0 IC9 Load Curve 0 5...

Page 9: ...n depth stock holding combine to provide a level of service which has earned the appreciation of customers across the spectrum of the UK and export markets Computerised distribution systems are geared...

Reviews: