E.g. The cursor will move down over the
first number to your left, to move this
across to the next cursor press the key with the arrow facing down
the cursor
has now moved one space to the right. To increment the number at any point
press the key with the arrow marked to the right. Continue until you have entered
the correct numbers: 0200/0005.
You must now press the return key
this will set all the parameters you have
chosen in the meter. a box will appear with yes/no in it . Press the key with
the arrow facing left
the cursor has now moved over the “YES” . Press return
this has now programmed the ct ratio.
IMPORTANT
: You will receive the meter in the factory default mode which is suitable for
3 phase 4 wire network, 230/400 volt, 50 hz 0005/0005 amp.
YOU SHOULD ONLY NEED TO PROGRAM THE CT RATIO AND THE TIME INTO THE METER
E.g: 0200/0005 (the date and time)
Select Menu
: You should now be back at the Config Menu:
Move the highlighted feature up or down by pressing the arrows marked up or
down
to the “RS 485” line.
RS 485
: Press the return key
this will take you to the RS 485 screen. Here you
have two features you can alter.
a. Address (meter’s unique Modbus number)
b. Baud Rate
a. Address
Please note the meter is factory-set to match Autometers protocol.
Baude Rate: 9600
Data Format:
Floating point
Parity Type: Even Modbus Type:
RTU
Wire Mode: 2 wire
F.P. High word first
When using RS 485 Modbus it is vital that you understand what management
system the meters will be connected to. Normally every meter must have a unique
address and must not be duplicated.
However, when connecting to Autometers Intelligent Termination Point then all
meters must have the address set at “001”.
To change this you will need to operate four keys
The two keys which have the arrows pointing up and down
move the cursor
along from left to right so you can enter your number in the correct sequence.
8
Network
:
Move the highlighted feature up or down by pressing the arrows marked
to
the “Network” line. The cursor will move over the “3p4w” symbol to alter this press
the key with the arrows facing the right
this will switch from 1p2w to 3p3w to
3p4w. Select the value you want then press the key with the arrow facing down
, this moves the cursor to the line below.
V. Range
:
You will notice that the 400 v is now highlighted. To change this press the arrow
key marked with the arrow pointing to the right
the number will change to
100V. select the voltage range you require and then press the key with the arrow
marked down
. You will notice the 5A is now highlighted.
I. Range
:
To change I range press the arrow key marked with the arrow pointing to the right
, the number will change to IA. Select the setting you require and then press the
key with the arrow marked down
. You will notice the 0400/0400 is
now highlighted.
VT
: To change this you will need to operate four keys
.
The two keys which have the arrows pointing up and down
move the cursor
along for you to enter your number in the correct sequence.
The two keys with arrows pointing left and right
increment the number up
or down.
E.g. The cursor will move down over the first number to your left, to move this across to the
next cursor press the key with the arrow facing down
the cursor has now moved one space
to the right. To increment the number at any point press the key with the arrow marked to the
right. Continue until you have entered the correct numbers.
0400/0400 select the voltage range you require and then press the key with the
arrow marked down
. You will notice the 0005/0005 is now highlighted.
C.T. (current transformer ratio)
: To change this you will need to operate four keys
The two keys which have the arrows pointing up and down
move the cursor
along for you to enter your number in the correct sequence.
The two keys with arrows pointing left and right
increment the number
up or down.