Total active energy(kWh)

Display format:0000.00

Import active energy(kWh) 

Display format: 0000.00 

Export active energy(kWh)

Display format: 0000.00 

Voltage (V)

Current (A)

Active power (W)

Frequency (F)

Power factor (PF)

Modbus Address or Primary address

Default: 001Baudrate Default : 9600bps

Parity

Even/Odd/None are optional

Primary current 1A-9999A

Default: 5 (sample shows 100A)

CT 2

Secondary current 5A

Software version

1. Introduction

This document provides operating,  maintenance and installation instructions 

of A-45 series. The unit measures and displays the characteristics of single 

phase two wires application. It provides voltage, current, power, frequency, 

power factor and energy information. A-45 series has both direct connect types 

and 5A CT operated types. The direct connect type can work with direct load 

45A. Two Pulse outputs and 1 remote communication port is provided.

This series covers 3 models:

2.Specifications

2.1  General Specifications

Voltage AC (Un).........................

Voltage Range...........................

Current Input............................

Power consumption.................

Frequency.................................           

AC voltage withstand...............

Impulse voltage withstand......

Overcurrent withstand............

Pulse output rate......................

                         

Display........................................

Max reading...............................

                     

230V

176~276V AC

0.25~5(6)A

<2W/10VA

50/60Hz (50Hz only for MID version)

4KV for 1 minute

6KV-1.2uS wavform

20Imax for 0.01s 

1000imp/kWh (default)

100/10/1 imp/kWh/kVarh (configurable)

LCD with white backlit

999999 kWh 

2.2 Accuracy

Voltage...................................

Current..................................

Frequency..............................

Power factor..........................

Active power..........................

Reactive power......................

Apparent power....................

Active energy.........................

                        .........................

Reactive energy.....................

0.5% of range maximum

0.5% of nominal

0.2% of mid-frequency

1% of Unity

1% of range maximum

1% of range maximum

1% of range maximum

Class 1 IEC62053-21

Class B EN50470-3 (MID product only)

1% of range maximum

2.3  Environment

Operating temperature...............................      

Storage and transportation temperature. 

Reference temperature...............................

Relative humidity..........................................

Altitude..........................................................

Warm up time...............................................

Mechanical Environment.............................

Electromagnetic environment....................

Degree of pollution......................................

-25

°c 

to +55

°c

-40

°c 

to +70

°c 

23

°c 

±2

°c 

0 to 95%, non-condensing

up to 2000m

3s

M1

E2

2

2.4  Mechanics

Din rail dimensions................      

Mounting.................................   

Sealing.....................................

Material...................................

18x119x62 (WxHxD) DIN 43880 DIN rail 

35mm

IP51 (indoor)

self-extinguishing UL94V-0

3. Display

3.1 Initialization Display

When it is powered on, the meter will initialize and do self-checking.

1

2

3

Full Screen. It will last for 3 seconds

Software version. It will last for 3 seconds

Total active energy (kWh)

After the self-checking program, the meter display will show the total active 

energy (kWh)

3.2 Scroll Display Button

After the self-checking program, the meter display will show the total active 

energy (kWh)

Click the button, the LCD display will scroll the 

measurements.

1

1-1

1-2

2

3

4

5

6

7

8

9

10

11

12

Model

A-45P

A-45M

A-45CTM

Current Input

Direct connect 45A

Direct connect 45A

5A CT operated

Communication

Pulse output only

Pulse plus Modbus

Pulse plus Modbus

A-45 SERIES

MID Approved B and D

Measures kWh, Kvarh, KW, Kvar, 

KVA, PF, Hz, dmd, V, A, etc. 
Bi-directional measurement IMP 

& EXP
Two pulse outputs
RS485 Modbus
Din Rail one Module width (18mm)
45A direct connected 
5 Amp C.T operated
Better than Class 1 accuracy

Autometers Systems Ltd. 4B Albany Road, Chorlton-cum-Hardy, Manchester M21 0AW 

Email: [email protected] Phone: 00(44) 0161 861 9056 Fax: 0161 881 3745 www.autometers.co.uk

  

Ref. A-45Series.06.2021

Product development is continuous and Autometers Systems Limited reserves the right to make alterations and manufacture without notice. Products as 

delivered may therefor differ from the descriptions and illustrations in this publication

Reviews: