background image

2

Tech Support 770-844-4200

www.productivity2000.com

General Specifications

Operating Temperature

0º to 60ºC (32º to 140ºF)

Storage Temperature

-20º to 70ºC (-4º to 158ºF)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800VAC applied for 1 second

Insulation Resistance

> 10MΩ @ 500VDC

Heat Dissipation

6.4 W

Enclosure Type

Open Equipment

Module Keying to Backplane Electronic
Module Location

Any I/O slot in a Productivity2000 System

Field Wiring

Use ZIPLink Wiring System ONLY. See “Wiring Options” 

on page 5. Must use copper conductors 75ºC or 

equivalent.

EU Directive

See the “EU Directive” topic in the Productivity2000 

Help File. Information can also be obtained at: 

www.productivity2000.com

Connector Type

24-Pin Molex Style 43025-2400

Weight

90g (3.2 oz)

Agency Approvals

UL 61010-1 and UL 61010-2-201 File E139594, Canada 

and USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-

201 Safety)*

Output Specifications

Output Channels

16

Module Signal Output Range

±10VDC

Output Signal Resolution

16-bit

Resolution Value of LSB 

(least significant bit)

±10VDC = 305μV/count

 

1 LSB = 1 count

Data Range

-32768 to 32767 counts

Output Type (sourcing/sinking)

Voltage: 10mA max current

Output Value in Fault Mode

0V

Load Impedance

≥1000Ω

Maximum Capacitive Load

0.01μF maximum

Allowed Load Type

Grounded

Maximum Inaccuracy

0.1% of range 

(including temperature drift)

Maximum Full Scale Calibration 

Error (not including offset error)

±0.025% of range maximum

Maximum Offset Calibration Error

±0.025% of range maximum

Accuracy vs. Temperature

±25ppm/°C max full scale calibration change 

(±0.0025% of range/°C)

Max Crosstalk

-96dB, 1 LSB

Linearity Error (End to End)

±16 LSB maximum (±0.025% of full scale) 

Monotonic with no missing codes

Output Stability and Repeatability

±10 LSB after 10 minute warm-up (typical)

Output Ripple

0.05% of full scale

Output Setting Time

300μs max, 5μs min (full scale change)

All Channel Update Rate

3ms

Maximum Continuous Overload

Outputs current limited to 40mA typical. 

Continuous overloads on multiple output 

can damage the module.

Type of Output Protection

0.1μF Transient Suppressor

External DC Power Required

24VDC (-20% / +25%), 265mA

*Meets EMC and Safety requirements. See the D.O.C. for details.

Summary of Contents for Productivity2000 P2-16DA-2

Page 1: ...s based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to the pr...

Page 2: ...odule Signal Output Range 10VDC Output Signal Resolution 16 bit Resolution Value of LSB least significant bit 10VDC 305 V count 1 LSB 1 count Data Range 32768 to 32767 counts Output Type sourcing sink...

Page 3: ...8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ISOLATED ANALOG CIRCUIT POWER CH11 ADC CH15 ADC CH12 ADC CH16 ADC COM COM COM COM V1 V5 V2 V6 V3 V7 V4 V8 V V V V V9 V13 V10 V14 V11 V15 V12 V16 CH9 AD...

Page 4: ...QR Code Use any QR Code reader application to display the module s product insert 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the followin...

Page 5: ...nt channel selected and to each Status Bit Item Module Configuration Wiring Options 1 ZIPLink Feed Through Modules and Cables 0 5 m 1 6 ft cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL RTB20 ZL RTB20...

Page 6: ...0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0...

Page 7: ...SELFTEST FAIL REPLACE MODULE 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 11 0 12 0 13 0 14 0 15 0 16 0 1 0000H 2 0000H 3 0000H 4 0000H 5 0000H 6 0000H 7 0000H 8 0000H 9 0000H 10 0000H 11 0000H 12 0000H...

Page 8: ...8 Tech Support 770 844 4200 www productivity2000 com Document Name Edition Revision Date P2 16DA 2 DS 2nd Ed 9 11 2019 Copyright 2014 AutomationDirect com Incorporated All Rights Reserved Worldwide...