IronHorse GSDA-DP-S User Manual –  1st Edition – 09/18/2019

Parameter Mode

 can be entered by simply pressing and holding the Enter button down for three 

seconds.  Once in Parameter Mode, the far left of the display will be a ‘P’.  The right side of the display 

will indicate the currently selected parameter number for editing purposes.  Pressing the Up or 

Down button will increase or decrease the selected parameter number on the display. Although the 

parameter numbers are in numerical order, some numbers are skipped.  These skipped numbers 

represent reserved parameters that are not yet implemented and are not displayed. Once the desired 

parameter number is displayed, pressing the Enter button will change the display to Value Mode.

Value Mode

 is used to modify the value of the selected parameter.  When in Value Mode, the two 

dots which form the colon between digits two and three, will alternately flash (one, then the other.) 

Pressing the Up or Down button increases or decreases the selected parameter’s value.  See the 

Software Parameters for a list of allowable values and ranges.  Value changes take effect immediately. 

Once the desired value is showing in the display window, pressing the Enter button again will return to 

Parameter Mode.  The new value is not saved in permanent memory until the Enter button is pressed.  

Removing power from the unit while in Value Mode may result in the specified new value being lost.
The front panel Annunciators will be perform as follows:

• 

Parameter 10 = 1; ‘Gen’ annunciator lit

• 

Parameter 10 = 2; ‘SCL’ annunciator lit

• 

Parameter 30 = 7, IN1 = Low; ‘SCL’ annunciator lit

• 

Parameter 35 = 7, IN2 = High; ‘SCL’ annunciator lit

D

eviCe

 C

onfiGUrAtion

Configuration is accomplished via jumper settings and (for Voltage Outputs only) a trimpot 

adjustment.  Location is as follows:

P3

Program Enable

(JP5)

V

OUT

/4-20mA

Jumper 4 (JP4)

V

OUT

/4-20mA

Jumper 3 (JP3)

P5

P6

JP1

Trimpot

(R9)

I_IN  V_IN

COM  P/EN

V_OUT

I_OUT 

V_OUT

I_OUT 

With the display set to 100.0 and no user device connected to ‘V-OUT’, P3-5 (-) and P3-6(+), adjust R9 

for the desired maximum V-OUT. Finally, connect the user device and carefully re-adjust R9 to trim 

the output to desired maximum V-OUT. This will prevent the output from exceeding the limits of the 

user device if done properly. The user should evaluate what their system will be doing during this 

adjustment to prevent any harmful results.

M

ODe

 

Of

 O

PeratiOn

There are three Modes of Operation for the GSDA-DP-S, established by the JP1, JP3, and JP4 jumper 

settings:

Summary of Contents for IronHorse GSDA-DP-S

Page 1: ...Page 1 IronHorse GSDA DP S User Manual 1st Edition 09 18 2019 GSDA DP S Signal Conditioner Generator User Manual User Manual Number GSDA DP S_UMP ...

Page 2: ...onments requiring fail safe performance such as in the operation of nuclear facilities aircraft navigation or communication systems air traffic control direct life support machines or weapons systems in which the failure of the product could lead directly to death personal injury or severe physical or environmental damage High Risk Activities AutomationDirect specifically disclaims any expressed o...

Page 3: ... 09 18 2019 Contents Warning 2 Trademarks 2 Publication History 2 GSDA DP S User Manual Overview 4 IronHorse GSDA DP S General Information 4 GSDA DP S Installation 6 GSDA DP S Operation 8 Device Configuration 9 Software Parameters 11 Troubleshooting 16 ...

Page 4: ...n in the left hand margin the paragraph to its immediate right will be a special note WARNING When you see the exclamation mark icon in the left hand margin the paragraph to its immediate right will be a WARNING This information could prevent injury loss of property or even death in extreme cases IronHorse GSDA DP S General Information The GSDA DP S is a panel mounted multi purpose signal conditio...

Page 5: ...essly excluded NOTE Carefully check the GSDA DP S for shipping damage Report any damage to the carrier immediately Do not attempt to install the device if visible damage is evident to either the circuit or to the electronic components Specifications GSDA DP S Specifications Electrical Line Input Voltage 85 265 VAC Line Input Frequency 48 62 Hz Voltage Signal Input 0 10 VDC Voltage Signal Output Mi...

Page 6: ...CONTROL HOUSING APPROXIMATELY 3 622 WIDE BY 1 770 HIGH GSDA DP S CONTROL SUPPLIED WITH EACH CONTROL 1 GASKET 2 2 6 32 X 3 4 PANHEAD BLACK OXIDE STAINLESS SCREWS 3 2 6 NUT WITH LOCKWASHER Exploded Panel View Cut out and Mounting Dimensions HOUSING DEPTH 4 625 117 5 PANEL CUT OUT GSDA DP S x 2 GEN SCL SPL ENTER SIGNAL SCALER AND GENERATOR 4 00 101 6 3 62 91 9 0 885 22 5 1 77 45 0 140 3 6 4 00 101 6 ...

Page 7: ...his terminal For systems with two hot AC lines connect either of the Hot AC lines to this terminal P3 3 SIGNAL IN In Scaled Mode connects to Negative or Common of voltage or current signal to be attenuated P3 4 SIGNAL IN In Scaled Mode connects to Positive of voltage or current signal to be attenuated P3 5 24VDC SUPPLY A 24VDC supply output is provided to the user for sensor or other device P3 6 2...

Page 8: ...e only the display setting effects the 4 20mA current output level In voltage output mode the display setting and the maximum level set by the potentiometer R9 adjustment determine the voltage output level see Device Configuration for proper hardware and software setup SPL The GSDA DP S is in Set Point Lock this effectively disables any changes until IN1 IN2 input levels change according to the fu...

Page 9: ...ed value is showing in the display window pressing the Enter button again will return to Parameter Mode The new value is not saved in permanent memory until the Enter button is pressed Removing power from the unit while in Value Mode may result in the specified new value being lost The front panel Annunciators will be perform as follows Parameter 10 1 Gen annunciator lit Parameter 10 2 SCL annunci...

Page 10: ... 2 0 10 VDC Input Scaled 4 20 mA or 0 1 20VDC Output 3 No Input Generator 4 20 mA or 0 1 20VDC Output NOTE Both JP3 and JP4 must be set the same GSDA DP S Current Voltage I O Jumpers and Parameter 10 Settings Input Output Parameter 10 JP1 JP3 JP4 JP5 Scale Generate V I In V I Out Reference V I Out Power Supply Application Configuration Pin to Pin Jumper Configuration Current Voltage Scale li Vo Vo...

Page 11: ...ult to Zero Display 2 Default to Power up Value 3 Default to Previous Running Value 3 19 Power Up Value 0 9999 Eng Units 0 Display and Output Setup Parameters 20 Display Value at Minimum Output 9999 9999 Eng Units 0 21 Display Value at Maximum Output 9999 9999 Eng Units 1000 25 Output Minimum 0 1000 1 10 0 26 Output Maximum 0 1000 1 10 1000 Input 1 IN1 Setup Parameters 30 IN1 Input Configuration 1...

Page 12: ...example with a Display Zero Blanking setting of 3 and a displayed value of 6 the display would show _006 Mode 1 ___X Always show at least 1 digit Mode 2 __XX Always show at least 2 digits Mode 3 _XXX Always show at least 3 digits Mode 4 XXXX Always show all 4 digits 13 Decimal Point Position This selects the format of the display with respect to the decimal point s position This parameter does not...

Page 13: ...parameters 21 Display Value at Maximum Output This parameter defines the upper end of the display range This is the value which limits how high the user is able to scroll the displayed value in Running Mode This parameter is set without consideration for the decimal point s position For example setting this parameter to 1000 would set the upper display limit at 100 0 1 000 or 1000 according to the...

Page 14: ...esponds to the programmed jog setpoint parameter 31 Once the IN1 input returns to an electrically low state or wired to the unit s common the output will once again correspond to the display value Mode 5 Output 100 When IN1 Low When the IN1 input is at an electrically low state or wired to the unit s common the GSDA DP S will force its output to 100 Once the IN1 input returns to an electrically hi...

Page 15: ...will once again correspond to the display value Mode 5 Output 100 When IN2 Low When the IN2 input is at an electrically low state or wired to the unit s common the GSDA DP S will force its output to 100 Once the IN2 input returns to an electrically high 5V state or allowed to float disconnected the output will once again correspond to the display value Mode 6 Output 100 When IN2 High When the IN2 ...

Page 16: ...r additional help and instructions Display is dim Display intensity parameter is too low Increase the display intensity parameter to cause the display digits to become brighter S1 or S2 displayed Switch S1 or S2 is active Remove S1 or S2 input Refer to Parameter 30 and 35 for information on settings LOC displayed Parameter 30 or 35 is set to 7 Change input state of S1 or S2 or reprogram Parameter ...