Page 10
IronHorse GSDA-DP-S User Manual – 1st Edition – 09/18/2019
1) JP1 - If the GSDA-DP-S is receiving a signal to be Scaled or Converted, this setting defines the
input signal type (0-10 VDC or 4-20 mA Current).
2) JP3 and JP4 - Determine the Output Signal type - Vdc or Current (4-20 mA). Both JP3 and JP4
MUST be set the same.
The four jumper settings allow the GSDA-DP-S to operate as:
1) 4-20 mA Input/Scaled 4-20 mA or 0.1-20VDC Output
2) 0-10 VDC Input/Scaled 4-20 mA or 0.1-20VDC Output
3) No Input/Generator 4-20 mA or 0.1-20VDC Output
NOTE: Both JP3 and JP4 must be set the same.
GSDA-DP-S Current/Voltage I/O Jumpers and Parameter 10 Settings
Input
Output
Parameter 10
JP1
JP3
JP4
JP5
Scale/
Generate
V/I In
V/I Out
Reference
V/I Out Power
Supply
Application
Configuration
Pin to Pin Jumper Configuration
Current
Voltage
Scale
li
Vo
Vo
Current
Current
Scale
li
Io
Io
Voltage
Voltage
Scale
Vi
Vo
Vo
Voltage
Current
Scale
Vi
Io
Io
Generate
Voltage
Gen
N/A
Vo
Vo
Generate
Current
Gen
N/A
Io
Io
Scale = 2
Allow Change = P/
EN position
Gen = 1
Inhibit Change =
‘COM’ position