9.2.3.6. IO-Link master diagnostic
IO-Link Master Diagnostic (Global Error Code 0x40)
Description
Value
Error
0x0000
Error Fetching Extended Events
0x97FF
Startup Parameterization Error
0x9801
Wrong Device. Inspection Level Mismatch
0x9802
Process Data Mismatch
0x9803
Short Circuit At C/Q - Pin 4
0x9804
IO-Link PHY Overtemperature
0x9805
Short Circuit L+ - Pin1
0x9806
Undervoltage L+ - Pin1
0x9807
Device Event Overflow
0x9808
Backup Failed - Memory Out Of Range 2k
0x9809
Backup Inconsistency - Data Storage Index Not Availaeirble
0x980A
Backup Inconsistency - Data Storage Unspecific Error
0x980B
Backup Inconsistency - Upload Fault
0x980C
Parameter Inconsistency - Download Fault
0x980D
Port Class B Failure - Power Missing
0x980E
Short Circuit At Pin 2
0x980F
Revision Fault
0x9811
Compatibility Fault Vendor ID (IO-Link 1.0)
0x9812
Compatibility Fault Device ID (IO-Link 1.0)
0x9813
Compatibility Fault Vendor ID (IO-Link 1.1)
0x9814
Compatibility Fault Device ID (IO-Link 1.1)
0x9815
Serial Number Fault
0x9816
Generic Data Storage Fault
0x9817
Invalid Cycle Time
0xE000
Revision Fault- Incompatible Protocol Version
0xE001
Parameter Inconsistency - ISDU Batch Failed
0xE002
Device Not Available - Communication Lost
0xFF22
Invalid Backup - Data Storage Identification Mismatch
0xFF23
Invalid Backup - Data Storage Buffer Overflow
0xFF24
Invalid Backup - Data Storage Parameter Access Denied
0xFF25
Event Lost - Incorrect Event Signaling
0xFF31