SIOL-EI8B-USER-M
9
Description
Powered by
Version 1, May 2022
3.1.5. Rotary switch settings
NOTE
In the default state, the rotary switches are set to
000
, DHCP enabled.
NOTE
A unique IP address must be assigned to each device in the network.
Setting the IP Address on the Rotary Switches
Address range: 1–999
x1
Rotary switch 9ones)
x10
Rotry switch (tens)
x100
Rotary switch (hundreds)
Position/
Range Description
0
DHCP
Request the IP addresses via DHCP (can be changed to BOOTP via the WebUI or Explicit Messaging)
◼
After factory reset: DHCP
◼
The network parameters have been saved previously: The parameters saved last are used.
1–254
IP address
Byte 4
The last octet of the IP address (set via DHCP or WebUI) is overwritten by the DIP switch setting and applied.
The default IP address subnet is
192.168.1.xxx
255
Last saved
IP address
The IP address saved last is used. (192.168.1.6 by default)
256–776
Reserved
777
Fixed IP
The IP address is set STATIC at 192.168.100.177.
778–912
Reserved
913
Deactivate
web server
Disables the web server and TCP port 80. Only the WebUI is disabled.
914
Reactivate
web server
WebUI is enabled again.
915–978
Reserved
979
Factory reset
Sequence:
1 | Disconnect module from power supply.
2 | Set switch position 979.
3 | Supply module with power.
4 |
Wait until SF LED changes from flashing green to solid green
.
5 | Disconnect module from power.
6 | Switch position to 000 or any other desired position.
7 | Supply module with power.
980–999
Reserved
NOTE
The saved default IP address is 192.168.1.6.
NOTE
The IP address parameters are stored for all switch settings. This must be taken into account in
particular with the switch setting
0
.
Setting an address
1.
Remove the rotary switch cover.
2.
Set the three rotary switches.
3.
Carefully replace the rotary switch cover.
The tightening torques can be found in Section 5.4.2, “Rotary switch cover”.