background image

Page 25

IronHorse GSDA-CM-8 User Manual –  1st Ed. Rev. A – 10/15/19

Parameter 

(Item)

Description

Value Range

Units

Default

GSD8-

240-5C

All other 

GSD8 

drives

Real-Time Process Variable Parameters (Read Only)

1070 

2070

GSD8-AI-A8 - Input Current

0-4095

DAC 

Steps

1071 

2071

GSD8-AI-A8 - Drive Target Speed 0-9999

3

1072 

2072

GSD8-AI-A8 - Drive Target Output 

Current

0-4095

DAC 

Steps

1073 

2073

GSDA-AI-A8 - Condition Flags - 

(Future)

0 = No Active "Flags"

BDC

0

1074 

2074

GSDA-AI-A8 - Auto/Manual 

Switch State

0 = Manual 

1 = Auto

0

GSDA-CM-8 Option Card Read-Only Parameters

5001

Model Number

51 = GSDA-CM-8

51

5002

Software Version

1-9999

n/a

5003

Hardware Version 

1-9999

n/a

5004

Device Type

100 = Type 1 Card

100

5005

Minimum Supported Framework 

Version

1-9999

n/a

5006

Reserved

0

n/a

5007

Serial Number - Major

0-9999

n/a

5008

Serial Number - Minor

0-9999

n/a

Serial Communications Setup Parameters

5020

GSDA-CM-8 - Network Address

1-99

1

5021

GSDA-CM-8 - Baud Rate

1 = 300 

2 = 1200 

3 = 2400 

4 = 4800 

5 = 9600 

6 = 19200 

7 = 38400 

8 = 57600

5

User Assignable Output Parameters

5030

GSDA-CM-8 - Output Function

0 = Off 

1 = Frequency Generator - Analog 

IN 

2 = Frequency Generator - Motor 

Speed 

3 = Frequency Generator - Fixed 

(Parm 32) 

4 = Alarm Output

0

5031

GSDA-CM-8 - Output Selector 

(N.O. / N.C.)

0 = Normally Open (N.O.) 

1 = Normally Closed (N.C.)

0

5032

GSDA-CM-8 - Freq Generator - 

Output Freq

0-3 = Disabled 

4-9999

Pulse/min

0

5033

GSDA-CM-8 - Freq Generator - 

Min Freq

0-9999

Pulse/min

0

5034

GSDA-CM-8 - Freq Generator - 

Max Freq

4-9999

Pulse/min

2400

Analog Input Parameters

5040

GSDA-CM-8 - Analog Input 

Destination

0 = Off 

1 = Target Speed 

2 = Percent of Target Speed 

3 = Reserved 

4 = Frequency Generator Rate 

5 = Main Tach Signal

6 = Leader Tach Signal

(Eng. 

Units) 

 

Pulse/

min

RPM

RPM

0

5041

GSDA-CM-8 - Analog Input 

Source Type

1 = Potentiometer 

2 = 0 to +5 

3 = 4 to 20

VDC 

mA

1

Summary of Contents for GSDA-CM-8

Page 1: ...Page 1 IronHorse GSDA CM 8 User Manual 1st Ed Rev A 10 15 19 GSDA CM 8 ASCII Communications Module User Manual User Manual Number GSDA CM 8...

Page 2: ...rformance such as in the operation of nuclear facilities aircraft navigation or communication systems air traffic control direct life support machines or weapons systems in which the failure of the pr...

Page 3: ...Using the Analog Input 7 User Assignable Output 12 Communications and Networking 13 Commonly Used Software 13 Hardware Jumper Selection 13 RS 232 and RS 422 485 Connections to the RJ45 Modular Jack 14...

Page 4: ...d to work with you in answering your questions If you cannot find the solution to your particular application or if for any reason you need additional technical assistance please call Technical Suppor...

Page 5: ...per and software parameter setup Baud rate is configurable from 300 to 57600 In addition the GSDA CM 8 can output a square wave frequency from 4 pulses per minute to 9999 ppm An analog input is also a...

Page 6: ...stored configuration Up button to store factory defaults Down button to ignore card If the Up button is pushed the factory settings will be installed and the card will be initialized If the Down butto...

Page 7: ...odular connector and can be used with a variety of signals The signal from the analog input source can be used to provide control or feedback information to the GSD8 drive This application note will c...

Page 8: ...36 13 85 0 5 0 0 5 0 20 40 13 33 0 5 0 0 5 0 5 W 4 to 20mA Current Source Input A 4 to 20 mA current source type is tracked by the GSD8 drive at a 50 millisecond sample rate in the same way as the vo...

Page 9: ...nimum value is obtained with a current of 4mA or less Maximum Value Maximum Value refers to the highest scaled value produced by the GSDA CM 8 A to D converter when the analog source signal is at the...

Page 10: ...change that can be processed by the A D converter Mathematically the example looks like this Analog input signal 2 5V 0 00488V A D converter minimum voltage per count 512 counts digital equivalent 0...

Page 11: ...of 20VDC can result in permanent damage to the GSDA CM 8 For proper operation the useful signal range is zero to 5VDC 0 to 5VDC Voltage Source Input Wiring Connect B to Analog Input Pin 7 of RJ45 Mod...

Page 12: ...rm Logic section for a circuit description Otherwise you can use Ladder Logic symbology Using the Frequency Generator Output Parameter 5030 1 2 or 3 The GSDA CM 8 has a frequency generator output that...

Page 13: ...llows the computer to communicate with a selected com port You will need to configure the software to allow it to communicate with the GSDA CM 8 Serial Card These products ship with their serial commu...

Page 14: ...t RS 232 be run more than 50 feet Specialty converters can be purchased to allow an RS 232 device to interface with one or more units on a shared multi point bus Once the desired interface standard ha...

Page 15: ...omplete and functional otherwise it will be necessary to double check the wiring and repeat some of the above tests NOTE Many of the commercially available modular connectors cables you buy off the sh...

Page 16: ...age format is shown below command address command stuff CR Format Description command A two letter UPPERCASE command There is NO comma between the command and the address address A number 01 thru 99 r...

Page 17: ...sponse if unsuccessful N CR NOTE The Set Target Speed commands are not stored in non volatile memory consequently upon power up in Auto Mode they will revert to zero When powered up in Manual Mode the...

Page 18: ...Engineering Units as defined by the drive Format TS address CR Example Read the GSDA CM 8 addressed as 02 for the actual speed of the pickup in Engineering Units TS02 CR Response if successful value C...

Page 19: ...e Flags Table 1 Below BCD n a 9 Drive Condition Flags See Flags Table 2 Below BCD n a General Setup Parameters 10 Operating Mode 1 Rate Mode 2 Time Mode 3 Follower Mode 1 11 Display Intensity Display...

Page 20: ...Low Spd Mode Off 2 Gain Tracking Off Low Spd Mode On 3 Gain Tracking On Low Spd Mode On 1 23 Accel Setting 1 9999 Display units 2500 9999 24 Decel Setting 1 9999 Display units 2500 9999 26 Proportiona...

Page 21: ...cel Eng Units 0 43 Disable U1 in Manual Mode 0 Disabled 1 Enabled Eng Units 0 Alarm Output 1 Setup Parameters 50 Alarm Activation Condition 0 Always Off 1 Always On 2 Active Upper Limit 3 Active Lower...

Page 22: ...ee Flags Table 2 Below BCD 0 67 Alarm1 Logical AND Activation Conditions See Flags Table 2 Below BCD 0 Alarm Output 2 Setup Parameters 70 Alarm2 Logical OR Activation Conditions See Flags Table 1 Belo...

Page 23: ...0 99 Restore From User Default Memory Restore Swap Environment Drive All ModularBus Card Settings from User Save Storage Area 0 Abort Exit 1 Restore User Default Settings 5 Copy Restore current Settin...

Page 24: ...003 Hardware Version 1 9999 N A 1004 2004 Device Type 100 Type 1 Card 100 1005 2005 Minimum Supported Framework Version 1 9999 N A 1006 2006 Maximum Supported Protocol Version 1 9999 N A 1007 2007 Ser...

Page 25: ...9999 n a 5008 Serial Number Minor 0 9999 n a Serial Communications Setup Parameters 5020 GSDA CM 8 Network Address 1 99 1 5021 GSDA CM 8 Baud Rate 1 300 2 1200 3 2400 4 4800 5 9600 6 19200 7 38400 8 5...

Page 26: ...version that is compatible with this card 6 Reserved Reserved 7 Serial Number Major These Items are reserved for future use as an electronic serial number and are unique to each manufactured unit 8 S...

Page 27: ...of the GSD8 drive Mode 3 RESERVED Mode 4 Frequency Generator Rate This will control the frequency output of the frequency generator Note When using this mode Item 30 of the serial communications board...

Page 28: ...ntation to ensure correct functioning This example section shows network comms using GSDA with ASCII Baudrate in drive is 9 6Kbps 8 1 N by default NOP 2 This rung loads the Initial values for NodeAddr...

Page 29: ...nd String or Text N 0D 8 Counter of Yes reply Increasing values for the counter means the command was accepted StrmOutSuccess C0 StrmInSuccess C5 CompareYesReply C7 UP RST Up Counter CNT Counter Struc...

Page 30: ...cation Always verify the product documentation to ensure correct functioning This example section shows network comms using GSDA with ASCII Baudrate in drive is 9 6Kbps 8 1 N by default NOP This rung...

Page 31: ...tion Code 1 1 Variable Length Max Num of Chars CPU 485 Serial Port Comparing the reply message with Y and N SendCom mand1 C omplete ReceiveC ommand 1 Success Enable COMPARE STRINGS 1 Number of Charact...

Page 32: ...9 2 9 3 10 11 12 13 14 15 Reset of bits involved If there is no increment in any of the counters the string command is not correctly formed ReceiveC ommand 1 Success SendCommand RST SendCommand1 Compl...

Page 33: ...Page 33 IronHorse GSDA CM 8 User Manual 1st Ed Rev A 10 15 19 Literature Number LT181 Drawing Number A 5 4166B...

Reviews: