F
3-
-0
4D
A
--1
4-
C
ha
nn
el
A
na
lo
g
O
ut
pu
t
7--2
F3--04DA--1 4-Channel Analog Output
Module Specifications
The following table provides the specifications for the F3--04DA--1 Analog Output
Module. Review these specifications to make sure the module meets your
application requirements.
Number of Channels
4
Output Ranges
0 -- 5V, 0 -- 10V, 4 -- 12 mA,
4 -- 20 mA (source)
Resolution
12 bit (1 in 4096)
Output Type
Single ended (one common)
Output Impedance
0.5
O
typical, voltage output
Output Current
5 mA source, 2.5 mA sink (voltage)
Short-circuit Current
40 mA typical, voltage output
Load Impedance
1K
O
maximum, current output
2K
O
minimum, voltage output
Linearity Error
?
1 count (
?
0.03% maximum)
Maximum Inaccuracy at 77
°
F
(25
°
C)
?
0.6% of span, current output
?
0.2% of span, voltage output
Accuracy vs. Temperature
?
50 ppm /
_
C maximum
Conversion Time
30
µ
S maximum
Power Budget Requirement
144 mA @9V, 108 mA @ 24V
External Power Supply
None required
Operating Temperature
32
°
to 140
°
F (0
°
to 60
°
C)
Storage Temperature
--4
°
to 158
°
F (--20
°
to 70
°
C)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3--304
The F3--04DA--1 Analog Output appears as a 16-point module. The module can be
installed in any slot configured for 16 points. See the DL305 User Manual for details
on using 16 point modules in DL305 systems. The limitation on the number of analog
modules are:
S
For local and expansion systems, the available power budget and
16-point module usage are the limiting factors.
Analog Output
Configuration
Requirements