background image

4.  SETTING THE MINIMUM 

 

OUTPUT LEVEL OF CONTROL 

When the vibratory feeder is nearly empty, turn the 

MAIN CONTROL DIAL

 to “1” and adjust the 

MIN

 

trimpot to just below the slowest speed that provides 
the proper feed rate. The MIN trimpot also serves as 
the “low speed” trimpot for 2-speed operation.  See 
“S1 Programming Chart” for feature selection details. 

 

5.  MAIN CONTROL DIAL

 

The output power is controlled by the 

MAIN 

CONTROL DIAL

.  It is a logarithmic-tapered power 

out curve (non-linear) that spreads the power broadly 
across the 

MAIN CONTROL DIAL

 The logarithmic 

taper power curve helps to give maximum "Fine 
Control" over the output speed of the vibratory 
feeder.  When very precise adjustment of the 

MAIN 

CONTROL DIAL

 is needed, increase the MIN 

trimpot setting and/or decrease the MAX trimpot 
setting. For precise scaling at low amplitudes, use 
the linear POT taper or reduce the Max pot setting.  
To select a linear pot taper for the Main Control Dial, 
see the “S1 Programming Chart.”  

 

6. SETTING THE SOFT-START

 

The start-up rate of the control output can be 
adjusted to ramp up to the desired output level 
instead of starting abruptly.  Soft-start keeps parts 
from falling off the tooling, reduces spring shock, and 
hammering when the control turns ON.  Turn the 

SOFT

 Start trimpot clockwise for the gentlest start 

(about a 6 sec. ramp up to full output).  Turn the 
trimpot fully counter-clockwise for no soft start.

 

 

7. LINE VOLTAGE COMPENSATION 

Fluctuations in the line voltage can cause a feeder 
bowl to vary its feed rate.  The line voltage 
compensation feature adjusts the control's output to 
help compensate for fluctuations in the supply 
voltage. If it becomes necessary to disable this 
feature, set “Disable LVC” from the S1 programming 
chart

 

 

8.  REMOTE SPEED CONTROL 

Remote control of the power level can be 
accomplished by the following methods: 

A. 4-20mA signal from a PLC can be used to remotely 

vary the output of the control instead of the Main 
Control Dial.  The 4-20mA input is automatically in 
control whenever a 4-20mA signal is applied to the 
control (terminals TB2-8 & 9).  The Main Control 

dial setting is ignored whenever there is a 4-
20mA signal. The 4-20mA input is transformer 
isolated from the power line. In an environment 
with high electrical noise, use a shielded cable 
for the 4-20mA signal. The “S1 Programming 
Chart” shows how change to 0-20mA speed 
control instead of the default of 4-20mA.  

B.  A 0-5VDC Analog input signal may be applied 
in place of the Main Control Dial at H1.  The 0-
5VDC input is transformer isolated from the power 
line.  

9. SUPPLEMENTARY FEATURES 

Special supplementary software features can be 
enabled on the 24-210/24-211 circuit boards The 
features include: 

linear pot taper

0-20mA control

e

mpty bowl timer

low pulse rates, 

and

 two speed 

pots

. See the S1 Switch Programming Chart. 

Contact the manufacturer for more information.  

 

10. STATUS LEDs 

When any of the inputs are active, the associated 
LED will turn ON.  When the RUN input conditions 
are met, the RUN LED will turn ON.  See section 3 
and the wiring diagram’s ON/OFF Control Guide 
for more information on how to satisfy the RUN 
conditions. 

 

WARNING: 

 

Fuses should be replaced with a Bussman 
ABC or Littelfuse 3AB "Fast Acting" type or 
equivalent of manufacturer's original value. 

 

Mounting this control directly to a vibrating 
device will void the warranty. 

 

 

TROUBLESHOOTING 

 

Basic Procedure – To ascertain whether the 
problem lies in the controller, take the following 
steps: 
A.   Check for good fuses.  Disconnect the input 

power and tighten the screw terminals. 

B.   For the control output to be on: Make sure that 

the proper input power is present.  The 

MAIN 

CONTROL DIAL

 must be turned up or if the 

4-20mA input is used, it must have over 5mA. 
 Either the DIRECT LED must be lit or both 
the INTERLOCK and EXT VOLTS LEDs must 
be lit.  Anytime the output is turned on, the 
RUN LED will be ON.  To light the DIRECT 
LED, a Run Jumper must be connected at 

TB2-6 & TB2-7.  To light the INTERLOCK 
LED, a Run Jumper must connect TB2-5 to 
TB2-6.  To illuminate the EXT VOLTS LED, a 
10-30 VDC signal has to be present at TB2-11 
& 12.  See the section titled “

Remote OFF/ON 

control

” for more information. 

 C.  Connect an AC voltmeter across the LOAD 

terminals (with the LOAD connected) and vary 
the 

MAIN CONTROL DIAL

 from minimum to 

maximum.  In 120 pulse mode, the output 
should vary from approximately 30% to 98% 
of the input voltage depending on the setting 
of the 

MIN

 and 

MAX

 trimpots.  In 60 pulse 

mode the output should vary from 20% to 
around 85% of the input voltage. 

D.  On new installations: If the Feeder only hums 

but it doesn’t feed any parts, try changing the 

60/120

 DIP switch (S1) to the opposite 

position. 

 

When neither a humming sound nor any vibration 
can be detected in the vibratory feeder, the 
problem may be in the controller. 

 

 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

ADI 6006.2 24-211 131015.doc 

  Page 2 

S1 Programming Chart 

Program Description 

S1 Switch Positions 

 

SW3 SW4 SW5 

Standard 

Program

0 0 0 

Linear Pot Taper

0-20mA 

option

0 1 0 

Empty Bowl Timer

Disable 

LVC

0 0 1 

2-Speed 

Operation

1 0 1 

30/40 Pulse Operation

Low Voltage at “1” 

Reviews: