P.E. BEAM AND AUTO CLOSE

16

STEP 21 - FITTING THE SAFETY PHOTO 
ELECTRIC BEAM SENSOR (OPTIONAL)

Locate the Photo Electric Beam (P.E.) normally closed contact
type in a strategic location within doorway. We recommend
150mm above the floor level and as close as possible to the
door opening, inside the garage. Remove shunt from P.E
connector 

(Fig. 28)

and connect the plug from the P.E. wiring

harness to P.E. connector 

(Fig. 29)

. The wiring diagram is for

Model PHBE (Order Code 90214).
Make sure to align the beams correctly. Follow the manual 
supplied with the Photo Electric Beam.

WARNING; When using Auto Close Mode and P.E. beams,
the doorway must be clear of all obstructions and persons
at all times. The location of the beam and manner in which
it is installed might not give safety protection at all times.
Check to make sure that the height of the beam and type
used give maximum protection possible. 

STEP 22 - SETTING AUTO CLOSE TIME

IMPORTANT NOTICE: IT IS COMPULSORY TO
INSTALL A PHOTO ELECTRIC BEAM BEFORE USING
THE AUTO CLOSE MODE.

The Auto Close timer will only start after the Photo Electric
Beams (P.E.) path is broken and the auto close time has been
set. If the P.E. path is not broken the door will remain open until
the path is broken. If the door opener incurs an obstruction (not
from the P.E.) while closing the door will re-open and not auto
close until the path of the P.E. beam is broken again.

1.  

Press and hold the Auto Close Time button 

(Fig. 30)

.

2.

While holding the Auto Close Time button, press the Open

button 

(Fig. 30)

. Each press of this button will add five seconds

to the auto close delay time.

3.  

To decrease the delay time follow Step 1 and press the Close

button. Each press will deduct five seconds from the auto close
time.

4.  

Press the O/S/C button 

(Fig. 30)

or transmitter to open the

door. When the door is fully opened the Open Limit green LED
will flash to indicate that the auto close mode is in operation.
Break the path of the P.E. Beam momentarily, the door will
close after the set auto-close time has elapsed.

23.  RE-INITIALISING THE OPENER

To re-initialise the opener press and hold the Reset Button 

(Fig. 30) 

until the open limit LED illuminates. The door will

start to move and re-calculate force margins. The initialisation
is complete and the door is ready for use when the door has 
completed a full open and close cycle.

FIG. 29

FIG. 28

FIG. 30

Summary of Contents for GDO-2 SecuraLife

Page 1: ...lure to comply with the installation instructions and the safety warnings may result in serious personal injury and or property and remote control opener damage Please save these instructions for future reference Installation Instructions F Fe ea at tu ur ri in ng g SecuraCode Code Hopping Technology F Fe ea at tu ur ri in ng g SecuraCode Code Hopping Technology ...

Page 2: ...en persons or any other objects including motor vehicles within the doorway Install the wall switch or wall mounted transmitter in a LOCATION POSITION where it is out of reach of children and the garage door is visible The door opener is not intended for use by young children or infirm persons without adequate supervision Young children should be supervised to ensure that they do not play with the...

Page 3: ...n the opener has been overloarded and indicates that the opener and or garage door requires service AUTO COURTESY LIGHT The courtesy light on the opener comes on automatically whenever the door is activated The light can also be switched on and off without operating the door This is done by pressing the button on any hand held or wall mounted transmitter which has been stored with the light code T...

Page 4: ...ecomes operable 8 OPEN Drive button Green is used during installation to help set the open limit stop position Pressing this button will move the door in the open direction Movement stops when the button is released NOTE The open safety obstruction detection is disabled when the Open Drive button is used to move the door 9 OPEN LIMIT LED Green the LED is very helpful during installation it illumin...

Page 5: ...RED 4 CLOSE LIMIT LED RED 5 AUTO CLOSE BUTTON WHITE 6 SET BUTTON YELLOW 7 O S C BUTTON YELLOW 8 OPEN DRIVE BUTTON GREEN 9 OPEN LIMIT LED GREEN 10 FORCE MARGIN SET BUTTON 11 CLOSE LIMIT ADJUST SCREW RED 12 OPEN LIMIT ADJUST SCREW GREEN 13 P E SHUNT 14 O S C INPUT 15 ENGAGE DISENGAGEMENT HANDLE ...

Page 6: ...RIVE UNIT 1 SECURACODE KEY RING TRANSMITTER PTX 4 2 WALL MOUNT BRACKET FOR PTX 4 1 BATTERY A23 12V ALKALINE 2 TUBES 5 TUBE INSERTS 4 PIPE SUPPORT ASSEMBLY 1 CHAIN 1 SHUTTLE TROLLEY ASSEMBLY 1 DOOR ATTACHMENT ARMS 2 ACCESSORY PACK 1 INSTALLATION MANUAL 1 ...

Page 7: ...otection STEP 2 The opener is supplied with a 10 tooth Drive Sprocket on the drive unit If the opener is to be fitted to a one piece door with out track exchange the 10 tooth sprocket with a 7 tooth drive sprocket available as an option from ATA IMPORTANT If using track type door often referred to as panel lift or track tilt door only use a 10 tooth drive sprocket If using a one piece door without...

Page 8: ... on tracks Fig 5 proceed with the installation from Step 5 z For a one piece door on tracks Fig 6 proceed with the installation from Step 5 z For a one piece door without tracks on springs Fig 7 proceed with the installation from Step 9 Remember a one piece door without tracks requires a 7 tooth drive sprocket FIG 5 FIG 6 FIG 7 ...

Page 9: ... proper position attach the support pipe assembly to wall bracket with 90mm long clevis pin and secure with supplied snap pin Fig 10 leaving drive unit in its packing box for protection during installation STEP 8 Raise the drive unit from the packing box and support it in a horizontal position with a step ladder then open the garage door Rest the opener on the open door and use a scrap piece of wo...

Page 10: ...supplied A representative mounting is shown Fig 11 11a Connect angle and drive unit with two flat perforated strips of angle not supplied with M8 x 20mm screws nuts and washers The strips should not extend more than 18mm below centre of drive unit mounting holes Fig 11 11a Do not lock screws at this stage STEP 11 Close the door slowly The opener pipe tube will be elevated by the top edge of the do...

Page 11: ...te and uses 4 mounting holes for extra strength This is used on sectional doors See Fig 16 Mount the door bracket to the centre line of the door Fig 16 using M6 or equivalent screws not supplied Alternatively it can be welded on steel doors Note As various types of doors exist if in doubt about the strength of the door reinforcement may need to be added to the frame of the door panel where necessa...

Page 12: ...s are being used and travel limits are not set 4 Press and hold the green open button The door will start opening Release the button once you have reached your desired open limit position Fig 19 To fine tune the open limit position turn the green open limit adjust screw anticlockwise until the green open limit LED is illuminated 5 Press and hold the red close button Fig 19 The door will start clos...

Page 13: ...ss and hold the Force Margin Set button Fig 20 2 While holding Force Margin Set press the green Open button The green LED will illuminate each time the green open button is pressed to indicate that the force pressure is being increased If the green LED flashes continuously when the open button is pressed this indicates that the maximum force pressure setting has been reached 16 3 TO DECREASE FORCE...

Page 14: ...range of the opener 1 Take any pre coded transmitter Press the button for the function you require until the door is activated and release 2 Then using a small needle press through the Coding Hole and hold firmly for two seconds Fig 23 3 Within 10 seconds take the additional transmitter you wish to code 4 Press the button one of four on that transmitter you would like to use to control the door fo...

Page 15: ... Fig 26 Each press will deduct 10 seconds from the light time 4 To recall the factory set default light time press and hold the Auto Close Time Force Margin Set and Reset buttons together for about 2 seconds Fig 26 20 DELETING PROGRAMMED CODES 20 1 DELETING A STORED TRANSMITTER CODE 1 Select the transmitter you want to delete 2 Press and hold the Door Code button Fig 27 3 Press the transmitter but...

Page 16: ...o Electric Beams P E path is broken and the auto close time has been set If the P E path is not broken the door will remain open until the path is broken If the door opener incurs an obstruction not from the P E while closing the door will re open and not auto close until the path of the P E beam is broken again 1 Press and hold the Auto Close Time button Fig 30 2 While holding the Auto Close Time...

Page 17: ...OOR OVERLOADED ALTERNATING FLASHES ALTERNATING FLASHES FLASHES TEN TIMES BEEPS ON OFF DOOR OPENER APPROACHING OVERLOAD BEEPS WHILE DOOR IS MOVING DOOR APPROACHED OVER LOAD 3 TIMES IN 8 CYCLES ON BEEPS AT START OF CYCLE DOOR OPEN WITH AUTO CLOSE MODE SELECTED ONE SECOND FLASHES MAINS POWER INTERRUPTED RAPID FLASHES TECHNICAL SPECIFICATIONS INPUT VOLTAGE 230V 240V AC 50Hz Other voltages available up...

Page 18: ...eplace globe Edison Type 240V 60W must be rough service construction globe Auto close not working PE Beam or wiring faulty PE Beam not aligned correctly PE Beam is obstructed Door obstructed when closing Auto close time not set Repair PE Beam or replace wiring Re align optics Remove obstruction from the path of PE Remove obstruction See Step 22 on page 16 Please Note Some areas may be prone to exc...

Page 19: ...SPARE PARTS LIST 19 WHEN ORDERING SPARE PARTS PLEASE QUOTE THE ORDER CODE NUMBER TO YOUR YOUR INSTALLER DISTRIBUTOR ...

Page 20: ...tion instructions incorporated in the document e attempted or complete modification or repairs to the Product carried out by a person who is not authorised by ATA to carry out such modification or repairs f faulty or unsuitable wiring of structure to which the Product is fixed or connected and g radio including citizen band transmission or any electronic interference h blown fuses or damage caused...

Reviews: