PART I: INSTALLATION MANUAL
23
SERVOCONTROL CAMS ADJUSTMENT
Fig. 45 - Berger STA4.5BO.37/6 - STA13B3.41
Setting the microswitches cams
For the setting refer to this correspondence table.
AIR PRESSURE SWITCH SETTING
BERGER
High flame position (set to 90°)
I
Stand-by position (set to 0°)
II
Not used
III
Low flame and ignition position
IV
Calibration of air pressure switch (single stage burners)
Calibration is carried out as follows:
z
Remove the transparent plastic cap.
z
With the burner in operation, after the gas and air settings have been
completed, rotate slowly the adjusting ring nut VR, and let the burner
lock; read the pressure value on the scale of the pressure switch and
decrease it of 0,5 mbar.
z
Repeat the start-up cycle and check the burner runs properly.
z
Refit the transparent plastic cover on the pressure switch.
Calibration of air pressure switch (high-low flame burners)
Calibration is carried out as follows.
z
Remove the transparent plastic cap.
z
With the burner in operation, after the gas and air settings have been
completed, rotate slowly the adjusting ring nut VR, and let the burner
lock; read the pressure value on the pressure switch scale and reduce
it by 15%.
z
Repeat the start-up cycle and check the burner runs properly.
z
Refit the transparent plastic cover on the pressure switch
Fig. 46
I
II
III
IV
VR
Summary of Contents for Enterprise LG 120
Page 1: ......
Page 30: ...PART III MAINTENANCE MANUAL 30 Wiring diagram cod 01 319 4 Single stage burners ...
Page 31: ...PART III MAINTENANCE MANUAL 31 Wiring diagram 18 069 Rev 1 High Low flame burners ...
Page 32: ...PART III MAINTENANCE MANUAL 32 Wiring diagram 18 069 Connectors layout on printed circuit ...
Page 41: ...APPENDIX COMPONENTS SPECIFICATIONS 41 ...
Page 42: ...APPENDIX COMPONENTS SPECIFICATIONS 42 ...