background image

10

Rev. (30-JAN-98) • RLM v4.7

© 1995-98 Automated Logic Corporation

The resistance values of the slidepot in Figure 15
(left column) were obtained by measuring the
resistance of the positions of the slidepot in 1/8
increments (far left, 1/8, 1/4, 3/8... far right).

Note that the slidepot input values (see Figure 15,
right column) are defined with a setpoint-bias rather
than absolute temperatures.  The GFB can be
designed to multiply these input values by a user-
definable parameter as the slidepot is adjusted and
then add the result to the zone setpoint.  This method
allows you to globally modify the above parameter
for all function blocks in the module instead of
changing the lookup table parameters for each zone.

Figure 15:  Example Custom Table for a Sample

Slidepot

(Tested Resistance Entered on the Left)

Figure 14:  Example Custom Table for a

Precon Type 3 Thermistor Sensor

Custom Translation Tables

In addition to the inputs already mentioned, it is possible
to create translation tables for non-standard thermistor or
slidepot inputs.  Provided on the parameter page of the
R683 module driver (see Parameter Page) are two user
definable tables for translating these inputs.

The following are typical applications for the custom
translation tables:

Thermistors other than Type 2 (such as Type 3).

Slide potentiometer inputs.

Non-linear voltage inputs.  (0-5 VDC maximum
range)

These tables use a 10 point linear translation method to
approximate a non-linear curve of resistance or voltage to
the desired units.

Procedure

1.

Display the R683 module driver parameter page (FB
#15) in SuperVision.

2.

For thermistor, slidepot, and other resistance inputs
set the option "Is input specified in voltage?" to NO.
For voltage inputs, set the option to YES.

3.

Determine the accuracy and range needed.  Note the
following:

Values which lie between two defined entries are
interpolated linearly by the FB.

The first and last entries of the resistance table
should always be set to zero and infinity
(32767x 10 represents infinity) in the event that
the sensor should short or open.  In the case of
voltage inputs, the first and last input voltages
should be set to zero and 5 V.  These are the
default values.

4.

Determine the resistance or voltage at the desired
settings.  This information may be obtained either
from manufacturer reference tables or through
testing.

5.

Select a custom translation table that is not currently
in use.  Record the custom gain from this table for
use when defining inputs which will reference this
custom translation table in the module.

6.

Enter the scaled voltage or resistance input on the
left and then enter the corresponding value on the
right (see Figures 14 and 15 for examples).

Input Ohms

Input Value

0

x  10

Ohms

=

300

230

x 10

Ohms

=

150

405

x 10

Ohms

=

120

752

x 10

Ohms

=

90

935

x 10

Ohms

=

80

1172

x 10

Ohms

=

70

1478

x 10

Ohms

=

60

1879

x 10

Ohms

=

50

2406

x 10

Ohms

=

40

7032

x 10

Ohms

=

0

32767

x 10

Ohms

=

-60.8

Input Ohms

Input Value

0

x  10

Ohms

=

-1.00

474

x 10

Ohms

=

-1.00

607

x 10

Ohms

=

-0.75

910

x 10

Ohms

=

-0.50

1210

x 10

Ohms

=

-0.25

1540

x 10

Ohms

=

0.00

1860

x 10

Ohms

=

0.25

2150

x 10

Ohms

=

0.50

2360

x 10

Ohms

=

0.75

2400

x 10

Ohms

=

1.00

32767

x 10

Ohms

=

1.00

Summary of Contents for R683

Page 1: ...ne Sensor 5 Enhanced Zone Sensor 5 Using the Enhanced Zone Sensor 6 Local Setpoint Adjust 6 Timed Local Override 6 Occupancy Indication 6 LocalAccess 7 UniversalInputs 9 Procedure 9 Custom Translation...

Page 2: ...s provided for diagnostic operations The R683 module can store a single Graphic Function Block GFB Specifications Power 24 VAC 50 60 Hz 20 VA 0 83 A maximum Inputs One enhanced zone sensor port and 8...

Page 3: ...he two large holes allow screws to pass through the module and hold the enclosure to the surface on which it is mounted see Figure 2 Panel Mounting To mount the R683 module directly to a surface the N...

Page 4: ...cation 6 Verify that 24 VAC is present at the power input NOTE Before turning the power on see Addressing and Baud Rate later in this document An error condition will occur if the address of the R683...

Page 5: ...nput 1 UI 1 connect the zone sensor wires to pins 1 and 2 on the 8 pin receptacle on the R683 module see Figure 5 3 Turn the module s power switch back ON 4 Input the channel number offset and gain on...

Page 6: ...page For example if the increment is set at 60 toggle the switch once for an occupancy of 60 minutes twice for 120 minutes etc Once the zone is occupied from this switch pressing it again and holding...

Page 7: ...ation is shown below The cable should not exceed 50 ft See Figure 11 for how to use the switches on the NI485 cable NOTE When making a sensor cable disregard the numbers imprinted on the plastic conne...

Page 8: ...8 Rev 30 JAN 98 RLM v4 7 1995 98 Automated Logic Corporation Figure 12 R683 I O Connections...

Page 9: ...pply see Figure 6 In some special cases when the module s power is limited a 4 20 mA passive transducer does require and external power supply to avoid power consumption from the module Table 1 Proced...

Page 10: ...r voltage to the desired units Procedure 1 Display the R683 module driver parameter page FB 15 in SuperVision 2 For thermistor slidepot and other resistance inputs set the option Is input specified in...

Page 11: ...dure 1 Turn the R683 s power switch OFF 2 Terminate the output wiring to the top termination strip as shown in Figure 12 3 Turn the R683 s power switch ON Digital Outputs The R683 has six digital outp...

Page 12: ...683 s power switch OFF 6 Set the R683 s address and baud rate using the 8 position dip switch see Figure 1 for location 7 Turn the R683 module s power ON The module is now formatted LEDs Identificatio...

Page 13: ...age and verify that the module type and number agrees with the module to be transferred 4 Transfer memory to this module For SuperVision 2 6 and earlier click on the Download icon and choose the Memor...

Page 14: ...5 06 Is input specified in voltage YES 0 Millivolts 0 00 500 Millivolts 50 00 1000 Millivolts 100 0 1500 Millivolts 150 0 2000 Millivolts 200 0 2500 Millivolts 250 0 3000 Millivolts 300 0 3500 Millivo...

Page 15: ...0 00 1 5 88 27 to 1 0 0 6 C 0 00 1 5 69 Zo ne Se nso r Inp ut RS Z Zo ne Se nso r Inp ut RS Z The rm isto r The rm isto r 39 39 1 7 to 2 13 F 0 00 1 5 88 27 to 1 0 0 6 C 0 00 1 5 69 S etpo int Ad jus...

Page 16: ...imer Normally at 10 minutes when the module is not halted Counts down when the module is halted or has other serious errors When it reaches zero the module re initializes itself to try to clear the so...

Reviews: