2.3 WIRING CONNECTIONS
External connections are by 27 screw terminals as follows:
Screw terminals are 7.5mm and 5mm spacing rising clamp style with 2.5mm²
wire entry size for power connections and with 1.5mm² wire entry size for
signal connections.
The terminal identification and description are provided below, together with
the maximum terminal capacity in mm
2
(shown in brackets). Note that some
terminals may require more than one cable to be terminated, and therefore
cable sizing should be selected accordingly. The 12V dc and 0V dc terminals
may require several cables to be terminated in a separate connector,
according to the number of remote sensors required. Any series wiring for
occupancy or switch sensor inputs should be achieved using a separate
connector.
CONTROLS SUPPLY
LIVE
Live supply input
(2.5)
NEUT Neutral
supply
input
(2.5)
E stud Earth termination point
(2.5)
INPUTS
S1+
Sensor 1
(1.5)
S1-
Sensor 1 signal -
(1.5)
S2+
Sensor 2
(1.5)
S2-
Sensor 2 signal -
(1.5)
S3+
Sensor 3
(1.5)
S3-
Sensor 3 signal -
(1.5)
OUTPUTS
ANO
Analogue output 0 – 10V (1.5)
GND
0V dc output
(1.5)
12V
12V dc output
(1.5)
INPUTS
S4+
Sensor 4
(1.5)
S4-
Sensor 4 signal -
(1.5)
S5+
Sensor 5
(1.5)
S5-
Sensor 5 signal -
(1.5)
S6+
Sensor 6
(1.5)
S6-
Sensor 6 signal -
(1.5)
RELAY CONNECTIONS
R12I
Relay 1 and 2 common input(2.5)
R1O Relay
1
output
(2.5)
R2O Relay
2
output
(2.5)
R3O Relay
3
output
(2.5)
R3I Relay
3
input
(2.5)
R4O Relay
4
output
(2.5)
R4I Relay
4
input
(2.5)
R5O
Relay 5 output (Live)
(2.5)
R6O
Relay 6 output (Live)
(2.5)
R7O
Relay 7 output (Live)
(2.5)
Figure – Terminal connections
*NOTE: RELAYS 1-4 ARE VOLT FREE. CONNECT SUITABLE VOLTAGE TO
R12I, R3I, R4I*
S1
+ S1-
S
2
+
S
2
-
S
3
+
S3-
A
N
O
GND 1
2
V S
4
+
S
4
-
S5+
S5
- S6
+
S
6
-
R4I R5O R6O R7O LIVE NEUT
R12I R1O R2O R3O R3I R40