23
C1 Zone
1
Sensor
Assignment
Read/Write 00 00
to
63
Sensors assigned to lighting
zone 1.
(see tables on pages 24 & 25)
C2 Zone
2
Sensor
Assignment
Read/Write 00 00
to
63
Sensors assigned to lighting
zone 2.
(see tables on pages 24 & 25)
C3 Zone
3
Sensor
Assignment
Read/Write 00 00
to
63
Sensors assigned to lighting
zone 3.
(see tables on pages 24 & 25)
C4 Zone
4
Sensor
Assignment
Read/Write 00 00
to
63
Sensors assigned to lighting
zone 4.
(see tables on pages 24 & 25)
C5 Zone
5
Sensor
Assignment
Read/Write 00 00
to
63
Sensors assigned to lighting
zone 5.
(see tables on pages 24 & 25)
C6 Zone
6
Sensor
Assignment
Read/Write 00 00
to
63
Sensors assigned to lighting
zone 6.
(see tables on pages 24 & 25)
L1 Lux
Level
hysteresis
Read/Write 05 01
to
25
Hysteresis applied as a
percentage of lux level.
A1 Alarm
Temperature
Read/Write 00 -9
to
30
Alarm temperature set point, in
degrees C.
0=Alarm relay contacts close
when temperature is below A1.
A2 Alarm
Relay
Operation
Read/Write 00 00
to
01
1= Alarm relay contacts close
when temperature is above A1.
F1 Frost
Protection
Temperature
Read/Write 00 -9
to
20
Frost protection temperature
set point, in degrees C.
b1 Analogue Output
Bandwidth
Read/Write 10 01
to
50
Analog output LUX level
bandwidth for full output, in %
decrease from set lux level.
0=zone relays 1 to 6 have
normally closed operation
(open for light).
O1 Zone Relay
Operation
Read/Write 00 00
to
01
1=zone relays 1 to 6 have
normally open operation (close
for light).