INSTRUCTION MANUAL «
I-STATION
»
13
The charger does not require any special setup or adjustment before it is switched on.
Before connecting the charger station to the grid, make sure that:
• The power supply (input) cable on the mains side is de-energized by external disconnecting
devices.
• The mains input has a connection diagram of 3 phases with separate neutral (N) and ground
conductors (PE).
• If you connect a 4-wire cable, make the protective earth connection with a separate
conductor.
To connect the station to the electrical circuit, connect the input power cable (the cross-
section depends on the station configuration) to the corresponding input terminals (L1,
L2, L3, N, PE). The following figure shows an example of how to connect a station in the
«1Type2» configuration. If the connection is made with a 4-wire cable, the external
grounding should be made with a cross section of at least 6 mm2 marked «PE» in the wiring
compartment. It is strictly forbidden to supply voltage to the mains input of the charging
station when the ground is not connected.