579-1200AC Rev. D
TrueAlert ES Addressable Indoor Audible Notification Appliance installation instructions
*05791200ACD*
Cautions, warnings, and regulatory information
Important:
When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires immediate atten-
tion of all occupants.
SAFETY:
Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and
instructions may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high
voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance
Circuit is disconnected at the control panel before installing, repairing, or internally adjusting any notification appliances. Even with
electrical power removed, some notification appliances (such as visible strobes) store a high voltage charge. The high voltage can cause
injury resulting in death from electrical shock. DO NOT TOUCH EXPOSED CIRCUITRY.
LOCATION REFERENCE:
Location and quantity of appliances required must conform to the applicable local standards and guidelines
(the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate
model building codes, etc.) and specific requirements of the local Authority Having Jurisdiction (AHJ). These notification appliances are
not intended for installation within hazardous locations as defined by the National Electrical Code (NEC) or NFPA.
UL listed TrueAlert ES indoor product identification reference
Table 1: Product identification reference
Type
Colors
Models
Wall Mount
Audible Only
(A/O)
Red
White
Components:
A59AO-APPLWR
A59AO-APPLWW
Covers:
A59AOC-WRF
A59AOC-WWF
A59AOC-WRFAB
A59AOC-WWFAB
A59AOC-WRS
A59AOC-WWS
Operation
These appliances provide an audible (AO) warning of an alarm condition when activated from the control panel of a compatible
UL/ULC Listed, Autocall Fire Alarm System.
Note:
For information about TrueAlert ES appliance testing, see
TrueAlert ES Addressable LED Appliances Troubleshooting
(579-1168AC).
*Appliance x1.
*Cover x1.
6-32 1 inch mounting screws (x2). Do not over tighten.
Required parts:
*Autocall parts
Single gang electrical box, 1-1/2 inch minimum depth required.
Mounting instructions
1.
Select the mounting location, and install the electrical box.
2.
Connect the building wires to the appliance. See
.
3.
Use the provided hardware to secure the appliance to the electrical box.
4.
Set the appliance settings. See
Setting the address DIP switch
.
5.
Attach the cover to the appliance.
Figure 1: Mounting instructions