TrueAlert ES Addressable Indoor Audible Notification Appliance installation instructions

*05791200ACD*

Cautions, warnings, and regulatory information

Important: 

When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires immediate atten-

tion of all occupants.

SAFETY:

 Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and

instructions may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high

voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance

Circuit is disconnected at the control panel before installing, repairing, or internally adjusting any notification appliances. Even with

electrical power removed, some notification appliances (such as visible strobes) store a high voltage charge. The high voltage can cause

injury resulting in death from electrical shock. DO NOT TOUCH EXPOSED CIRCUITRY.

LOCATION REFERENCE:

 Location and quantity of appliances required must conform to the applicable local standards and guidelines

(the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate

model building codes, etc.) and specific requirements of the local Authority Having Jurisdiction (AHJ). These notification appliances are

not intended for installation within hazardous locations as defined by the National Electrical Code (NEC) or NFPA.

UL listed TrueAlert ES indoor product identification reference

Table 1: Product identification reference

Type

Colors

Models

Wall Mount

Audible Only

(A/O)

Red
White

Components:

A59AO-APPLWR
A59AO-APPLWW

Covers:

A59AOC-WRF
A59AOC-WWF
A59AOC-WRFAB

A59AOC-WWFAB

A59AOC-WRS
A59AOC-WWS

Operation

These appliances provide an audible (AO) warning of an alarm condition when activated from the control panel of a compatible

UL/ULC Listed, Autocall Fire Alarm System.

Note: 

For information about TrueAlert ES appliance testing, see 

TrueAlert ES Addressable LED Appliances Troubleshooting

 (579-1168AC).

*Appliance x1.
*Cover x1.
6-32 1 inch mounting screws (x2). Do not over tighten.

Required parts:

*Autocall parts

Single gang electrical box, 1-1/2 inch minimum depth required.

Mounting instructions

1.

Select the mounting location, and install the electrical box.

2.

Connect the building wires to the appliance. See 

Wiring instructions

.

3.

Use the provided hardware to secure the appliance to the electrical box.

4.

Set the appliance settings. See 

Setting the address DIP switch

.

5.

Attach the cover to the appliance.

Figure 1: Mounting instructions

Summary of Contents for A59AO-APPLWR

Page 1: ...Signaling Code NFPA 72 ULC Standard CAN ULC S524 Installation of Fire Alarm Systems the appropriate model building codes etc and specific requirements of the local Authority Having Jurisdiction AHJ These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical Code NEC or NFPA UL listed TrueAlert ES indoor product identification ref...

Page 2: ...es on an IDNAC channel is 127 The maximum number of active appliances is limited to 3 amps per circuit Refer to the field wiring diagrams for the driving compatible fire alarm control panel for further instructions b Notification appliances are rated using an individual module label c Maintain the correct polarity on the terminal connections d Terminals and can each accommodate 2 wires one wire go...

Page 3: ... the switches using a non metallic stylus or the equivalent 3 Record the set address 4 Confirm the setting for the appliance at this address with the Fire Alarm Control Panel FACP system configuration documentation DIP switch position 8 determines whether this appliance is viewed by the system as an ALARM OFF or ALERT ON type appliance Figure 3 Setting the DIP switch address Setting the appliance ...

Page 4: ... Note 1 23 86 9 83 3 High Volume Setting using Addressable Controller See Note 3 29 5 88 4 84 7 23 85 7 81 2 Low Volume Setting using Addressable Controller See Note 3 29 5 87 7 83 3 Anechoic room at 10 feet in accordance with ULC S525 see note 4 see note 4 23 93 8 93 7 High Volume Setting 29 5 95 2 95 1 23 87 5 87 4 Low Volume Setting 29 5 89 5 89 4 Note 1 The coded category covers both Temporal ...