TrueAlert ES Addressable Indoor Audible Notification Appliance installation instructions

Setting the address DIP switch

Each addressable TrueAlert ES notification appliance has a unique address that is set with an eight-position DIP switch (ADDR1). Assign up to 127

unique addresses to an SLC, however, the total appliance loading available may be less due to appliance current requirements.
To set the address, complete the following steps:

1.

Locate the 8-position DIP switch on the bottom left front of the appliance, see Figure 3. You must set the DIP switch before you snap on the

cover.

2.

Set the switches using a non-metallic stylus, or the equivalent.

3.

Record the set address.

4.

Confirm the setting for the appliance at this address with the Fire Alarm Control Panel (FACP) system configuration documentation. DIP

switch position 8 determines whether this appliance is viewed by the system as an 'ALARM' (OFF) or 'ALERT' (ON) type appliance.

Figure 3: Setting the DIP switch address

Setting the appliance configuration

You can configure certain options for the horn and strobe directly on the appliance using the appliance configuration switch (CFIG1) located on the

front of the appliance, see Figure 4.

A/O only:
Position 1:

 Configuration Control - OFF to enable Local Audible control,

ON for panel control.

Position 2:

 Audible Volume - High (OFF), Low (ON).

Position 3:

 Not used.

Figure 4: Setting the strobe and appliance configuration

Summary of Contents for A59AO-APPLWR

Page 1: ...Signaling Code NFPA 72 ULC Standard CAN ULC S524 Installation of Fire Alarm Systems the appropriate model building codes etc and specific requirements of the local Authority Having Jurisdiction AHJ These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical Code NEC or NFPA UL listed TrueAlert ES indoor product identification ref...

Page 2: ...es on an IDNAC channel is 127 The maximum number of active appliances is limited to 3 amps per circuit Refer to the field wiring diagrams for the driving compatible fire alarm control panel for further instructions b Notification appliances are rated using an individual module label c Maintain the correct polarity on the terminal connections d Terminals and can each accommodate 2 wires one wire go...

Page 3: ... the switches using a non metallic stylus or the equivalent 3 Record the set address 4 Confirm the setting for the appliance at this address with the Fire Alarm Control Panel FACP system configuration documentation DIP switch position 8 determines whether this appliance is viewed by the system as an ALARM OFF or ALERT ON type appliance Figure 3 Setting the DIP switch address Setting the appliance ...

Page 4: ... Note 1 23 86 9 83 3 High Volume Setting using Addressable Controller See Note 3 29 5 88 4 84 7 23 85 7 81 2 Low Volume Setting using Addressable Controller See Note 3 29 5 87 7 83 3 Anechoic room at 10 feet in accordance with ULC S525 see note 4 see note 4 23 93 8 93 7 High Volume Setting 29 5 95 2 95 1 23 87 5 87 4 Low Volume Setting 29 5 89 5 89 4 Note 1 The coded category covers both Temporal ...

Reviews: