Maximum loading of automatic circuit breakers
Calculation uses typical values from ABB series S200 as a reference.
Actual values may differ due to used circuit breaker types and installation environment.
Harmonic distortion in the mains supply (at 230V/50Hz and full load)
Dimming
Dimming range 1 % bis 100 %
Digital control with:
• DSI signal: 8 bit Manchester Code, Speed 1% to 100% in 1,4 s
• DALI signal: 16 Bit Manchester Code, Speed 1% to 100% in 0,2 s
Programmable parameter:
Minimum dimming level = 1 %, Programmable range 1% ≤ MIN ≤ 100%
Maximum dimming level = 100 %, Programmable range 100% ≥ MAX ≥ 1%
Dimming curve is adapted to the eye sensitiveness.
Dimming is realized by amplitude dimming.
Dimming characteristic
Acc. to 61000-3-2. Harmonics < 5 mA or < 0.6% (whatever is greater) of the input current are not
considered for calculation of THD.