12
Installation
D. - Terminal connection diagrams
S6
V1
V2
+
S5
S4
S3
S2
S1
-
PELV
R3I
R3
R2 R1
L
N
VFS2
VFS1
CAN CAN
D.1. - „With circulation pump“
Danger
Mains side
230VAC
Sensor side
max. 12V
Caution
Mains voltages 230VAC 50-60Hz
Connection in the right-hand terminal
compartment!
Terminal: Connection for:
L
Mains phase conductor L
N
Mains neutral conductor N
R1
Primary pump (opt.)
R2
Relay 2
R3
Relay 3 (normally open)
R3I
Relay 3 (normally closed)
The PE protective conductor must be
connected to the PE metal terminal block!
Low
voltage
max. 12VAC/DC connection in
the left-hand terminal compartment!
Terminal: Connection for:
S1
Circulation (opt.)
S2
Cold water (optional, see box below)
S3
Primary flow (opt.)
S4
Storage top (opt.)
S5
storage middle (opt.)
V1
0-10V/PWM signal primary pump
V2
0-10V/PWM signal (opt.)
S6
Primary return flow (opt.)
-
Terminal connection sensor -
VFS1
Warm water tap
VFS2 optional
The polarity of the sensors is freely selectable.
Relay connection changes depending on the additional functions selected.
Connection of sensor earths (1-6) via terminal block sensor(-)
VFS sensor has to be connected to the socket on the circuit board.
Sensor 2 / Cold water: If no sensor is connected, a temperature of 10° C is set. See also „6.2
Sensor calibration“