AURORA UPC ZS ZONE SENSORS INSTALLATION GUIDE

To wire and mount a ZS zone sensor 

The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain, star, or hybrid configuration. 

PREREQUISITE

  The Rnet cable is wired to the controller. The shield wire and the ground wire should be inserted 

into the controller's GND terminal. 
  

Turn off the controller's power. 

Using a hex screwdriver, turn the setscrew clockwise until it stops turning.  

Pull out the bottom of the backplate, and then pull off the backplate.  

Pull the Rnet communication cable through the wire guide in the backplate. 

  

3.30 in.

(8.38 cm)

 

  

Use 2 screws to mount the backplate to the wall or outlet box. 

Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation. 

  

Inner insulation

Outer jacket

Foil shield

.25 in.

(.6 cm)

Shield wire

 

  

Strip about .25 inch (.6 cm) of the inner insulation from each wire.  

If wiring 1 cable to the ZS Sensor, cut the shield wire off at the outer jacket, then wrap the cable with tape at 

the outer jacket to cover the end of the shield wire. 

If wiring 2 cables in a daisy-chain configuration, twist together the shield wires, then wrap the shield wires 
with tape. 

Specifications for ZS zone sensors 

ZS zone sensors 

Summary of Contents for UPC ZS ZONE SENSOR

Page 1: ...Aurora UPC ZS Zone Sensors Installation Guide Aurora Universal Protocol Converter UPC ZS Zone Sensors Installation Guide IG1582EW 06 18...

Page 2: ......

Page 3: ...pecifications Power requirements ZS zone sensors 8 Specifications for ZS zone sensors CO2 sensor installation Motion sensor installation To address a ZS zone sensor To wire and mount a ZS zone sensor...

Page 4: ...x OEMPrtl Pro The following table shows the ZS Sensor models their features and the available configurations Zone Sensors Features Available configurations Part number ZS Standard x Local access port...

Page 5: ...midity Temp and CO2 Temp humidity and CO2 Temp and motion Temp humidity and motion Temp CO2 and motion Temp humidity CO2 and motion ZS2P ZS2P H ZS2P C ZS2P HC ZS2P M ZS2P HM ZS2P CM ZS2P HCM x Green L...

Page 6: ...troller s Rnet depends on how many control programs it can have If the controller supports x Only one control program the Rnet can consist of x Up to 5 ZS sensors x One Wireless Adapter supporting up...

Page 7: ...r maximum signal integrity Description 4 conductor shielded or unshielded CMP plenum rated cable Conductor 22 AWG 7x0096 bare copper Maximum length 500 feet 152 meters Insulation Low smoke PVC or equi...

Page 8: ...ION GUIDE Power requirements See the sensor specifications for power requirements and power supply information CAUTION Do not share power between controller s power and external 12 Vdc unless both dev...

Page 9: ...0 C 0 36 F 0 2 C Temperature if humidity is included 50 to 104 F 10 to 40 C 0 54 F 0 3 C Humidity 10 to 90 1 8 typical Less than 0 5 drift per year CO2 400 to 1250 PPM 30 PPM or 3 of reading whichever...

Page 10: ...dle to 190 mA CO2 measurement cycle A ZS Pro with motion sensor has the same power requirements as a ZS Pro without a motion sensor Power supply The 4 conductor Rnet cable from a controller supplies 1...

Page 11: ...nsor on a ZS Pro needs to have a direct line of sight to the occupants in the room If the size of the room exceeds the maximum detector range use multiple sensors to adequately monitor the area Avoid...

Page 12: ...l the Rnet communication cable through the wire guide in the backplate 3 30 in 8 38 cm 5 Use 2 screws to mount the backplate to the wall or outlet box Partially cut then bend and pull off the outer ja...

Page 13: ...ield shield wire or a metal surface other than the terminal block the device may not communicate correctly 9 Attach the sensor s cover and circuit board to the mounted backplate inserting the top firs...

Page 14: ...splay the effective setpoint values They can display a maximum value of 99 or 99 5 if the Edit Increment is set to 0 5 If the effective setpoint exceeds this maximum value or if the Edit Increment is...

Page 15: ...from the sensor b Note the current position of the DIP switches c Set all DIP switches to the ON position d Reattach the wiring connector to format e After approximately 3 seconds remove the wiring c...

Page 16: ...icy of continual product research and development and reserves the right to change design and specifications without notice Product Aurora UPC ZS Zone Sensors Document Type Installation Guide Part Num...

Reviews: