- EE -if the temperature measured by the SR1
sensor exceeds 90oC, the cyclical operation mode of the
fan will be inactive (no control and the OUT5 output), and
the display will show the “EE” message., protecting against
excessive burning in the boiler furnace. If the temperature
measured by the SR1 sensor drops below 90oC, the
controller resumes the cyclical operation of the fan, with the
intervals between blow-downs according to the settings.
6.4 Wiring diagram: controller - fan and
controller - pump
NOTE
: When only the SR1 sensor is connected,
the remaining functions of the controller are not
active, i.e. the C.H. pump in the fireplace heating
system, and the D.H.W. pump are not indicated.
A
B
C
D
SR1 SR2 SR3
OUT1
OUT2
OUT3
OUT4
OUT5
IN
BOILER
C.H. pump
L 230VAC
Temperature
sensor
Air blower
AURATON 1111 Multi
21
EN