6.2 Operation of the controller
6.2.1) Załączanie sterownika
Starting the controller Put the switch in position “
I
”. All
display segments will light up for about 2 seconds. Then,
the display will show the current temperature on the
sensor.
6.2.2) Settings range
NTemperature settings (from 10oC do 90oC).
The operation time and blow-down interval settings: from
0 to 59 seconds, and then from 1 do 99 minutes.
The fan is controlled by means of the OUT 5 output. The
set temperature refers to the temperature measured by the
SR1 sensor (C.H.). The hysteresis (temperature difference
between the activation and deactivation) is 4oC.
6.2.3) Changing the temperature settings
Press the “
D
” button briefly - the factory (default) set value
of 50oC will start to blink. Then, use the “
+
” (increase) or “
-
“
(decrease) buttons to set the required temperature above
which the fan will be switched on and off.
Confirm by pressing “
OK
” within 10 seconds. Otherwise,
the new set value will not be stored in the memory and the
controller will return to the previous setting.
6.2.4) Changing the operation time and operation
cycles
When the “
D
” button is depressed once, the fan triggering
temperature will start to blink.
If the “
D
” button is depressed again within 10 seconds, you
enter into the fan operation cycles programming mode
(blow-down duration times, the default value is 15
seconds). Use the “
+
” (increase) or “
-
“ (decrease) buttons
to set the required value (when you exceed 59 seconds,
the time will automatically be displayed in minutes).
If the “
D
” button is depressed again within 10 seconds, you
enter into the fan operation cycles programming mode
(intervals between blow-downs, the default value is 5
minutes).
AURATON 1111 Multi
19
EN