5.3.
Accessories for electrical connection
5.3.1.
Parking frame
Figure 19: Parking frame, example with SH plug/socket connector and cover
Application
Parking frame for safe storage of a disconnected plug or cover.
For protection against touching the bare contacts and against environmental
influences.
5.3.2.
External earth connection
Figure 20: Earth connection for multi-turn actuator
Application
External earth connection (U-bracket) for connection to equipotential compensation.
Table 9:
Terminal cross sections and earth connection tightening torques
Tightening torques
Terminal cross sections
Conductor type
3 – 4 Nm
2.5 mm² to 6 mm²
Solid wire and stranded
3 – 4 Nm
1.5 mm² to 4 mm²
Fine stranded
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.