Figure 64:
Access to fuses
[1]
Local controls
[2]
Signal and control board
[3]
Power supply unit
F1/F2
Primary fuses on power supply unit
AUMA Art. No.:
F1/F2
G fuses
6.3 x 32 mm
Size
K002.277
1 A T; 500 V
Reversing contactors
Power supply
≤
500 V
K002.665
2 A FF; 690 V
Reversing contactors
Power supply > 500 V
F3
Internal 24 V DC supply
AUMA Art.no.:
F3
G fuse according to IEC 60127-2/III
5 x 20 mm
Size
K001.183
500 mA T; 250 V
Voltage output (power supply unit) = 24 V
K001.183
500 mA T; 250 V
Voltage output (power supply unit) = 115 V
F4
Internal 24 V AC supply (115 V AC) for:
●
Heater, switch compartment, reversing contactors control
●
PTC tripping device
●
for 115 V AC also control inputs OPEN - STOP - CLOSE
AUMA Art.no.:
F4
G fuse according to IEC 60127-2/III
5 x 20 mm
Size
K004.831
K003.131
1.0 A T; 250 V
1.6 A T; 250 V
Voltage output (power supply unit) = 24 V
K003.021
0.4 A T; 250 V
Voltage output (power supply unit) = 115 V
Information
Only replace fuses with fuses of the same type and value.
→
After replacing the fuses, screw local controls back on again.
Cable damage due to twisting or pinching!
Risk of functional failures.
→
Turn local controls by a maximum of 180°.
→
Carefully assemble local controls to avoid pinching the cables.
11.2.2
Motor protection (thermal monitoring)
In order to protect against overheating and impermissibly high surface temperatures
at the actuator, PTC thermistors or thermoswitches are embedded in the motor
52