34
4.3.2 Limit close calibration
a.
The LCD screen shows the current value Close Limit.
b.
Press CLOSE push button to run the actuator in Close direction. Press "STOP"
button to stop the actuator before reaching end travel.
c.
Engage Manual operation, Turn the hand wheel until valve is completely Closed.
d.
Confirm the calibration by giving "yes" by pressing "OPEN" key and " STOP" to
store.
e.
Press STOP key to accept the Close Limit Value.
f.
Follow the flow chart mentioned below.