Technical data
Table 9:
Electrical connection via AUMA plug/socket connector
Control contacts
Power contacts
50 pins/sockets
6 (3 equipped) + protective
earth conductor (PE)
No. of contacts max.
1 to 50
U1, V1, W1, U2, V2, W2, PE
Designation
250 V
750 V
Connection voltage max.
16 A
25 A
Rated current max.
Screw connection, crimp-type (option)
Screw connection
Type of customer connection
2.5 mm
2
(Flexible or solid)
6 mm
2
(flexible)
10 mm
2
(solid)
Connection diameter max.
Brass, tin plated or gold plated (option)
Brass
Material - contacts
Information
For some special motors, the connection of the power terminals (U1, V1, W1, U2,
V2, W2) is not performed via the AUMA plug/socket connector but via a terminal
board directly at the motor.
5.2.1.
Terminal compartment : open
Figure 18: Open terminal compartment
[1]
Cover (figure shows S version)
[2]
Screws for cover
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Cable entry
[7]
Blanking plugs
[8]
Cable gland (not included in delivery)
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
1.
Loosen screws [2] and remove cover [1].
2.
Loosen screws [4] and remove socket carrier [5] from cover [1].
23
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
SEM 01.1/SEM 02.1
Electrical connection