AUMA PF-M100 Series Short Instructions Download Page 9

4.

Parameter (Profibus DP)

Signals

Feedback signals via fieldbus are defined by the GSD file.

Information

If required, download the GSD file (General Station Description) from the Internet:
www.auma.com

Refer to Technical data of the actuator for the Profibus DP ident no.

Fieldbus address (Slave address)

Via AUMA Assistant App or AUMA CDT software:

DIS_53 Configuration

DIS_600 Profibus

PRM_1321 DP1 slave address

Default value:

126

Setting range:

0 ... 126

For information on the feedback signals via fieldbus and the configuration of the
parameters via fieldbus interface, refer to Manual “PROFOX Device integration
Profibus DP”.

Information

Profibus DP address setting is carried out via parameter (AUMA CDT software or
AUMA Assistant App)

Change-over between fieldbus control and OPEN-CLOSE via I/O signals (for
actuators with fieldbus interface)

As standard, the actuator is supplied with fieldbus and binary signals. A digital input
is used to define which source is active, this means whether the actuator is controlled
via fieldbus or via I/O signals. It is not possible to use both sources to active
simultaneously. The 

PRM_926 Signal DIN 3

 signal is assigned to 

PZD_275 I/O

interface

 as factory setting:

Not live (= 0 V) means that control is made from REMOTE via fieldbus.

Live (= 24 V) means that control is made from REMOTE via binary I/O signals.

Commands for the operation function:

OPEN-CLOSE operation commands can be issued via fieldbus or a setpoint can be
sent for any position. Change-over is made via the 

PZD_332 Fieldbus SETPOINT

command.

Setpoint control:

Fieldbus SETPOINT

 command bit = 1 = REMOTE SETPOINT

The actuator reacts to the setpoint E1 transmitted via the fieldbus.

OPEN-CLOSE control:

Fieldbus SETPOINT

 command bit = 0 = REMOTE OPEN-CLOSE

Actuator can be operated via 

Fieldbus OPEN

/

Fieldbus CLOSE

 command bits

in direction OPEN or CLOSE.

For further information on these parameters as well as on other settings, refer
to the Manual PROFOX “Parameters and functions”.

9

Parameter (Profibus DP)

Summary of Contents for PF-M100 Series

Page 1: ...ith operation instructions only These short instructions are only complete with the respective operation instructions of the actuator Safety and warning instructions contained in the actuator operatio...

Page 2: ...e of contents Page 3 1 Basic information on fieldbus connection 4 2 Cable connection 7 3 Connect fieldbus cables 9 4 Parameter Profibus DP 10 5 Technical data 10 5 1 PROFOX Profibus DP 2 Table of cont...

Page 3: ...0 MHz Impedance 30 pF per metre Cable capacity 0 64 mm Wire diameter 0 34 mm corresponds to AWG 22 Cross section 110 Ohm per km Loop resistance CU shielding braid or shielding braid and shielding foil...

Page 4: ...eding the following order 1 If a signal cable is connected in addition to the fieldbus cable Insert signal cable into cable gland on the right and push upward until the cable is visible 2 Insert field...

Page 5: ...th connection example Table 2 Terminal cross sections and tightening torques of PE connection Tightening torques Terminal cross sections Designation 3 4 Nm Standard version 1 0 6 mm 2 flexible via spa...

Page 6: ...crewdriver and always carefully remove signal cables It must be possible to pull out the signal cable without resistance when the push in terminal held down Information To avoid unevenness at wire end...

Page 7: ...last fieldbus device termination must be activ ated from the previous device to the next device In case of a fault electric shock due to presence of hazardous voltage if the PE conductor is NOT connec...

Page 8: ...tic sleeve AWG 16 AWG 20 AWG Bus termination 5 If the actuator is the last fieldbus device within the fieldbus segment Activate parameter or function PRM_5559 Bus termination channel 1 via AUMA Assist...

Page 9: ...nary signals A digital input is used to define which source is active this means whether the actuator is controlled via fieldbus or via I O signals It is not possible to use both sources to active sim...

Page 10: ...ehaviour on loss of communication General Profibus DP interface data Profibus DP according to IEC 61158 and IEC 61784 1 Communication protocol Line fieldbus structure When using repeaters tree structu...

Page 11: ...11...

Page 12: ...er GmbH Co KG P O Box 1362 DE 79373 Muellheim Tel 49 7631 809 0 Fax 49 7631 809 1250 info auma com www auma com Y009 651 003 en 1 22 For detailed information on AUMA products refer to the Internet www...

Reviews: