AUMA PF-M100 Series Short Instructions Download Page 10

5.

Technical data

Information

The following tables include standard and optional features. For detailed information
on the customer-specific version, refer to the order-related data sheet. The technical
data sheet can be downloaded from the Internet in both German and English at ht-
tp://www.auma.com
 (please state the order number).

5.1.

PROFOX Profibus DP

Setting/programming the Profibus DP interface

Automatic baud rate recognition

Baud rate setting

The setting of the Profibus DP address is made via parameters using the AUMA Software CDT or AUMA
Assistant App.

Setting the Profibus DP interface

Commands and signals of the Profibus DP interface

OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command

Process representation output
(command signals)

End positions OPEN, CLOSED

Actual position value

Selector in position LOCAL/REMOTE/OFF

Torque switches OPEN, CLOSED

Limit switches OPEN, CLOSE

Process representation input
(feedback signals)

Torque switch tripped in mid-travel

Process representation input
(fault signal)

The behaviour of the actuator is programmable:

Stop at current position

Execute operation to end positions OPEN and CLOSED

Travel to any intermediate position

Execute last received operation command

Behaviour on loss of communication

General Profibus DP interface data

Profibus DP according to IEC 61158 and IEC 61784-1

Communication protocol

Line (fieldbus) structure. When using repeaters, tree structures can also be implemented. If a unit fails,
communication in the line is still maintained.

Network topology

Twisted, screened copper cable according to IEC 61158

Transmission medium

EIA-485 (RS485)

Fieldbus interface

Baud rate and maximum cable length (segment length) without repeater:

-

between 9.6 and 93.75 kbit/s: 1,200 m

-

for 187.5 kbit/s: 1,000 m

-

for 500 kbit/s: 400 m

-

for 1,500 kbit/s: 200 m

Baud rate and possible cable length with repeater (total network cable length):

-

between 9.6 and 93.75 kbit/s: approx. 10 km

-

for 187.5 kbit/s: approx. 10 km

-

for 500 kbit/s: approx. 4 km

-

for 1,500 kbit/s: approx. 2 km

Transmission rate/cable length

DP master class 1, e.g. central controllers such as PLC, PC,.

DP master class 2, e.g. parts programming/configuration tools

DP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors

Device type

32 devices without repeater, with repeater expandable to 126

Number of devices

Token-passing between masters and polling for slaves

Mono-master or multi-master systems are possible.

Bus access

Cyclic data exchange, sync mode, freeze mode, fail safe mode

Supported fieldbus functions

0x1146. Standard applications with Profibus DP-V0 and DP-V1

Profibus DP ident no.

10

Technical data

Summary of Contents for PF-M100 Series

Page 1: ...ith operation instructions only These short instructions are only complete with the respective operation instructions of the actuator Safety and warning instructions contained in the actuator operatio...

Page 2: ...e of contents Page 3 1 Basic information on fieldbus connection 4 2 Cable connection 7 3 Connect fieldbus cables 9 4 Parameter Profibus DP 10 5 Technical data 10 5 1 PROFOX Profibus DP 2 Table of cont...

Page 3: ...0 MHz Impedance 30 pF per metre Cable capacity 0 64 mm Wire diameter 0 34 mm corresponds to AWG 22 Cross section 110 Ohm per km Loop resistance CU shielding braid or shielding braid and shielding foil...

Page 4: ...eding the following order 1 If a signal cable is connected in addition to the fieldbus cable Insert signal cable into cable gland on the right and push upward until the cable is visible 2 Insert field...

Page 5: ...th connection example Table 2 Terminal cross sections and tightening torques of PE connection Tightening torques Terminal cross sections Designation 3 4 Nm Standard version 1 0 6 mm 2 flexible via spa...

Page 6: ...crewdriver and always carefully remove signal cables It must be possible to pull out the signal cable without resistance when the push in terminal held down Information To avoid unevenness at wire end...

Page 7: ...last fieldbus device termination must be activ ated from the previous device to the next device In case of a fault electric shock due to presence of hazardous voltage if the PE conductor is NOT connec...

Page 8: ...tic sleeve AWG 16 AWG 20 AWG Bus termination 5 If the actuator is the last fieldbus device within the fieldbus segment Activate parameter or function PRM_5559 Bus termination channel 1 via AUMA Assist...

Page 9: ...nary signals A digital input is used to define which source is active this means whether the actuator is controlled via fieldbus or via I O signals It is not possible to use both sources to active sim...

Page 10: ...ehaviour on loss of communication General Profibus DP interface data Profibus DP according to IEC 61158 and IEC 61784 1 Communication protocol Line fieldbus structure When using repeaters tree structu...

Page 11: ...11...

Page 12: ...er GmbH Co KG P O Box 1362 DE 79373 Muellheim Tel 49 7631 809 0 Fax 49 7631 809 1250 info auma com www auma com Y009 651 003 en 1 22 For detailed information on AUMA products refer to the Internet www...

Reviews: