Protective earth connection
In case of a fault, electric shock due to presence of hazardous voltage if the
PE conductor is NOT connected!
Risk of death or serious injury!
→
Connect all protective earth conductors.
→
Connect PE connection to external protective earth conductor of connecting
cables.
→
Start running the device only after having connected the protective earth con-
ductor.
7.
Fasten PE using spade lugs or wire end sleeves at protective earth connection
( ) as shown. Do not completely loosen screw!
Figure 2: Protective earth connection (example)
Table 2:
Terminal cross sections and tightening torques of PE connection
Tightening torques
Terminal cross sections
Designation
3 – 4 Nm
Standard version: 1.0 – 6 mm
2
(flexible)
via spade lug or wire end sleeve
Explosion-proof version: 1.0 – 2.5 mm
2
(flexible) via spade lug or wire end sleeve
1.5 – 2.5 mm
2
(flexible) directly
Standard version: 1.5 – 6 mm
2
(rigid)
directly
Explosion-proof version: 1.5 – 2.5 mm
2
(rigid) directly
Protective earth connection
(PE)
Connection of mains and signal cables
8.
Connect mains cable according to order-related wiring diagram.
Table 3:
Terminal cross sections
Cross section
Wire type
Designation
max [mm²]
min [mm²]
2.5
0.08
rigid/flexible
Mains cable
AWG 12
AWG 28
AWG
5
Cable connection